Packaged Air Conditioning Unit

Transcription

Packaged Air Conditioning Unit
......................................................................................................................
RTU
Packaged Air Conditioning Unit
......................................................................................................................
RTU
....................................................................................................................................................
Packaged Air Conditioning Unit
....................................................................................................................................................
The Reznor RTU series
is a range of packaged
Air Conditioning units,
providing cooling and
heating.
Model Range
Reznor's range of high
efficiency packaged
rooftop units are available
in cooling only and
reversible modes. Both
are available with energy
recovery function as an
option.
>>
>>
RTU units come in different models with
cooling and heat pump capacities ranging
from 20 to 300 kW.
Features & Benefits
Acoustic jackets combined with
insulated compressor compartments
>>
Low noise variable speed condenser
fans providing energy efficient
operation and head pressure control
>>
Plug and play controls, compatible
with a range of BMS protocols
including Modbus, and BACnet
>>
Energy analyzer
>>
Variable speed EC fans
>>
Damper actuators
>>
Optimised design for R410A refrigerant
>>
High energy efficiency at both full
and part load operation to reduce
operating costs
>>
Low noise levels achieved through high
performance fans and use of antivibration blocks for the compressor
and refrigeration circuit assembly
>>
Centrifugal fans with optional EC
plug fans for both supply and exhaust
airflow
>>
Active heat recovery option available
to provide enhanced cooling and
heatpump performance
>>
Electronic Expansion Valves driver
modules
>>
Digital-scroll or Inverter Compressor
driver modules
>>
CO2 or VOC sensors and control
Controls
The Reznor RTU utilises Carel Microprocessor Controls to provide automatic operation
of cooling, ventilation, heating and heat
recovery operation. Additional control options inlcude :
>>
Remote control operation
>>
Temperature and/or humidity sensors
(up to 6 units)
..................................................................................................
Packaged Air Conditioning Unit
..................................................................................................
....................................................................................................................................................
Energy Efficiency Multiscroll Technology
Annual energy consumption kWh
Multiscroll technology combined with
electronic expansion valves (EEV) and
EC plug fans increase the system energy
efficiency and provide a resilient and reliable
solution.
Multiscroll technology +
Electronic Plug-fan
Thanks to the RTU's ability to produce its
output in smaller increments, spaces with
a variable occupancy rate and changing
conditions during the day, such as shopping
centres, can benefit from energy savings up
to 30%.
Standard
The RTU range of units come equipped
as standard with high efficiency G4 class
air filters. Fresh air & ventilation options
provide a high level of indoor air quality
and help ensure a clean and comfortable air
conditioned space.
Supply air fan
Compressors
Outdoor fan
Return air fan
The seasonal efficiency of multiscroll units
in tandem from four scroll AC compressors
is similar to the equipment with inverter
compressors. For units with less than four
compressors, high ESEER is achieved thanks
to Digital Scroll technology with refrigerant
flow control.
Comfort - Air Quality and
Low Level Noise
Up to 30% of
savings
Up
Up to
to 30%
30% of
of
savings
savings
0
50 000
100 000
150 000
Typical annual energy consumption for a commercial application
Seasonal efficiency comparison
40
30
Multiscroll
20
Optional pre-filters and F6 to F9 filters can
be provided.
10
The RTU rooftop can be equipped with
Axitop diffusers for the outdoor fans,
improving operational efficiency and
lowering noise levels.
0
Inverter
2
3
4
6
Number of compressors
Free cooling & heat recovery options
[DER] Dynamic Energy Recovery. A subcooler
in the DX circuit increases the unit's output by
15% without any additional compressors.
[AER+] Active Energy Recovery + Digital
Scroll: this is Active energy recovery by
a compressor group with Digital Scroll
technology and EC fan.
[AER] Active energy recovery using a separate
DX circuit to recover heat, suitable for exhaust
rates between 20 and 60% of airflow.
[ERH] Free Cooling using a two or three way
mixing box, with dampers and automatic
controls to use the outside air for free
IDA 3
IDA 4
[AERH] Enhanced
Active energy recovery
Commercial
industrial buil- cooling.
IDA
IDA 33to recover heat,
IDA 44
using a separate
DX circuit
buildings
dings IDA
Commercial
industrial
builCommercial
industrial
builsuitable for exhaust rates between 60 and
buildings
dings
buildings
dings
5
l/s
pers.
8
l/s
pers.
100% of airflow.
n minimum
ow
tilation minimum
ntilation
minimum
0,55 l/s m 2
88 l/s
l/s pers.
pers.
0,28 l/s m 2
55 l/s
l/s pers.
pers.
[ACS] Partial condensation energy recovery.
Includes a de-superheater that allows using
recovered heat for sanitary hot water.
[MSC] Multiscroll refrigerant circuit. Available
option for series 2000 and 3000, with
refrigerant circuit with two compressors in
tandem, increases seasonal energy efficiency
..................................................................................................
Packaged Air Conditioning Unit
..................................................................................................
3-way mixing box for freecooling and active recovery.
Low speed axial fans
settings
air quality
filters G4
F-class filtration
double F-class filtration
dirty filter indication
CO2 sensor duct/ambient
settings
air quality
filters G4
External coils
integrated in unit body
F-class filtration
double F-class filtration
Sound insulated scroll compressorsdirty
in filter indication
duct/ambient
included
as standard
included
as standard
closed and insulated compartment.CO2 sensor
settings
settings
VOC sensor duct/ambient
optionally
available
optionally
available
smoke detector
quality
airairquality
filters
filters
G4G4
ventilation
ventilation
energy
sensor
duct/ambient
COCO
sensor
duct/ambient
2
2
condensing
pressure
control
condensing
pressure
control
electronic expansion valve
supply/return
plug
supply/return
EC EC
plug
fanfan
active energy recovery
external
axial
external
axial
EC EC
fansfans
enhanced active recovery
Axitop
diffuser
Axitop
diffuser
active energy recovery + digital
scroll
VOC
sensor
duct/ambient
VOC
sensor
duct/ambient
free cooling thermal/enthalpy
smoke
detector
smoke
detector
total/partial recovery of condensation heat
F-class
filtration
F-class
filtration
double
F-class
filtration
double
F-class
filtration
dirty
filter
indication
dirty
filter
indication
installation
installation
energy
energy
active
energy
recovery
active
energy
recovery
enhanced
active
recovery
enhanced
active
recovery
active
energy
recovery
+ digital
active
energy
recovery
+ digital
scroll
scroll
cooling
thermal/enthalpy
freefree
cooling
thermal/enthalpy
total/partial
recovery
of contotal/partial
recovery
of condensation
heat
densation
heat
settings
energy
ventilation
electronic expansion valve
condensing pressure control
active energy recovery
supply/return EC plug fan
enhanced active recovery
external
axial EC
fans + digital
active energy
recovery
scroll
Axitop diffuser
free cooling thermal/enthalpy
Controls and electronic
total/partial recovery of concomponents
densation
heat
installation
stainless steel internal condensate tray
anti-corrosion
external condensate tray
hot water battery backup
polyurethane coating
electrical resistance heating
2-phase
copper-copper battery
antivibration supplement
ALUCOAT fins - CrMg alloy
antifreeze electrical resistances
Blygold
coating
for
low temperatures
control
stainless
internal
condensate
stainless
steelsteel
internal
condensate
traytray
Carel controls
external
condensate
external
condensate
traytray
RS485 communication
anti-corrosion
water
battery
backup
hothot
water
battery
backup
electronic
expansion
valve
electronic
expansion
valve
VOC sensor duct/ambient
included as standard
smoke detector
optionally available
electrical
resistance
heating
electrical
resistance
heating
2-phase
2-phase
polyurethane
coating
antivibration
supplement
antivibration
supplement
copper-copper battery
antifreeze
electrical
resistances
antifreeze
electrical
resistances
ALUCOAT
fins
- CrMg alloy
temperatures
forfor
lowlow
temperatures
PGD remote display
master-slave management
Plant Visor / Watch PRO
energy meter
BACnet / LonWorks communication
Blygold coating
settings
control
control
included as standard
included as standard
optionally available
optionally available
Double Filtration F
Double Filtration F
external axial fans E
Clogged Filter detectorClogged Filter detector
Axitop diffuser
..................................................................................................
Packaged Air Conditioning Unit
..................................................................................................
CO2 probe ambient/conduit
CO2 probe ambient/conduit
VOC probe ambient/conduit
VOC probe ambient/conduit
....................................................................................................................................................
Smoke Detector
Assembly type:
Supply
Supply
Smoke Detector
installatio
Assembly type
B - Lower
Return
Return
0 - Standard
A - Two way mixing box
S - Lateral
B - Lower
B - Axial return
C - Centrifugal return
E - Axial extraction
T - Upper
S - Lateral
D - Dynamic Recovery
A - Short side
(only with
plug ventilat.)
T - Upper
F - active recovery with
return fan
energy
A - Short side
R - Active recovery
E
energy
Return air
external condensate
B - Return EC plug fan
T
T
A
A
A
S recoverySactive energy
S
active energy
recovery
A
E
antivibration supple
B
antifreeze electrica
temperatur
active0 energy recovery active
+ digital
energy
recovery + digital for low
A
B B
scroll
scroll
C - Centrifugal return
B
E - Extract EC plug fan
freecooling thermal/enthalpy
freecooling thermal/enthalpy
E
S
total/partial Nrecovery oftotal/partial
conrecovery of condensation heat
densation heat
T
A
B
B
S C
anti-corrosion
anti-corrosion
F - Acti v e re co v e r y wi th re tur n fan
E
S
T
N
B E
communication
RS4
command PGD
supervision Plant Viso
copper-copper
batterycopper-copper battery
B
supervision tERA
ALUCOAST
fin - CrMgALUCOAST
alloy
S F fin - CrMg alloy
B F
energy meter
Blygold coating
communication BACN
B
T - Fresh air intake
B
platform CLIMANAG
PolyurethaneE coating Polyurethane
coating
A
S
B
E
master-slave manag
N
A
control
N
S
A
S
electrical resistance
N
phases)
A
S
enhanced Bactive recovery
enhanced
activeB recovery
B
B
S
Pressure relief
dampers
Exhaust air
N valve
electronic expansion valve
electronic expansion
A
S
T
T
stainless steel internal c
hot water battery b
A - Two way mixing box
T
Adjustable dampers
Fresh air
T - External air intake
Z - EC plug fan return
0 - Standard
N
Supply air
T
Blygold coating
Z - Return EC plug fan
T
T
N
A
S
A
B
S
B
T
N
A
S
E
B
B
B Z
..................................................................................................
Packaged Air Conditioning Unit
..................................................................................................
Technical Data
Model
Cooling Only
Cooling Capacity
Nomin. absorbed power Cooling
EER
Heat pump
Heat Capacity
Nomin. absorbed power Cooling
EER
Nomin. absorbed power Heating
COP
Airflow (m3/h)
0017
0020
0022
0026
0030
0035
1039
1044
kW
kW
17.8
4.9
3.6
20.7
5.8
3.6
23.1
6.4
3.6
25.8
7.0
3.7
30.5
8.5
3.6
34.2
9.3
3.7
41.3
12.5
3.3
46.2
13.3
3.5
kW
kW
17.8
5.3
3.6
4.9
4.1
20.7
6.2
3.6
5.5
4.2
32.1
6.4
3.6
6.9
39
25.8
7.7
3.7
7.1
4.1
30.5
9.2
3.6
8.4
4.1
34.2
11.1
3.7
10.8
4.0
40.6
12.9
3.1
11.7
3.5
46
13.9
3.3
13.8
3.4
Supply
3300
3700
4000
4600
5100
6000
6800
7400
Outdoor
9000
9500
14000
14000
14000
20000
20000
20000
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
kW
No.compressors /no. circuits
Stages
Weight
Sound pressure level @10m
1
1
1
1
1
1
1
1
Kg
489
495
504
521
538
561
641
660
dB(A)
48
49
49
52
55
57
57
58
Technical Data
Model
Cooling Only
Cooling Capacity
Nomin. absorbed power Cooling
EER
Heat pump
Heat Capacity
Nomin. absorbed power Cooling
EER
Nomin. absorbed power Heating
COP
Airflow (m3/h)
1041
1045
2050
2060
3070
3080
4090
4095
4100
kW
kW
42.5
12.2
3.5
47.1
13.4
3.5
52.6
16.8
3.1
66.4
18.5
13.6
74.3
20.8
3.6
80.8
23.4
3.5
95.5
27.6
3.5
95.3
27.4
3.5
105.8
31.2
3.4
kW
kW
41.6
13.2
3.2
12.9
3.3
45.9
14.6
3.1
14.8
3.2
52.2
17.6
3.0
15.0
3.5
60.1
19.5
3.1
17.9
3.5
71.3
22.2
3.2
20.6
3.6
77.1
25.2
3.1
23.0
3.5
91.4
29.2
31
27.0
3.4
90.4
29.5
3.1
28.9
3.2
99.8
32.4
3.1
31.0
3.3
kW
Supply
6800
7400
8900
10300
12000
13300
15400
15400
17700
Outdoor
20000
20000
25000
24000
26000
26000
36000
36000
36000
2/1
2/1
2/2
2/2
2/2
2/2
2/2
4/2
4/2
2
2
2
2
2
2
2
4
4
Kg
682
694
948
1075
1155
1210
1256
1419
1560
dB(A)
56
57
57
57
58
57
58
58
60
No.compressors /no. circuits
Stages
Weight
Sound pressure level @10m
Technical Data
Model
Cooling Only
Cooling Capacity
Nomin. absorbed power Cooling
EER
Heat pump
Heat Capacity
Nomin. absorbed power Cooling
EER
Nomin. absorbed power Heating
COP
Airflow (m3/h)
5120
5135
5140
5150
5170
6200
6230
kW
kW
123.6
35.4
3.5
144.0
41.7
3.5
149.8
43.8
3.4
159.8
45.8
3.5
182.1
57.5
3.2
208.9
63.6
3.3
230.5
76.5
3.0
kW
kW
118.9
40.2
3.0
37.8
3.1
134.0
45.1
3.0
40.8
3.5
144.4
48.9
3.0
43.7
3.4
155.1
49.5
3.1
46.4
3.4
173.4
60.0
2.9
53.4
3.4
200.6
65.3
3.1
63.7
3.3
218.7
78.7
2.8
81.7
2.9
Supply
19800
22700
23500
24900
28600
31900
36000
Outdoor
56000
56000
56000
56000
76000
76000
76000
4/2
4/2
4/2
4/2
4/2
4/2
4/2
4
4
4
4
4
4
4
2024
2093
2223
2140
2285
2579
2646
61
62
62
61
61
64
65
kW
No.compressors /no. circuits
Stages
Weight
Sound pressure level @10m
Kg
dB(A)
..................................................................................................
Packaged Air Conditioning Unit
..................................................................................................
ries 0 s eries 0
s eries 1 s eries 1
eries 0
s eries 1
Series 0
Series 1
H
H
H
H
H
H
L
L
L
L
L
L
RETORNO Y RETORNO Y
AIRE NUEVOAIRE NUEVO
RETORNO Y RETORNO Y
AIRE NUEVOAIRE NUEVO
A
Return Y
RETORNO
A
A
Return
RETORNO
Y
AIRE NUEVO
A
AIRE NUEVO
A
A
IMPULSIÓN IMPULSIÓN
IMPULSIÓN IMPULSIÓN
Supply
Supply
IMPULSIÓN
IMPULSIÓN
series 5-7series 5-7
ries 2-4series 2-4
Series 2-4
eries 2-4
H
Series 5-7
series 5-7
H
H
H
H
H
L
L
L
L
L
L
Return
RETORNO Y RETORNO Y
AIRE NUEVOAIRE NUEVO
A
Return
RETORNO Y RETORNO Y
AIRE NUEVOAIRE NUEVO
RETORNO Y
AIRE NUEVO
A
A
A
RETORNO Y
AIRE NUEVO
A
Supply
IMPULSIÓN IMPULSIÓN
A
Supply
IMPULSIÓN
IMPULSIÓN
IMPULSIÓN
IMPULSIÓN
Dimensions (mm)
Model
Series 0
Series Series
0
1
Series 0
DimensionsDimensions
standard units
standard
(mm)units (mm)
Series Series
1
2
Series 1
Series 2
Series Series
2
3
Series 3
Series Series
3
4
Series 4
Series Series
4
5
Series 5
Series Series
5
6
Series 6
Series Series
6
7
LL
L
2400
2400 2755
2400 2755Dimensions
2755
3055 4575 5175
4575
units
2755
2755 standard
2755 2755
2755(mm)
3055 27553055 4575
AA
A
Series 0
1370
Series 1
1370 2100
4
5
2100
2100 2 2100
2100 Series
2100 32100
2100 Series
2100 2100
2100 Series
2100
2100 Series
2100
1370 Series
2100
21006
2100 Series
2100 7
2100
2100
2100
H
2755
1175
1430 1555
6350
2490 2490
2200
2200
2200
HL
H
2400
1430
2755
1430 1175
A
1370
2100
H
1430
Series
0
Series Series
0 1175
1
2755
3055
4575
5175
1555 1810
1810 1810
1175
1555
18101810 2200
1810 2200 2490
2200
2100
2100
2100
2100
Dimensions
Dimensions
unit upper unit
drawer
upper
(setdrawer
upSC &(set
SF)upSC
(mm)& SF) (mm)
Series Series
1 1555
2
2100
5175 5175
6350
Series 7
Series 7
2100
Series Series
2 1810
3 Series Series
3 1810
4 Series Series
4 2200
5 Series Series
5 2490
6 Series Series
6 2200
7 Series 7
Dimensions
Centrifugal
Return
Air Fan
Dimensions
unitSection
upper2755
drawer (set
upSC3055
& SF) (mm)
L
L (mm)
2400 with2400
2755
2755
2755
2755
2755
3055 4575
4575 5175
5175 6350
Series 0 1370 2100
Series 1 Series
Series
3 2100
4
Series
5 4 2100 Series
Series
Model
2 Series
Series
3
Series
Series
A
A 1370
2100 0
2100 2Series
21001 Series
2100 Series
2100
2100
2100
2100 65 2100Series
2100 67
LH L
A
A
H
2400
2050
2755
2050 1830
1370
2100
2755
1830 2230
2400
1370
2100
2755 2755
3055
4575
2230 2490
2490 2490
2755
2755 2490 2490
3055
2100
2100
2100
2100
2100
2100
1830
2230
2490
H*equipment
2050
1830
2230
2490 on request.
2490
* Key CR
Key CR equipment
can be manufactured
can be
manufactured
in split
version
in spliton
version
request.
H
2050
6350
6350
* Key CR equipment can be manufactured in split version on request.
5175
2490 2490
4575
2100
6350
2490 5175
2490
2100
6350
Series 7
2100
2490
6350
2100
2100
2100
2100
2490
2490
2490
2490
2490
2490
2490
Reznor RTU Selection Procedure
Please photocopy page and send through any enquiries to [email protected]
Customer name .............................................. Date....................................
Project reference .........................................................................................
Application Type:
Version
Mounting Position
Cooling Only
HP: Heating and cooling
Standard
Floor
Cooling and Gas Fired
Dual: HP and Gas Fired
Free cooling
Roof
Recovery
Airflow information
Supply airflow
..............................
m3/s or m3/h
Fresh airflow / air rate
..............................
m3/s or m3/h
Recirculation airflow / air rate
..............................
m3/s or m3/h
External static pressure on return duct
..............................
Pa
External static pressure on supply duct
..............................
Pa
Unit total cooling capacity
..............................
kW
Unit sensible cooling capacity
..............................
kW
Indoor air dry bulb
..............................
°C
Indoor air wet bulb / relative humidity
..............................
°C
Outdoor air dry bulb
..............................
°C
..............................
kW
Cooling mode design conditions
..................
%
Heating mode design conditions
Heating capacity
Auxiliary heat type (if applicable)
Electric heat
Gas heat
LPHW
Gas type (if applicable)
Natural gas G20
Natural gas G25
Propane
Indoor air dry bulb
..............................
°C
Outdoor air dry bulb
..............................
°C
Outdoor air wet bulb / relative humidity
..............................
°C
..............................
%
Options
Air filter class
..............................
Built in digital controller
Built in digital controller
with BACnet
Remote relay interface control
External communication protocol
Lon
Bacnet
Modbus
Air quality CO2
With
Without
AXITOP - Acoustic attenuation system
With
Without
Electronic expansion valve
With
Without
Smoke detector
With
Without
Unit control
Dirty filter switch
Coil coatings
With
Polyurethane coating int
Without
Polyurethane coating ext
With
Without
Unit anti vibration mounts
With
Without
GB/REZ/043/0715
Heaters for drain pan
Nortek Global HVAC Belgium nv
J&M Sabbestraat 130/A000
B-8930 Menen
Belgium
Tel. +32 (0)56 52 95 11
Fax. +32 (0)56 52 95 33
[email protected]
www.reznor.eu
Company Standards and Services:
All products are tested and approved to CE standards. We are assessed to EN ISO 9001 Quality Assurance. We offer a service to
our customers; including budget schemes, on site technical support and a comprehensive after-sales package. We reserve the right
to change specifications without prior notice. Errors and omissions excepted.