TIMERS
TIMERS
GENERAL DETAILS
OF TYPE Q TIMERS
Q series timers are compact, low cost, precision devices designed to the most demanding
specifications. The small size, epoxy filled case is highly resistant against dust, vibrations,
shock and humidity. Creep and strike distance according to VDE 0110 Group C 250V. Case
protection IP66. Case material - Phenolic.
1.30
(33.2 mm)
2.00
(50.8mm)
.75
(19.05 mm)
2
2.00
(50.8mm)
250
(16.35 mm)
250 DIA. MALE QUICK CONNECT TERMINALS
(16.35 mm)
Function A:
QAS
SERIES
DELAY ON MAKE
Delay on Make
Input Power S1
Output
ELECTRONIC TIMER
UL listed
0
CSA recognized
SPECIFICATIONS:
Input Power . . . . . . . . . . . . . . . . . 24 VAC/DC, 110 VAC/DC
220 VAC/DC ±15%, 50/60 Hz
Output Rating . . . . . . . . . . . . . . . max.: 1.0 A at 20°C
min.: 10 mA
Voltage drop after timing . . . . . . 3.5 VAC/DC
Repetition accuracy . . . . . . . . . . ±0.5% at a constant ambient
Temp rise derating . . . . . . . . . . . 5 mA / °C
Reset time SAS & SAS-D . . . . . . 25 ms after timing
50 ms during timing
Leakage current during timing . . 5 mA max
Peak surge current . . . . . . . . . . . 20 A < 10 ms
Peak surge voltage . . . . . . . . . . . 1400 V, 10 µs
Terminals . . . . . . . . . . . . . . . . . . . 1/4˝ (6.35mm) quick connect
Operating temperature . . . . . . . . -22°F to +140°F (-30°C to +60°C)
Weight . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
T
Function A: When input power is applied, timing (t) begins. At the end
of the preselected time, the solid state SCR output turns on. The output turns off when the input power is removed, resetting the timer for
the next cycle.
WIRING DIAGRAM:
QAS
QAS-D
470K
RT
Peak Surge Current
1
20A
15A
10A
3
+-
100A
50A
˜
1
3
+- +-
˜˜
LOAD
+-
˜
LOAD
Peak Surge Current vs Surge Current Duration
5A
INPUT
INPUT
2A
1A
Note: Available with internal potentiometer in AS-P Series
10ms 20ms 50ms 100ms 200ms 500ms
1s 2s 5s
Surge Current Duration
ORDERING INFORMATION: (100 pcs. minimum)
P.S.: Specify maximum time for “D” and “P” version.
Q
AS-D
100S
220 AD
L
MOUNTING
SERIES
TIME RANGE
INPUT POWER
UL
Q = Encapsulated
AS = fixed time
AS-D = remote potentiometer
AS-P = internal potentiometer
AS = Fixed .1 sec - 120 min
AS-D = .1 sec - 60 min. 10:1 Ratio
AS-P = .1 sec - 10 sec
1-100 sec maintain 100:1 ratio
24AD = 24 VAC/DC
110AD = 110 VAC/DC
220AD = 220 VAC/DC
Products and specifications subject to change without notice.
2/46a
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
1 AMP
TIMERS
TIMERS
QBS
SERIES
SINGLE SHOT TIMER
QCS
SERIES
DELAY ON BREAK TIMER
UL listed
CSA recognized
• CMOS Technology
• Epoxy Encapsulated
• 2˝ x 2˝ Compact Size
• .250˝ Quick Connect Terminals
Function B:
Function C:
Single Shot
Delay on Break
Function B: Input power (S1) is continuously supplied to the timer. When
an external initiate switch (S2) is closed, momentarily or maintained, the
output relay is energized. At the end of the delay time (T), the output is
de-energized. The timer is ready for another cycle. Isolate the initiate
switch (S2) from other circuits.
Input
Power S1
Initiate
Switch S2
Function C: Input power (S1) is continuously supplied to the timer. When
an external initiate switch (S2) is closed, the output relay is energized.
Timing begins when the S2 switch opens. At the end of the delay time (T),
the output is de-energized and the timer is ready for another cycle. Isolate
the initiate switch (S2) from other circuits.
Relay
T
T
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC, 48 VAC, 110 VAC
220 VAC, ±15%, 50/60 Hz
Maximum power consumption . . . 24 VAC: 0.2 VA
48 VAC: 0.3 VA
110 VAC: 0.6 VA
220 VAC: 1.2 VA
Output . . . . . . . . . . . . . . . . . . . . . . SCR
Output Rating . . . . . . . . . . . . . . . . max.: 1A at 20°C
min.: 10 mA
Voltage drop after timing . . . . . . . . 3.5 V max. AC
Repetition accuracy . . . . . . . . . . . ±0.5% at a constant ambient
Temp. rise derating . . . . . . . . . . . . 5 mA / °C
Reset time . . . . . . . . . . . . . . . . . . . 80 ms
Minimum contact closure . . . . . . . 100 ms during timing
Leakage current during timing . . . 5 mA max.
Peak surge current . . . . . . . . . . . . 20 A < 10 ms
Peak surge voltage . . . . . . . . . . . . 1400 V, 100 µs
Terminals . . . . . . . . . . . . . . . . . . . . 1/4˝ (6.35) quick connect
Operating temperature . . . . . . . . . -22°F to +140°F -30°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
WIRING DIAGRAM:
QCS
QBS
Initiate
Switch
S2
˜
QCS-D
Initiate
Switch
S2
6
˜
1
2
3
˜
QBS-D
˜
R = 470K
6
5
4
1
2
3
Load
Load
Input
Input
The initiate switch should be isolated from the other circuits. Contact will
operate on the same supply as the timer and will have a max. load of 5 mA.
NOTE: Available with internal potentiometer in B or CS-P Series.
The remote potentiometer for the QCS-D and QBS-D should be 470 kΩ, 1/4 W.
Use with shielded cable at a maximum length of 50 feet.
DIMENSIONS See page 4-34
ORDERING INFORMATION: (100 pcs. minimum)
Q
CS
B
110A
MOUNTING
SERIES
TIME RANGE
INPUT POWER
Q = Encapsulated
CS = Fixed time
BS = Fixed time
CS-D = Remote potentiometer
BS-D = Remote potentiometer
CS-P = Internal potentiometer
BS-P = Internal potentiometer
CS/BS = Fixed time
CS-D = .06 sec. - 120 min
BS-D = .06 sec. - 120 min. maintain 10:1 ratio
B or CSP = .1 - 10 sec. or min
1 - 100 sec. or min. maintain 100:1 ratio
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
2/46b
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
L
UL
1 AMP
TIMERS
TIMERS
QDS
SERIES
REPEAT CYCLE
QHS
SERIES
INTERVAL ELECTRONIC TIMER
UL listed
CSA recognized
• Consistent Repeat Cycle
• Multiple Voltage
• 2˝ Square Cases
• Fixed and Variable Time Ranges
Function D:
Function H:
Recycling
Interval Timer
Function H: The solid state output turns on when the input power
(S1) is applied. The output turns off at the end of time (T). The timer
is reset when the input power is removed.
Input
Power S1
Output
0
T1
T2
t
T
0
Function D: When input power (S1) is applied, the sold state output
turns on immediately for the time period specified. It then turns OFF
for that same time period and repeats continuously while power is
applied.
t
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC, 48 VAC, 110 VAC
220 VAC, ±15%, 50/60 Hz
Maximum power consumption . . . 24 VAC: 0.2 VA
48 VAC: 0.3 VA
110 VAC: 0.6 VA
220 VAC: 1.2 VA
Output . . . . . . . . . . . . . . . . . . . . . . SCR
Output Rating . . . . . . . . . . . . . . . . max.: 1 A at 20°C
min.: 10 mA
Voltage drop after timing . . . . . . . . 3.5 VAC
Repetition accuracy . . . . . . . . . . . ±0.5% at a constant ambient
Temp. rise derating . . . . . . . . . . . . 5 mA / °C
Reset time . . . . . . . . . . . . . . . . . . . 100 ms after timing
150 ms during timing
Minimum contact closure . . . . . . . 100 ms during timing
Leakage current during timing . . . 2 mA max.
Peak surge current . . . . . . . . . . . . 20 A < 10 ms
Peak surge voltage . . . . . . . . . . . . 1400 V, 100 µs
Terminals . . . . . . . . . . . . . . . . . . . . Faston 1/4˝ (6.35)
Operating temperature . . . . . . . . . -22°F to +140°F -30°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
WIRING DIAGRAM:
QDS
QHS
QDS-D
QHS-D
470K
RT
5
˜
1
2
3
˜
˜
4
1
2
3
˜
Load
Load
Input
Input
NOTE: Available with internal potentiometer in HS-P Series.
DIMENSIONS See page 4-34
ORDERING INFORMATION: (500 pcs. minimum)
Q
DS
MOUNTING
SERIES
MOUNTING
Q = Encapsulated
DS
DS-D
HS
HS-D
DS-P
HS-P
= Fixed time
= Remote potentiometer
= Fixed time
= Remote potentiometer
= Internal potentiometer
= Internal potentiometer
SERIES
10 min
24A
TIME RANGE
INPUT POWER
TIME RANGE
INPUT POWER
DS/HS = Fixed .1s - 120 min.
DS-D/HS-D = .1 sec - 120 min. maintaining 10:1 ratio
DS-P/HS-P = .1-10 sec or min
1-100 sec. or min. maintain 100:1 ratio
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/46c
2
TIMERS
TIMERS
GENERAL DETAILS
OF TYPE S TIMERS
S series are compact, low cost, precision devices designed to the most
demanding specifications. The small size, epoxy filled case is highly resistant
against dust, vibrations, shock or humidity. Creep and strike distance according
to VDE 0110 Group C 250V. Case protection IP66. Case material - Polymid.
1.96
(50)
0.47
(12)
0.8
0.77
(45)
2.46
(62.5)
0.16
(42)
0.69
(17.5)
6.35
2.76
(70)
2.36
(60)
2
SAS
SERIES
DELAY ON MAKE
Function A:
Delay on Make
Input Power S1
TIMER WITH SOLID
STATE OUTPUT
UL listed
Output
0
T
CSA recognized
SPECIFICATIONS:
Function A: When input power is applied, timing (t) begins. At the end
of the preselected time, the solid state SCR output turns on. The output turns off when the input power is removed, resetting the timer for
the next cycle.
Input Power . . . . . . . . . . . . . . . . . . 24 VAC/DC, 110 VAC/DC
220 VAC/DC, ±15%, 50/60 Hz
Output Rating . . . . . . . . . . . . . . . . max.: 0.7 A at 20°C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . min.: 10 mA
Repetition accuracy . . . . . . . . . . . ±0.5% at a constant ambient
Temp rise derating . . . . . . . . . . . . 5 mA / °C
Reset time SAS & SAS-D . . . . . . . 25 ms after timing
100 ms during timing
SAS-P . . . . . . . . . . . . . 100 ms during timing
Leakage current during timing . . . 5 mA max
Peak surge current . . . . . . . . . . . . 20 A < 10 ms
Peak surge voltage . . . . . . . . . . . . 1400 V, 10 µs
Terminals . . . . . . . . . . . . . . . . . . . . 1/4˝ (6.35mm) quick connect
Opertating temperature . . . . . . . . . -22°F to +140°F (-30°C to +60°C)
Weight . . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
WIRING DIAGRAM:
+-
˜
SAS
SAS-D
S1
SAS-P
S1
S1
470K
POTENTIOMETER
A1 A2
Peak Surge Current
A1 A2 Z1 Z2
A1 A2
100A
50A
20A
15A
10A
Peak Surge Current vs Surge Current Duration
LOAD
5A
LOAD
LOAD
2A
1A
10ms 20ms 50ms 100ms 200ms 500ms
1s 2s 5s
+-
Surge Current Duration
˜
ORDERING INFORMATION: (500 pcs. minimum order, 250 pcs. minimum release)
S
AS-D
100S
220 AD
MOUNTING
MOUNTING
S =Encapsulated requiring
DIN-Rail, Panel Adapter
or use Base Mounting
Holes
SERIES
AS = standard relay
AS-D = remote potentiometer
AS-P = internal potentiometer
SERIES
TIME RANGE
INPUT POWER
TIME RANGE
AS = Fixed .1 sec - 1 min
AS-D = .1 sec - 60 min
Ex: = 10-100 sec maintain 10:1 ratio
AS-P = .1 sec - 10 sec
1-100 sec maintain 100:1 ratio
INPUT POWER
24AD = 24 VAC/DC
110AD = 110 VAC/DC
220AD = 220 VAC/DC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/43
TIMERS
TIMERS
SDS
SERIES
REPEAT CYCLE TIMER
UL listed
CSA recognized
• Shock Resistant
• SCR Solid State Output
• Optional Remote Potentiometer
• DIN-Rail or Base Mounting
When input power S1 is applied, the solid state output turns on
immediately for the timer period specified. It then turns OFF for that
same time period and repeats continuously while power is applied.
Recycling
Input Power S1
Output
0
T
t
T
SPECIFICATIONS:
WIRING DIAGRAM:
Input
. . . . . . . . . . . . . . . . . . . . . . 24 VAC, 48 VAC, 110 VAC
220 VAC, ±15%, 50/60 Hz
Maximum power consumption . . 24 VAC: 0.2 VA
48 VAC: 0.3 VA
110 VAC: 0.6 VA
220 VAC: 1.2 VA
Output . . . . . . . . . . . . . . . . . . . . . SCR
Output Rating . . . . . . . . . . . . . . . max.: 0.7 A at 20°C
min.: 10 mA
Repetition accuracy . . . . . . . . . . ±0.5% at a constant ambient
Temp. rise derating . . . . . . . . . . . 5 mA / °C
Reset time . . . . . . . . . . . . . . . . . . 100 ms after timing
150 ms during timing
Leakage current during timing . . 2 mA max.
Peak surge current . . . . . . . . . . . 20 A < 10ms
Peak surge voltage . . . . . . . . . . . 1400 V, 100 µs
Terminals . . . . . . . . . . . . . . . . . . . Faston 1/4˝ (6.35mm)
Operating temperature . . . . . . . . -22°F to +140°F -30°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
SDS
SDSD
S1
SDSP
S1
470 K
S1
POTENTIOMETER
A2 18 A1
A2 18 A1 Z1 Z2
LOAD
A2 18 A1
LOAD
LOAD
ORDERING INFORMATION: (500 pcs. minimum order, 250 pcs. minimum release)
P.S.: Specify maximum time for “D” and “P” versions.
S
DS
10 min
24
MOUNTING
SERIES
TIME RANGE
INPUT POWER
MOUNTING
SERIES
TIME RANGE
S = Encapsulated, requiring
DIN-Rail, Panel Adapter or
use Base Mounting Holes
DS = Fixed time
DS-D = remote potentiometer
DS-P = internal potentiometer
DS = Fixed .1s. - 120 min
DS-D = .1 sec. - 120 min.
Maintain 10:1 ratio
DS-P = 1 -10 sec. or min., 10 - 100 sec. or min.
Maintain 100:1 ratio
DIMENSIONS See page 3-34
INPUT POWER
24A = 24 VAC
48A= 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/44
TIMERS
TIMERS
SHS
SERIES
INTERVAL TIMER WITH
SOLID STATE OUTPUT
UL listed
CSA recognized
• Epoxy Encapsulated
• DIN-Rail or Base Mounting
• Internal or External Time Set
• Fixed Time
2
The solid state output turns on when the input power (S1) is
applied. The output turns off at the end of time (T). The timer is
reset when the input power is removed.
Function H:
Internal Timer
Input Power S1
Output
t
T
0
SPECIFICATIONS:
WIRING DIAGRAM:
Input . . . . . . . . . . . . . . . . . . . . . . 24 VAC, 48 VAC, 110 VAC
220 VAC, ±15%, 50/60 Hz
Maximum power consumption . . 24 VAC: 0.2 VA
48 VAC: 0.3 VA
110 VAC: 0.6 VA
220 VAC: 1.2 VA
Output . . . . . . . . . . . . . . . . . . . . . SCR
Output Rating . . . . . . . . . . . . . . . max.: 0.7 A at 20°C
min.: 10 mA
Repetition accuracy . . . . . . . . . . ±0.5% at a constant ambient
Temp. rise derating . . . . . . . . . . . 5 mA / °C
Reset time . . . . . . . . . . . . . . . . . . 100 ms after timing
150 ms during timing
Leakage current during timing . 2 mA max.
Peak surge current . . . . . . . . . . . 20 A < 10 ms
Peak surge voltage . . . . . . . . . . . 1400 V, 100 µs
Terminals . . . . . . . . . . . . . . . . . . Faston 1/4˝ (6.35mm)
Operating temperature . . . . . . . . -22°F to +140°F
-30°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . 1.9 oz. (55g)
SHS
SHS-D
S1
SHS-P
S1
470 K
S1
POTENTIOMETER
A2 18 A1
A2 18 A1 Z1 Z2
LOAD
A2 18 A1
LOAD
LOAD
Note: Available with internal potentiometer in HS-P Series.
ORDERING INFORMATION: (500 pcs. minimum order, 250 pcs. minimum release)
P.S.: Specify maximum time for “D” and “P” versions.
S
HS-D
300S
220A
MOUNTING
SERIES
TIME RANGE
INPUT POWER
MOUNTING
SERIES
S = Encapsulated, requiring
DIN-Rail, Panel Adapter or
use Base Mounting Holes
HS = Fixed time
HS-D = remote potentiometer
HS-P = internal potentiometer
DIMENSIONS See page 3-34
TIME RANGE
HS = Fixed .1s. - 120 min
HS-D = .1 sec. - 120 min. Maintain 10:1 ratio
HS-P = 1 -10 sec. or min., 10 - 100 sec. or min.
Maintain 100:1 ratio
INPUT POWER
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/45
2
Control Relays
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/57
CONTROLS
CONTROLS
NNR
SERIES
LIQUID LEVEL CONTROL
PUMP UP OR DOWN
SWITCH SELECTABLE
UL listed
•
•
•
•
CSA recognized
10 Amp SPDT Rated
Sensitivity Adjustment 4.7 kΩ to 47 kΩ
One, Two or Three Probe Operation
24 VAC to 220 VAC Voltages
2
A - Pump down function: the output relay energizes when the liquid level
reaches the high or max. probe. It remains energized until the level is
below the low or min probe. The relay will remain de-energized until the
high level is again reached. This control may also be used with only two
probes by connecting the maximum and common terminals together.
The output is energized when the low probe is in contact with the liquid.
S
Max
min
LEVEL
R
S
LEVEL
R
0
t
B - Pump up function: when power is supplied to the unit, the output
relay is energized. When the level reaches the high probe the relay is
de-energized. The relay is energized again when the level falls below
the lob probe. The control may also be used with only two probes by
connecting the maximum and common terminals together. The output is
de-energized when the level reaches the low probe.
In both functions, If the container is conductive, It may be used as the
common probe in some applications
SPECIFICATIONS:
Input
. . . . . . . . . . . . . . . . . . . . . . 24, 48, 110, 220 VAC
±15% (50/60 Hz)
Maximum power consumption . . 24 VAC: 1.5 VA
48 VAC: 1.7 VA
110 VAC: 2 VA
220 VAC: 2 VA
Output . . . . . . . . . . . . . . . . . . . . . SPDT relay
Contact material . . . . . . . . . . . . . AgCdO (90/10)
Maximum loading . . . . . . . . . . . . 10 A AC resistive 1A DC inductive
Maximum switching voltage . . . . 250 VAC
30 VDC
Relay maximum power rating . . . 2500 VA
30 VDC
Mechanical life of relay . . . . . . . . 3 x 107 operations
Electrical life of relay . . . . . . . . . 2 x 105 at 2200 VA resistive load
Probe isolation . . . . . . . . . . . . . . . Switching contact: 2000 VA
Electrodes: 2000 VAC
Probe sensitivity . . . . . . . . . . . . . 4.7 K ohm to 47 K ohm
Probe voltage . . . . . . . . . . . . . . . 24 VAC, 60 Hz
Probe current . . . . . . . . . . . . . . . 2 mA max.
Operating temperature . . . . . . . . +14°F to 140°F -10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . 4.6 oz. (130g)
WIRING DIAGRAM:
AC
s
Pump Down (2)
Pump Up (1)
Common
Max Min
AC
DIMENSIONS:
3.62
(92)
Note: For best results use shielded cable with the probes and do not run probe
cables with other wires.
1.5
(38.1)
2.16
(55)
3
(76.2)
ORDERING INFORMATION:
N
NR
220A
MOUNTING
SERIES
INPUT POWER
SERIES
MOUNTING
N = Open PC Board
NR
Products and specifications subject to change without notice.
INPUT POWER
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/73
CONTROLS
CONTROLS
NRU
SERIES
LIQUID LEVEL CONTROL
PUMP UP
UL listed
•
•
•
•
•
CSA recognized
LED Relay Indicator
Three Styles
Pump Up Control
4.7 kΩ to 100 kΩ Sensitivity
10 Amp SPDT Relay
Control of conductive liquids (tap water, sea water, sewage,
chemical solutions, coffee, ice cream, etc.)
S
Max
min
LEVEL
The relay is energized when the level falls below the low level
probe. It de-energizes when the high level probe is reached.
The NRU will also control a single level. In this case, a single
probe is used and the relay operates when the probe is not
immersed. The Max terminal is connected to common with a
jumper.
R
S
LEVEL
R
0
In either case, a common electrode is needed if the container
is non-conductive.
t
SPECIFICATIONS:
WIRING DIAGRAM:
Input Power . . . . . . . . . . . . . . .24, 48, 110, 220 VAC, ±15% (50/60 Hz)
Maximum voltage . . . . . . . . . . .24 VAC: 1.5 VA
48 VAC: 1.7 VA
110 VAC: 2 VA
220 VAC: 2 VA
Output . . . . . . . . . . . . . . . . . . .SPDT Relay
Contact material . . . . . . . . . . .AgCdO
Maximum loading . . . . . . . . . .10A AC resistive
8A DC resistive
Maximum switching voltage . .250 VAC
80 VDC
Maximum power rating . . . . . .2500 VA
80 W
Electrical life . . . . . . . . . . . . . .2 x 105 at 2200 VA resistive load
Mechanical life . . . . . . . . . . . . .3 x 107 operations
Probe isolation . . . . . . . . . . . . .Electrodes: 2000 VAC
Probe sensitivity . . . . . . . . . . .4.7 K to 100 K ohms
Probe voltage . . . . . . . . . . . . . .24 VAC, 60 Hz
Probe current . . . . . . . . . . . . . .2 mA max.
Operating temperature . . . . . .+14°F to +140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . .7 oz. (200g)
DNRU
PNRU
LNRU
˜
S
S
S
Max C min
A1 11
C
min
Max
6
5
12 14
8
3
A2
4
7
4
R
C
1
6
R
2
10
2
5
3
9
R
Max min
1
11
7
8
˜
Note: The cable for probes (max 300ft) should be run in separate conduit. A
shielded cable is recommended.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting
L = 11 pin plug-in
P = 8 pin plug-in
P
NRU
220D
MOUNTING
SERIES
INPUT POWER
SERIES
NRU
INPUT POWER
24A = 24VAC
48A = 48VAC
110A = 110VAC
220A = 220VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/74
CONTROLS
CONTROLS
NR
SERIES
LIQUID LEVEL CONTROL
PUMP DOWN
UL listed
•
•
•
•
CSA recognized
24 VAC to 220 VAC Operating Voltages
4.7 kΩ to 100 kΩ Sensitivity
LED Relay Indicator
10 Amp SPDT Relay
2
S
Max
min
LEVEL
The output relay energizes when the liquid level reaches the high
probe. The relay de-energizes when the liquid falls below the low
probe. This control can also be used with only two probes by connecting the maximum and common terminals together. The output is
energized when the level reaches the low probe. In both functions,
if the container is conductive, it may be used as the common probe
in some applications.
R
S
LEVEL
R
0
t
SPECIFICATIONS:
WIRING DIAGRAM:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24, 48, 110, 220 VAC ±15% (50/60 Hz)
Maximum power consumption . . . 24 VAC: 1.5 VA
48 VAC: 1.7 VA
110 VAC: 2 VA
220 VAC: 2 VA
Output . . . . . . . . . . . . . . . . . . . . . . SPDT relay
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10A AC resistive 8A DC inductive
Maximum switching voltage . . . . . 250 VAC
250 VDC
Relay maximum power rating . . . . 2500 VA
80 W
7
Mechanical life of relay . . . . . . . . . 3 x 10 operations
Electrical life of relay . . . . . . . . . . . 2 x 105 at 2200 VA resistive load
Probe isolation . . . . . . . . . . . . . . . . Electrodes: 2000 VAC
Probe sensitivity . . . . . . . . . . . . . . 4.7 K to 100 K ohms
Probe voltage . . . . . . . . . . . . . . . . 24 VAC, 60 Hz
Probe current . . . . . . . . . . . . . . . . . 2 mA max.
Operating temperature . . . . . . . . . +14°F to 140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 4.6 oz. (130g)
DNR
LNR
PNR
˜
S
S
S
Max C min
A1 11
C
min
Max
6
5
12 14
8
3
6
R
2
10
1
1
11
Max min
5
3
9
R
2
A2
4
7
4
R
C
7
8
˜
ORDERING INFORMATION:
MOUNTING
D = DIN-rail or panel mounting
L = 11 pin plug-in
P = 8 pin plug-in
P
NR
110A
MOUNTING
SERIES
INPUT POWER
SERIES
INPUT POWER
NR
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/75
CONTROLS
CONTROLS
NRT
SERIES
LIQUID LEVEL CONTROL
CONSTANT LEVEL
PUMP UP
UL listed
•
•
•
•
CSA recognized
100 kΩ Sensitivity
10 Amp SPDT Relay
Maintain Constant Level
Four Mounting Options
2
The NRT series is applied for maintaining a constant level of
conductive liquid. When the liquid decreases below the probe,
the relay is energized after a 4 second time delay to avoid wave
disturbances. The relay de-energizes when the liquid reaches
the probe. A common electrode is needed if the container is
non-conductive.
s
Level
R
T
0
T
0.3 s
t
SPECIFICATIONS:
WIRING DIAGRAM:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC, 48 VAC, 110 VAC
220 VAC, ± 15%, 50/60 Hz
Maximum power consumption . . . 24 VAC: 1.5 VA
48 VAC: 1.7 VA
110 VAC: 2 VA
220 VAC: 2 VA
Output . . . . . . . . . . . . . . . . . . . . . . SPDT Relay
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 8 A Dc resistive
Maximum switching voltage . . . . . 250 VAC
250 VDC
Relay maximum power rating . . . . 2500 VA
80 W
Mechanical life of relay . . . . . . . . . 3 x 10 7 operations
Electrical life of relay . . . . . . . . . . . 2 x 10 5 at 2200 VA resistive load
Probe isolation . . . . . . . . . . . . . . . Switching contact 2000 VAC
Electrodes: 2000 VAC
Probe sensitivity . . . . . . . . . . . . . . 100 kΩ
Probe voltage . . . . . . . . . . . . . . . . 24 VAC, 60 Hz
Probe current . . . . . . . . . . . . . . . . . 1 mA max.
Operating temperature . . . . . . . . . +14°F to +140°F -10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
DNRT
LNRT
PNRT
˜
S
S
S
Max C
A1 11
C min max
C
6
5
R
12 14
8
3
6
R
2
10
1
5
3
9
R
2
A2
4
7
4
Max
1
11
7
8
˜
Note: The probe cables (max. 300ft) need not be shielded; however, it is
not advisable to run the probe cables with power cables. If shielded cable
is used, the shield and common should be connected.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail or panel mounting
L = 11 pin plug-in
P = 8 pin plug-in
N = open PC board
P
NRT
110A
MOUNTING
SERIES
INPUT POWER
SERIES
NRT = Enclosed
NNRT = Open PC board version mounting
dimensions same as NNR
INPUT POWER
24A = 24 VAC
48A = 48 VAC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/77
CONTROLS
CONTROLS
JR
SERIES
ALTERNATING RELAY
UL listed
•
•
•
•
CSA recognized
Duplex Alternating Control
SPDT or DPDT Control Relay
10 Amp Rated
Externally Controlled
The electronic alternating relay is designed to replace mechanical
style devices used in control applications requiring a duplexing
or alternating action of the control circuits to operate pumps,
compressors, etc. This is achieved by activating a control switch
which is common to one side of the input control voltage. The output
contact of the relay(s) change state when this switch is opened
(on de-energization of the control circuit). When the control initiate
switch is actuated and released or opened, the relay will change
state. The next time the initiate switch is actuated and released it
will change back to its original state. Two red LED’s located on the
top of the dust resistant enclosure provide the status of the relay.
SPECIFICATIONS:
WIRING DIAGRAM:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC/DC, 110, 220 VAC
± 15%, 50/60 Hz
Maximum power consumption . . . 24 VAC: 1.5 VA
110 VAC: 5 VA
220 VAC: 11 VA
Output . . . . . . . . . . . . . . . . . . . . . . SPDT 10 A resistive
DPDT 10 A resistive
DPDT 10 A crosswired
Minimum pulse . . . . . . . . . . . . . . . 30 ms
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
Maximum switching voltage . . . . . 250 VAC
250 VDC
Relay maximum power rating . . . . 2200 VA
80 W
Mechanical life of relay . . . . . . . . . 3 x 106 operations
Electrical life of relay . . . . . . . . . . . 2 x 105 at 2200 VA resistive load
Operating temperature . . . . . . . . . 14°F to 140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 2.8 oz. (100g)
PJR
PJRX
INITIATE
SWITCH
4
LJR2
INITIATE
SWITCH
*
5
4
5
3
6
3
6
2
7
2
7
1
1
8
6
5
4
8
3
9
10
2
8
*
7
1
11
INITIATE SWITCH*
* INITIATE SWITCH must be isolated from other circuits
ORDERING INFORMATION:
MOUNTING
L = 11 pin plug-in
P = 8 pin plug-in
L
JR2
110A
MOUNTING
SERIES
INPUT POWER
SERIES
INPUT POWER
JR2 = DPDT (LJRZ only)
JR = SPDT
JRX = DPDT crosswired
24A = 24 VAC/DC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/78
CONTROLS
CONTROLS
JRS
SERIES
ALTERNATING RELAY WITH
SELECTOR SWITCH
UL listed
•
•
•
•
•
Duplex Alternating Control
SPDT or DPDT Control Relay
10 Amp Rated
Externally Controlled
Selection of Lead or Lag Load
2
The electronic alternating relay is designed to replace mechanical
style devices used in control applications requiring a duplexing
or alternating action of the control circuits to operate pumps,
compressors, etc. This is achieved by activating a control switch
which is common to one side of the input control voltage. The
output contact of the relay(s) change state when this switch is
opened (on de-energization of the control circuit). When the control
initiate switch is actuated and released or opened, the relay will
change state. The next time the initiate switch is actuated, it will
change back to its original state. Two red LED’s located on the top
of the dust resistant enclosure provide the status of the relay. A 3
Position Selector switch is installed for selection of normal operation (alternating) or selection of lead or lag load.
SPECIFICATIONS:
WIRING DIAGRAM:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC/DC, 110, 220 VAC
±15%, 50/60 Hz
Maximum power consumption . . . 24 VAC: 1.5 VA
110 VAC: 5 VA
220 VAC: 11VA
Output . . . . . . . . . . . . . . . . . . . . . . SPDT 10 A resistive
DPDT 10 A resistive
DPDT 10 A crosswired
Minimum pulse . . . . . . . . . . . . . . . 30 ms
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
Maximum switching voltage . . . . . 250 VAC
250 VDC
Relay maximum power rating . . . . 2200 VA
80 W
Mechanical life of relay . . . . . . . . . 3 x 106 operations
Electrical life of relay . . . . . . . . . . . 2 x 105 at 2200 VA resistive load
Operating temperature . . . . . . . . . 14°F to 140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 2.8 oz. (100g)
PJRS
PJRXS
LJRS2
INITIATE
SWITCH
INITIATE
SWITCH
4
5
4
5
6
3
6
2
7
2
7
1
1
8
6
5
3
8
7
4
8
3
9
10
2
1
11
INITIATE SWITCH
ORDERING INFORMATION:
L
JRS 2
110A
MOUNTING
SERIES
INPUT POWER
SERIES
MOUNTING
LJRS 2 = DPDT
PJRS = SPDT
PJRXS = DPDT (crosswired)
L = 11 pin plug-in
P = 8 pin plug-in
NOTE: DPDT relay available only with 11 pin plug-in (L).
INPUT POWER
24A = 24
VAC/DC
110A = 110 VAC
220A = 220 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/79
CONTROLS
CONTROLS
WRA
SERIES
PHASE CONTROL RELAY
UL listed
CSA recognized (220 VAC Version Only)
• Monitors
Phase Sequence
Loss of Any Phase even if Induced Voltage
reaches 95% of Nominal Voltage
• LED Relay Status Indicator
• SPDT 10 Amp Relay Output
MODE OF OPERATION:
RST
RTS
WIRING DIAGRAM:
RST
RS
N
R
S
T
T
R = L1
S = L2
T = L3
R
D1
11
The WRL Phase Control Relay monitors the sequence loss or reversal
of three phase power supplies. The output relay is energized when
the phase sequence is correct and is de-energize when the phase
sequence is wrong or one phase is lost. It monitors the symmetry
of 3 voltages and a loss of phase even when the voltage is reinjected
through a machine. The rate of asymmetry is controlled between 5%
and 15% by a top mounted potentiometer.
R
S
T
12 14
STOP
SPECIFICATIONS:
d1
START
Input Power Directly . . . . . . . . 3 x 220 60 Hz
from controlled voltage ±15%
3 x 380 60 Hz
3 x 440 60 Hz
Power consumption . . . . . . . . . 3 VA at 220 V
Output . . . . . . . . . . . . . . . . . . . SPDT relay
Contact material . . . . . . . . . . . AgCdO
Maximum Loading . . . . . . . . . 10 AC resistive
8A DC inductive
Maximum switching voltage . . 250 VAC
250 VDC
Relay max. power rating . . . . . 220 VA
80 W
Mechanical life of relay . . . . . . 30 x 106 operations
Electrical life of relay . . . . . . . . 2 x 105 operations at 2200VA resistive load
Operating temperature . . . . . . +14°F to +140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
U
V
W
M
DWRA
11
12
14
R
S
T
LWRA
1
4
3
5
6
7
PWRA
1
2
8
3
4
5
Note: The alarm threshold adjustment is 5% to 15% of asymmetry between
the phases. The initial response time is .1 seconds at 5% asymmetry and 1
second at 15% after input power is applied. When a phase loss or failure
occurs, the “off delay” response time is 100 ms.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting
L = 11 pin plug-in
P = 8 pin plug-in
L
WRA
380 A
MOUNTING
SERIES
INPUT POWER
SERIES
WRA
INPUT POWER
220A = 3 x 220 VAC
380A = 3 x 380 VAC
440A = 3 x 415/440 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/82
CONTROLS
CONTROLS
WRA
2
SERIES
PHASE CONTROL RELAY
UL listed
CSA recognized (220 VAC Version Only)
• Monitors
Phase Sequence
Loss of Any Phase even if Induced Voltage
reaches 95% of Nominal Voltage
• LED Relay Status Indicator
• DPDT 5 Amp Relay Output
2
MODE OF OPERATION:
RST
WIRING DIAGRAM:
RTS
RST
RS
N
R
S
T
T
R = L1
S = L2
T = L3
R
D1
The WRA 2 Phase Control Relay monitors the sequence loss or
reversal of three phase power supplies. The output relay is energized
when the phase sequence is correct and is de-energize when the phase
sequence is wrong or one phase is lost. It monitors the symmetry of
3 voltages and a loss of phase even when the voltage is reinjected
through a machine. The rate of asymmetry is controlled between 5%
and 15% by a top mounted potentiometer.
R
12 14 22
24
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
3 VA at 220 V
DPDT relay
AgCdO
5 A AC resistive
250 VAC
1250 VA
30 x 106 operations
2 x 105 operations at
+14°F to +140°F
7 oz. (200g)
T
d1
START
.
.
.
.
S
STOP
SPECIFICATIONS:
Power consumption . . . . . .
Output . . . . . . . . . . . . . . . .
Contact material . . . . . . . .
Maximum Loading . . . . . .
Maximum switching voltage
Relay max. power rating . .
Mechanical life of relay . . .
Electrical life of relay . . . . .
Operating temperature . . .
Weight . . . . . . . . . . . . . . . .
11 21
U
V
W
M
1 A DC inductive
250 VDC
30 W
2200 VA resistive load
-10°C to +60°C
DWRA 2
11
12
14
R
S
T
21
22
24
LWRA 2
1
4
3
5
6
7
11
8
9
Note: The alarm threshold adjustment is 5% to 15% of asymmetry between
the phases. The initial response time is .1 seconds at 5% asymmetry and
1 second at 15% after input power is applied. When a phase loss or failure
occurs, the “off delay” response time is 100 ms.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting or panel mounting
L = 11 pin plug-in
L
WRA 2
380 A
MOUNTING
SERIES
INPUT POWER
SERIES
WRA 2
INPUT POWER
220A = 3 x 220 VAC
380A = 3 x 380 VAC
440A = 3 x 415/440 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/83
CONTROLS
CONTROLS
WRS
SERIES
PHASE CONTROL RELAY
UL listed
CSA recognized
• Monitors
Phase Sequence
Loss of Any Phase
• LED Indicator
• 10 Amp SPDT Output
• Low Cost
MODE OF OPERATION:
RST
RTS
WIRING DIAGRAM:
RST
RS
N
R
S
T
T
R = L1
S = L2
T = L3
R
D1
11
The WRS Phase Control Relay monitors the sequence loss or reversal
of three phase power supplies. The output relay is energized when
the phase sequence is correct and is de-energize when the phase
sequence is wrong or one phase is lost.
R
S
T
12 14
STOP
SPECIFICATIONS:
Input Power Directly . . . . . . . . 3 x 220 60 Hz
from controlled voltage ±15%
3 x 380 60 Hz
3 x 440 60 Hz
Power consumption . . . . . . . . . 3 VA at 220 V
Output . . . . . . . . . . . . . . . . . . . SPDT relay
Contact material . . . . . . . . . . . AgCdO
Maximum Loading . . . . . . . . . 10 AC resistive
1 A SC inductive
Maximum switching voltage . . 250 VAC
250 VDC
Relay max. power rating . . . . . 2200 VA
30 W
Mechanical life of relay . . . . . . 30 x 106 operations
Electrical life of relay . . . . . . . . 2 x 105 operations at 2200 VA resistive load
Operating temperature . . . . . . +14°F to +140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
d1
START
U
V
W
M
DWRS
11
12
14
R
S
T
LWRS
1
4
3
5
6
7
PWRS
1
2
8
3
4
5
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting or panel mounting
L = 11 pin plug-in
P = 8 pin plug-in
L
WRS
380
MOUNTING
SERIES
INPUT POWER
SERIES
WRS
INPUT POWER
220A = 3 x 220 VAC
380A = 3 x 380 VAC
440A = 3 x 415/440 VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/84
CONTROLS
CONTROLS
IR.T
SERIES
CURRENT CONTROL RELAY
UL listed
•
•
•
•
•
CSA recognized
Automatic or Manual Control
Start-up Inhibit
Adjustable Hysteresis
Multiple Voltages
LED Relay Status Indicator
1. AC Current Control Without Latching:
The output relay is energized when the current (peak current on AC) overshoots the level selected on the potentiometer. It de-energizes when the
current falls below the normal current by 5 to 50% or when input power
breaks. The hysteresis is controlled by a top mounted potentiometer and
its selection does not change the chosen current level.
2. AC Current Control With Latching:
The output relay is energized when the current reaches the selected value
and stays latched. The contact between terminal B1 and B2 (or 11 and 9)
should be opened or input power to the device interrupted to reset. In this
case, it is preferable to reduce the hysteresis 5%.
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VDC, 24, 48, 110, 220 VAC
±15%, 50/60 Hz
Power consumption . . . . . . . . . . . 3 VA maximum
CONTROL RANGE
PERMITTED
OVERLOAD
DC
AC
INPUT
LESS THAN
CURRENT
CURRENT
RESISTANCE PERMANENTLY 1 sec Peak
5 to 100 mA 3.5 to 70.7 mA
1 ohm
1.5 V
5A
0.05 to 1 A 0.035 to 0.707 A 0.1 ohm
5A
17 A
0.5 to 10 A
0.35 to 7.07 A
0.01 ohm
15 A
55 A
Hysteresis selection . . . . . . . . . . . 5 to 50% of input current
Repeat accuracy . . . . . . . . . . . . . . ±2% at a constant ambient
Response time . . . . . . . . . . . . . . . . 100 ms On Make
200 ms On Break
Output Relay . . . . . . . . . . . . . . . . . SPDT Relay
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 1 A DC inductive
Maximum switching voltage . . . . . 250 VAC or DC
Relay maximum power rating . . . . 2500 VA
30W
Mechanical life of relay . . . . . . . . . 30 x 104 operations
Electrical life of relay . . . . . . . . . . . 2 x 105 at 2500 VA resistive load
Operating temperature . . . . . . . . . +14°F to + 140°F -10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
WIRING DIAGRAM:
(+)5 to 100mA ~
–
–
(+)0.05 to 1A ~
–
(+)0.5 to 10A ~
0V
(–)0V
0V
Note: Upon energization of the current control IR.T Series Relay,
the time delay, which is adjustable from .1 to 10 seconds, inhibits
the output relay during start-up periods. The delay time is adjustable
via a potentiometer located on the side of the case. Applies to both
versions, with and without latching.
Option: 24 VDC power - the voltage and the measured current must be
from separate sources.
Note: It is recommended that the unit be adequately fused.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting
L = 11 pin plug-in
L
IR.T
110A
MOUNTING
SERIES
INPUT POWER
SERIES
IR.T
INPUT POWER
24D
24A
48A
110A
220A
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/88
= 24VDC
= 24VAC
= 48VAC
= 110VAC
= 220VAC
CONTROLS
CONTROLS
IAR.T
SERIES
CURRENT CONTROL RELAY
UL listed
•
•
•
•
•
CSA recognized
Automatic or Manual Control
Start-up Inhibit
Adjustable Hysteresis
Multiple Voltages
5 to 100 Amp RMS
The DIAR.T is a current control which is capable of sensing up to 100
Amps. If requires a stepdown transformer, T1 100. The transformer
has a 0.4˝ diameter center hole through which a current carrying lead
is routed. Automatic or manual unlatching is available in each unit.
1. AC Current Control Without Latching:
The output relay is energized when the AC current overshoots the
level selected on the potentiometer. It de-energizes when the current
falls below the selected current by 5 to 50% or when input power
breaks. The hysteresis is controlled by a top mounted potentiometer
and its selection does not change the chosen current level.
2. AC Current Control With Latching:
The output relay is energized when the current reaches the selected
value and stays latched. The contact between terminal B1 and B2 (or
11 and 9) should be opened or input power to the device interrupted
to reset. In this case, it is preferable to reduce the hysteresis 5%.
2
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . . . 24 VDC, 24, 48, 110, 220 VAC
±15%, 50/60 Hz
Power consumption . . . . . . . . . . . . . . 3 VA maximum
Hysteresis selection . . . . . . . . . . . . . . 5 to 50% of input current
Repeat accuracy . . . . . . . . . . . . . . . . . ±2% at a constant ambient
±5% with temperature variation
VDE 0435
Response time . . . . . . . . . . . . . . . . . . 100 ms On Make
200 ms On Break
Output Relay . . . . . . . . . . . . . . . . . . . . SPDT Relay
Contact material . . . . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . . . . 10 A AC resistive
1 A DC inductive
Maximum switching voltage . . . . . . . . 250 VAC
30 VDC
Relay maximum power rating . . . . . . 2500 VA
30 W
Mechanical life of relay . . . . . . . . . . . 30 x 104 operations
Electrical life of relay . . . . . . . . . . . . . 2 x 105 at 2500 VA resistive load
Operating temperature . . . . . . . . . . . . +14°F to +140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
WIRING DIAGRAM:
TRANSFORMER: (Part Number 74 525 305)
Note: Upon energization of the current control IAR.T Series
Relay, the time delay, which is adjustable from .1 to 10 seconds,
inhibits the output relay during start-up periods. The delay time is
adjustable via a potentiometer located on the side of the case.
For additional current transformer see “Accessories” section:
L595 Series. Page 2/99
Current
Range: 5 to 100 A RMS
Maximum
Overload: 1 max = 150 A
ORDERING INFORMATION:
L
IAR.T
110A
MOUNTING
SERIES
INPUT POWER
INPUT POWER
MOUNTING
D = DIN-rail mounting
L = 11 pin plug-in
SERIES
IAR.T
24D = 24VDC
24A = 24VAC
48A = 48VAC
110A = 110VAC
220A = 220VAC
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/89
CONTROLS
CONTROLS
UR
SERIES
VOLTAGE CONTROL RELAY
UL listed
•
•
•
•
•
CSA recognized
AC or DC Voltage Control
Manual or Automatic Operation
Adjustable Threshold
5 to 50% Hysteresis Range
LED Relay Status Indicator
1. AC/DC voltage control without latching:
The output relay is energized when the voltage (AC peak voltage)
exceeds the selected threshold. It de-energizes when the voltage
falls below the hysteresis setting (5 to 50%) or when supply breaks.
The hysteresis is controlled by a potentiometer and its selection does
not change the chosen threshold.
2. AC/DC voltage control with latching:
The output relay is energized when the voltage reaches the selected
threshold and stays latched in this position. The contact between terminal B1 and M (or 8 or 9) should be opened or the input power of
the device interrupted to reset.
2
S1
hysteresis
Automatic
Unlatching
Threshold
R
S1
S2
Manual
Unlatching
Threshold
SPECIFICATIONS:
hysteresis
R
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VDC, 24, 48, 110, 220 VAC
±15%, 50/60 Hz
Power consumption . . . . . . . . . . . 24 VAC: 1 VA
48 VAC: 1.2 VA
110 VAC: 3.5 VA
220 VAC: 7 VA
Control
Input
Acceptance load (input)
Range
Resistance
Permanent
Less than
AC or DC
(max)
10ms peak max.
0.1 to 10 V
10 kΩ
50 V
100 V
0.4 to 40 V
40 kΩ
100 V
300 V
4 to 400 V
400 kΩ
440 V
750 V
Hysteresis selection . . . . . . . . . . . 5 to 50% of set point
Repeat accuracy . . . . . . . . . . . . . . ±2% at a constant ambient
Output Relay . . . . . . . . . . . . . . . . . SPDT Relay
Contact material . . . . . . . . . . . . . . AgCdO
Maximum loading . . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
Maximum switching voltage . . . . . 250 VAC
250 VDC
Relay maximum power rating . . . . 2200 VA
Transient protection . . . . . . . . . . . 2500 volts
30 W
Mechanical life of relay . . . . . . . . . 30 x 106 operations
Electrical life of relay . . . . . . . . . . . 2 x 105 at 2400 VA resistive load
Repetition accuracy . . . . . . . . . . . ±0.5% at a constant ambient
Response time . . . . . . . . . . . . . . . . 100 ms on make
200 ms on break
Operating temperature . . . . . . . . . -4°F to +140°F
-20°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
WIRING DIAGRAM:
˜+
DUR
LUR
(+)0.1 to 10v
(+)0.4 to 40v
(+)4 to 400v
S1
A1 11
(+)0.1 to 10v
(+)0.4 to 40v
(+)4 to 400v
(-)0v
S1
6
5
E1 E2 E3
7
4
3
8
10
2
12 14
B1
1
M A2
Latching
S2
Latching S2
9
R
11
(-)0v
˜-
Option: 24 VDC power – the voltage and the measured current must be
from separate sources.
ORDERING INFORMATION:
MOUNTING
D = DIN-rail mounting
L = 11 pin plug-in
D
UR
24A
MOUNTING
SERIES
INPUT POWER
SERIES
UR
UR SP50
Products and specifications subject to change without notice.
INPUT POWER
24A = 24VAC
24D = 24VDC
48A = 48VAC
110A = 110VAC
220A = 220VAC
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/93
CONTROLS
CONTROLS
SR
SERIES
UNDER VOLTAGE RELAY
UL listed
•
•
•
•
CSA recognized
Multiple AC/DC Voltages
5 to 20% Hysteresis Adjustment
Automatic Operation
Adjustable Threshold
Threshold
hysteresis
R
0
t
The voltage threshold SR Relay controls a voltage supply which
is its own supply. The output relay is energized when the supply
(effective for AC) exceeds the selected threshold. It de-energizes
when the controlled supply falls below (5 to 20% Hysteresis) of
the supply voltage or when the input power breaks. Hysteresis
is controlled by a potentiometer and its selection does not
change the chosen threshold. Pulses or drops of 100ms or
less are ignored.
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . .12 VDC, 24 VAC, 24 VDC, 48 VAC
48 VDC, 110 VAC, 220 VAC, 50/60 Hz
-20% to +30% DC,
-30% to +15% AC
Maximum power consumption . . .24 VAC: 1.5 VA
24 VDC: .6 W
. . . . . . . . . . . . . . . . . . . . . . . . . . . .48 VAC: 2 VA
24 VDC: .8 W
. . . . . . . . . . . . . . . . . . . . . . . . . . . .110 VAC: 5 VA
48 VDC: 1.8 W
220 VAC: 11 VA
Residual ripple . . . . . . . . . . . . . . .<Hysteresis value
Output relay . . . . . . . . . . . . . . . . . .SPDT Relay
Contact material . . . . . . . . . . . . . .AgCdO
Maximum loading . . . . . . . . . . . . .10 A AC resistive 8 A DC inductive
Maximum switching voltage . . . . .250 VAC
250 VDC
Maximum power rating . . . . . . . . .2200 VA
80 W
6
Mechanical life of relay . . . . . . . . .30 x 10 operations
Electrical life of relay . . . . . . . . . . .2 x 105 at 2200 VA resistive load
Operating temperature . . . . . . . . .+14°F to 140°F
-10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . . . . .2.8 oz. (100g)
DSR
PSR
LSR
˜+
S
S
S
A1 11
6
5
R
12 14
8
3
9
R
10
2
A2
4
7
4
1
11
5
3
6
R
2
1
7
8
˜–
ORDERING INFORMATION:
MOUNTING
D = DIN-rail or panel mounting
L = 11 pin plug-in
P = 8 pin plug-in
L
SR
24
MOUNTING
SERIES
INPUT POWER
SERIES
SR
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/94
INPUT POWER
12 = 12 VDC
24D = 24 VDC
24A = 24 VAC
48D = 48 VDC
48A = 48 VAC
110 = 110 VAC
220 = 220 VAC
CONTROLS
CONTROLS
Dimensions
2.76˝
(70mm)
D – Din Rail
L, P & K Socket
1.89˝
(48mm)
A 1 15
2.72˝
(69mm)
1.77˝
(45mm)
16
.43˝
(11mm)
.19˝
(5mm)
2.95˝
(75mm)
1.10˝
.14˝
(28mm) (3.5mm)
18
A2
.94˝
.94˝
(24mm) (24mm)
1.89˝
(48mm)
.08˝
(2mm)
.08˝
(2mm)
.43˝
(11mm)
2.93˝
(74.5mm)
4.05˝
(103mm)
O Socket
B – Din Rail
1.10˝
(28mm)
2.52˝
(64mm)
1.77˝
45mm
3.42˝
(87mm)
.69˝
(17.5mm)
.43˝
(11mm)
2.83˝
(72mm)
1.88˝
(48mm)
2.95˝
(75mm)
.43˝
(11mm)
.94˝
(24mm)
2.93˝
(74.5mm)
1.06˝
(27mm)
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/100

Documents pareils