Notice technique NT604
Transcription
Notice technique NT604
MULTIMESURE MULTIMETERING INSTRUMENTS DE MESURE Centrale de mesure multifonctions pour réseau BT 4 modules Réseau triphasé 50...450V (phase - phase) Réseau monophasé 30...260V Raccordement sur TC dédié Rapport TC et TT externe programmable Energie active cl.1 Diagnostic, correction séquence de phase Sortie impulsion Communication RS485 Interfaces externes : Communication Ethernet (NT809-NT891) Network monitor for low voltage 4 module Nemo D4-L Three-phase network 50...450V (phase - phase) Single-phase network 30...260V Connection with dedicated CT Programmable external CT - VT ratio Active energy cl.1 Phase sequence correction, diagnostic Pulse output RS485 communication External interfaces : Ethernet communication (NT809-NT891) DISPLAY IMPULSIONS • PULSE 1 3 4 6 7 9 8 5 2 V 1 V 2 V 3 Tension par phase et composée Phase and linked voltage 11 Courant par phase et du neutre Phase and neutral current RS 48 5 33 34 35 20 V 1 V 2 V 3 Courant moyen et valeur max. du courant moyen Current demand and current max. demand Fréquence Frequency 21 Facteur de puissance Power factor Puissance active, réactive par phase Active, réactive phase power Puissance moyenne et valeur max. de la puissance moyenne Power demand and power max. demand ETHERNET Energie active et réactive Active and reactive energy 3N3E V NT604 03 -2016 18ème Ed. pag.1/7 80...450V 80...500V Energie active partielle Partial active energy A /1A /5A /1A Heures et minutes de fonctionnement Working hours and minutes Diagnostic, correction séquence de phase Phase sequence correction diagnostic L1 L2 L3 N 3-3E V 80...450V 80...500V L1 L2 L3 A /1A /5A /1A 3-2E 3-2E V 80...450V 80...500V L1 L2 L3 A /1A /5A /1A 1N1E V 30...260V 50...290V L N A /1A /5A /1A MODELE RESEAU MODEL Nemo D4-L NETWORK bt / LV 4 Monophasé / Single-phase RACCORDEMENT CONNECTION Triphasé, équilibré Three-phase, balanced load 4 Triphasé, non équilibré Three-phase, unbalanced load 4 DIAGNOSTIC SEQUENCE DE PHASE / PHASE SEQUENCE DIAGNOSTIC ENTREE INPUT VALEUR NOMINALE RATED VALUE ENTREE COURANT INPUT CURRENT Tension / Voltage 400V Courant / Current 1 + 5A 4 TC dédié / Dedicated CT Isolé / Insulated TT (kTV) / VT (kVT) RAPPORT PROGRAMMABLE PROGRAMMABLE RATIO TC/CT 1...10 Calibres / Ranges Ipn / Isn 1...9’999 max. kTV x kTA / max. kVT x kCT 99’990 Shunt Précision / Accuracy EN/IEC 61557-12 ENERGIE ACTIVE ACTIVE ENERGY cl.1 Précision énergie cc Energy accuracy dc 4 Positive, totale et partielle Positive, total and partial Négative, totale / Negative total Précision / Accuracy EN/IEC 61557-12 ENERGIE REACTIVE REACTIVE ENERGY cl.2 4 Positive, totale / Positive, total Positive, partielle / Positive, partial Négative, totale / Negative, total TENSION VOLTAGE AFFICHAGE DISPLAY COURANT CURRENT par phase et composée / Phase and linked 4 par Phase Phase 4 du Neutre (mesuré) Neutral (measured) moyen et moyen max. par phase Phase demand and max. demand FACTEUR DE PUISSANCE POWER FACTOR PUISSANCE POWER DISTORSION Courant / Tension HARMONIC DISTORTION Current / Voltage Triphasé / Three-phase 4 4 Par phase / Phase Active, réactive, apparente Active, reactive, apparent 4 Moyenne et moyenne max. Demand and max. demand 4 Active et réactive par phase Phase active and reactive 4 THD Analyse / Analysis FREQUENCE / FREQUENCY MESURE C.C. 1 / D.C. 1 MEASURE COMPTEUR HORAIRE / RUN HOUR METER 4 4 SEQUENCE DE PHASE ERRONÉE / WRONG PHASE SEQUENCE TEMPERATURE / TEMPERATURE SORTIE OUTPUT IMPULSIONS / PULSES ■ RELAIS ALARME / ALARM RELAYS RELAIS ALARME+ ENTREE NUMERIQUE / ALARM RELAYS + DIGITAL INPUTS ANALOGIQUE / ANALOGUE COMMUNICATION COMMUNICATION RS485 MODBUS RTU ■ RS485 + MEMOIRE / RS485 + MEMORY PROFIBUS LONWORKS M-BUS BACNET ETHERNET RS485+IF2E001 TRANSMISSION RADIO 868MHz / 868MHz RADIO TRASMISSION 1 Tension, courant, puissance, Ah positive et négative / 1 Voltage, current, power, Ah positive and negative ■ En alternative NT604 03 -2016 18ème Ed. pag.2/7 RS232 On choice CODE ALIM. AUX. AUX. SUPPLY 9017 7000 9017 7050 9017 7010 9017 7100 9017 7150 9017 7110 9017 7002 9017 7052 9017 7012 9017 7102 9017 7152 9017 7112 9017 7001 9017 7051 9017 7011 9017 7101 9017 7151 9017 7111 230V ac 115V ac 20...150Vdc - 40...60Vac 230V ac 115V ac 20...150Vdc - 40...60Vac 230V ac 115V ac 20...150Vdc - 40...60Vac 230V ac 115V ac 20...150Vdc - 40...60Vac 230V ac 115V ac 20...150Vdc - 40...60Vac 230V ac 115V ac 20...150Vdc - 40...60Vac SORTIE OUTPUT ENTREE INPUT 5A 1A communication RS485 communication 5A 230V monophasé single-phase 1A 400V triphasé three-phase 5A impulsions énergie energy puses 1A Affichage DISPLAY Extinction automatique du rétroéclairage, temporisation 20 secondes Type of display: LCD backlit Type d’affichage: cristaux liquides rétroéclairés (LCD) Affichage des mesures: divisé en différentes pages, à sélection manuelle Nb de points d’affichage: 10.000 (4 chiffes) Automatic backlit reduction off after 20 s that keyboard is not used Unité de mesure: affichage automatique en fonction des rapports TC et TT Energy count: 8 digit counter Comptage de l’énergie: totalisateur 8 chiffres Measurement display: different pages, with manual scanning N° of reading points: 10.000 (4 digits) Résolution: changement automatique en fonction du calibre Engineering units: automatic display according to the set VT and CT ratios Echantillonnage: 1,2 secondes Decimal point: automatic, with the highest possible resolution La fonction compteur horaire est activée quand le dispositif détecte la phase L1. Run hour meter: working hours and minutes . Point décimal: automatique en tenant compte de la plus haute résolution Resolution: automatic, with the highest possible number of decimals Reading update: 1,2 seconds Compteur horaire: heures et minutes de fonctionnement. Diagnostic séquence de phase: signalisation d’un raccordement erroné. Run hour function is operating when the device detects L1 phase Voltage sequence diagnostic: wrong connection reporting AFFICHAGE DES PAGES • DISPLAY PAGES page page 1 2 3 4 5 6 7 8 9 10 NT604 03 -2016 18ème Ed. pag.3/7 11 12 13 14 Triphasé 4 fils / Three-phase 4-wire S 1000/212 tension par phase phase voltage Courant par phase phase current Tension composée linked voltage Puissance active par phase phase active power Puissance réactive par phase phase reactive power puissance triphasée active, réactive, apparente active, reactive, apparent three-phase power Courant du neutre + fréquence + facteur de puissance tri. neutral current + frequency + three-phase power factor courant moyen par phase phase current demand courant moyen max. par phase max. phase current demand puissance moyenne et puissance moyenne max. power demand and power max. demand heures et minutes de fonctionnement working hours and minutes énergie active active energy énergie réactive reactive energy énergie active partielle partial active energy Triphasé 3 fils / Three-phase 3-wire S1000/213 - S1000/282 tension composée linked voltage courant par phase phase current puissance triphasée active, réactive, apparente active, reactive, apparent three-phase power fréquence + facteur de puissance triphasé frequency + three-phase power factor courant moyen par phase phase current demand courant moyen max. par phase max. phase current demand puissance moyenne et valeur max. power demand and power max. demand heures et minutes de fonctionnement working hours and minutes énergie active active energy énergie réactive reactive energy énergie active partielle partial active energy Monophasé / Single-phase S1000/220 tension + courant voltage + current puissance active, réactive, apparente active, reactive, apparent power fréquence + facteur de puissance frequency + power factor courant moyen et moyenne max. current demand and max. current demand puissance moyenne et moyenne max. power demand and power max. demand heures et minutes de fonctionnement working hours and minutes énergie active active energy énergie réactive reactive energy énergie active partielle partial active energy Précision selon la norme EN/IEC 61557-12 Energie active Energie réactive Tension Conformity accuracy with EN/IEC 61557-12 Active energy Courant Voltage Puissance réactive Active power Puissance apparente Fréquence Apparent power Facteur de puissance Power factor Puissance active Ea cl.1 U cl.0,5 P cl.1 Erv Reactive energy I Current cl.2 cl.0,5 Qv Reactive power Sv f Frequence PFv cl.2 cl.2 cl.0,5 cl.0,5 COURANT MOYEN - PUISSANCE MOYENNE CURRENT DEMAND - POWER DEMAND Puissance sélectionnable: active, réactive, apparente Display: Current and maximum demand, current and peak max. demand Valeur sélectionnable: 5/8/10/15/20/30/60 minutes Average period: only for current and power Remise à zéro de la valeur max.: manuelle par touches Calculation: fixed average, on the period selectable Peak max. reset: by hand, by key PROGRAMMATION PROGRAMMING Affichage: courant et puissance moyenne, valeur max. courant et puissance moyenne Temps d’intégration : uniquement pour courant et puissance Power selectable: active or reactive or apparent power Calcul: moyenne fixe sur la période sélectionnée Value selectable: 5/8/10/15/20/30/60 Programmation des paramètres: 3 touches en face avant Accès à la programmation: protégé par un code d’accès Conservation des données et paramètres: mémoire permanente Parameters programming: front keyboard, 3 keys Programming access: protected by password Data and configuration parameters retention: non volatile memory PARAMETRES PROGRAMMABLES PROGRAMMABLE PARAMETERS Raccordement: réseau monophasé - triphasé 3 fils et 4 fils Rapport TC externe: 1...9999 Rapport TT externe: 1...10,0 Puissance moyenne: grandeur, temps d’intégration, RAZ valeur moyenne Courant moyen: temps d’intégration, reset valeur max. Communication RS485: n° adresse, vitesse de transmission, bit de parité, time-out Sortie impulsion: grandeur de l’énergie, impulsion et durée de l’impulsion Comptage de l’énergie: reset énergie active et réactive partielle Compteur horaire: reset Affichage: contraste de l’affichage Connection: single-phase — three-phase 3 and 4-wire External CT transformers ratio: 1...9999 External TT transformers ratio: 1...10,0 Power demand: quantity, average period, peak max.demand reset Current demand: average period, peak max. reset RS485 communication: address, baud rate, parity bit, time-out Pulse output: energy quantity, pulses and duration pulse Energy count: reset partial active and reactive energy Run hour meter: reset Dispaly: contrast display ENTREE INPUT Single-phase network, three-phase network 3 and 4-wire Three-phase voltage rating Un: 400V (phase-phase) Three-phase voltage: 80...480V (phase-phase) Single-phase voltage rating Un: 230V Single-phase voltage: 57 - 278V Connection with external dedicated current transformers Inputs have a common point (terminals 3 - 6 - 9) Current rating In: 5 - 1A Max. current Imax: 1,2In Instantaneous overload: 20In/0,5 seconds Frequency rating fn: 50Hz Tolerance: 47...63Hz Type of measurement: true RMS value Harmonic content: up to the 16th harmonic Peak factor: 2 Start time (energy count): < 5 seconds Voltage rated burden: ≤ 0,2VA (neutral-phase to voltage rating) Current rated burden: ≤ 1VA (each phase to max. current 6A) DIAGNOSTIC, CORRECTION SEQUENCE DE PHASE PHASE SEQUENCE CORRECTION, DIAGNOSTIC au raccordement tension et / ou courant. In the software of the device IME have added a specific functionality to detect and modifier, via software, la séquence de raccordement pour autant que les conditions This function can be activated through password and allows to display and modify 1) fil du neutre (dans un réseau 4 fils) est raccordé à la borne correspondante 1) The neutral wire (in a 4-wire network) is connected to the right terminal IME a rajouté un algorithme pour détecter et corriger de nombreux problèmes liés Cette fonction peut être activée par un mot de passe et permet d’afficher et de correct many problems concerning voltage and / or current connection. suivantes soient remplies: the connection sequence provided that the following conditions are respected: (normalement numéro 11). (normally number 11). NT604 03 -2016 18ème Ed. pag.4/7 Réseau monophasé, réseau triphasé 3 et 4 fils Tension triphasée nominale Un: 400V (phase-phase) Tension triphasée: 80...480V (phase-phase) Tension monophasée nominale Un: 230V Tension monophasée: 57 - 278V Raccordement sur transformateur de courant externe dédié Les entrées ont un point commun (bornes 3 - 6 - 9) Courant nominal In: 5 - 1A Courant max. Imax: 1,2In Surcharge instantanée: 20 In/0,5 secondes Fréquence nominale fn: 50Hz Variation admissible: 47...63Hz Type de mesure: valeur efficace vraie Contenu harmonique: jusqu’à la 16ème harmonique Facteur de crête: 2 Temps de démarrage (comptage de l’énergie): < 5 secondes Autoconsommation tension: ≤ 0,2VA (phase-neutre à la tension nominale) Autoconsommation courant: ≤ 1VA (par phase au courant max. 1,2A) 2) Pas de croisements entre les câbles raccordés aux TC (ex.: sur la phase 1 de l'appareil éviter un câble provenant de TC1 et un câble provenant de TC2) 3) Le facteur de puissance et compris entre 1 et 0,5 inductif pour chacune des phases. 2) No crossings between cables connected to CTs (e.g. avoid that on phase 1 of the meter -terminals 1 and 3 - are connected some way both to CT1 and CT2). 3) The power factor is between 1 and 0,5 - Inductive load - for each phase. See www.imeitaly.com “TECHNICAL SUPPORT”. See www.imeitaly.com “TECHNICAL SUPPORT”. ALIMENTATION AUXILIAIRE AUXILIARY SUPPLY Valeur nominale Uaux ac: 48 - 115 – 230V (monophasé) Fréquence nominale: 50Hz Fréquence de fonctionnemement: 47…63Hz Autoconsommation: ≤ 2,5W (230Vac rétroéclairage sans module externe) Valeur nominale Uaux dc: 20...150Vdc Autoconsommation: ≤ 1W (sans module) Protection contre l’inversion de polarité Rated value Uaux ac: 48 - 115 – 230V (single phase) Rated frequency: 50Hz Working frequency: 47…63Hz Rated burden: 2,5W (230VAc backlight 30% without external modules) Rated value Uaux dc: 20...150Vdc Rated burden: ≤ 1W (without modules) Protected against incorrect polarity SORTIE OUTPUTS IMPULSION ENERGIE Sortie impulsion compatible avec SO EN / IEC 62053-31 Optorelais avec contact SPST-NO libre de potentiel Pouvoir de coupure: 110Vdc/ac - 50mA Grandeurs associables: énergie active ou réactive Poids de l’impulsion: 0,1kWh(kvarh) - 1kWh(kvarh) - 10kWh(kvarh) - 100kWh(kvarh) Durée de l’impulsion: sélectionnable 50 - 100 - 200 - 300ms COMMUNICATION RS485 Isolée galvaniquement de l’entrée et de l’alimentation auxiliaire Standard: RS485 - 3 fils Transmission: asynchrone série Protocole: compatibile JBUS/MODBUS N°- adresse: 1...255 Nombre de bit: 8 Bit de stop: 1 Bit de parité: sans - paire - impair Time-out: 3...100ms Vitesse de transmission: 9600 - 19200 bit/seconde Temps de réponse à l’interrogation: ≤ 200ms N°- max.d’appareil raccordés au réseau: 32 (jusqu’à 255 avec répétiteur RS485) Distance max. du superviseur: 1200m ENERGY PULSES Pulse output according to SO EN / IEC 62053-31 Optorelay with potential-free SPST-NO Contact range: 110Vdc/ac - 50mA Associated quantity: active or reactive energy Weight pulses: 0,1kWh(kvarh)- 1kWh(kvarh) - 10kWh(kvarh) - 100kWh(kvarh) Duration pulsee: selectable 50 - 100 - 200 - 300ms RS485 COMMUNICATION Galvanically insulated from input and aux. supply Standard: RS485 - 3 wire Transmission: serial asynchronous Protocol: compatible JBUS/MODBUS Address: 1...255 Bit number: 8 Stop bit: 1 Parity bit: none - even - odd Time-out: 3...100ms Baud rate: 9600 - 19200 bit/seconds Required response time to request: ≤ 200ms Meters that can be connected on the bus: 32(up to 255 with RS485 repeater) Highest distance from supervisor: 1200m COMMUNICATION ETHERNET (NT809 - NT891) ETHERNET COMMUNICATION Réalisable avec les interfaces IF2E ou IF4E (RS485/Ethernet) ISOLEMENT Catégorie de l’installation: III It can be carried out with IF2E or IF4E (RS485/Ethernet) interface (EN61010-1) Degrée de pollution: 2 Tension de référence pour l’isolement: : 300V (Phase/Neutre) Circuits considérés Considered circuits INSULATION Pollution degree: 2 Insulation voltage rating: 300V Phase/Neutral PROVE TESTS Tension à impulsions 1,2 / 50μs 0,5J Tension alternative valeur efficace 50Hz 1min Voltage test 1,2 / 50μs 0,5J Alternating voltage r.m.s value 50Hz 1min ?kV 3kV ?kV 3kV ?kV - 3kV 4kV Measure inputs / RS485 (232)1 Communication Entrée mesure / Sortie impulsion1 Meaure inputs / Pulse output1 NT604 03 -2016 18ème Ed. pag.5/7 Tous les circuits et la masse All circuits and earth avec module additionnel (EN61010-1) Installation category: III Alimentation / Entrée voltmétrique Supply / Voltmetric inputs Entrée mesure / Communication RS485 (232)1 1 (NT809 - NT891) 1 with addition module COMPATIBILITE ELECTROMAGNETIQUE ELETROMAGNETIC COMPATIBILITY Test d’immunité selon la norme EN 61326-1 Emission according to EN 61326-1 class B CONDITIONS D’EMPLOI ENVIRONMENTAL CONDITIONS Température de fonctionnement spécifique: -5...55°C Specified operating range: -5...55°C émission selon la norme EN 61326-1 classe B Température de référence: 23°C ± 2°C Température limite pour le stockage et le transport: -25...70°C Variation de l’indice de classe: ≤ 0,1% /°C Immunity according to EN 61326-1 Reference temperature: 23°C ± 2°C Limit range for storage and transport: -25...70°C Variation to the class index: ≤ 0,1% /°C Adapté pour les climats tropicaux Suitable for tropical climates Puissance max. dissipée1: ≤ 6,8W Max. power dissipation 1: ≤ 6,8W Pour le dimensionnement thermique du coffret 1 For switchboard thermal calculation BOITIER HOUSING Raccordement: bornier à vis pour conducteur jusqu’à 4 mm 2 Housing: 4 modules DIN 43880 Type de profil: TH35-15 (EN60715) Mounting: snap-on 35mm rail Degré de protection (EN60529): IP52 face avant, IP20 bornes Housing material: self-extinguishing policarbonate Boîtier: 4 modules DIN 43880 Fixation: rail 35mm Connections: screw terminals for cable up to 4 mm 2 Materiau du boîtier: polycarbonate autoextinguible Rail type: top hat TH35-15 (EN60715) Poids: 285 grammes Protection degree (EN60529): IP52 front frame, IP20 terminals CAPACITE DES BORNES TERMINAL CAPACITY ENTREE MESURE Weight: 285 grams Fil rigide : min.0,05mm / max. 4,5mm 2 MEASURE INPUT 2 Fil souple: min.0,05mm / max. 2,5mm Rigid cable: min.0,05mm2 / max. 4,5mm2 ENTREE COURANT Tightening torque advised: 0,5 - 0,8Nm Fil souple: min.0,05mm2 / max. 4mm2 Rigid cable: min.0,05mm2 / max. 6mm2 2 2 Flexible cable: min.0,05mm2 / max. 2,5mm2 Couple de serrage conseillé: 0,5 - 0,8Nm CURRENT INPUT Fil rigide: min.0,05mm2 / max. 6mm2 Couple de serrage conseillé: 0,5 - 0,8Nm Flexible cable: min.0,05mm2 / max. 4mm2 Fil rigide: min.0,05mm / max. 4,5mm AUX. SUPPLY ALIMENTATION AUXILIAIRE 2 Tightening torque advised: 0,5 - 0,8Nm 2 Rigid cable: min.0,05mm2 / max. 4,5mm2 Fil souple: min.0,05mm / max. 2,5mm 2 2 Couple de serrage conseillé: 0,5 - 0,8Nm Flexible cable: min.0,05mm2 / max. 2,5mm2 Fil rigide: min.0,05mm2 / max. 4,5mm2 OUTPUT Tightening torque advised: 0,5 - 0,8Nm SORTIE Rigid cable: min.0,05mm2 / max. 4,5mm2 Fil souple: min.0,05mm / max. 2,5mm 2 2 Flexible cable: min.0,05mm2 / max. 2,5mm2 Couple de serrage conseillé: 0,5 - 0,8Nm POSITION DES BORNES DIMENSIONS Tightening torque advised: 0,5 - 0,8Nm TERMINAL POSITION DIMENSIONS 65,6 89,5 45 70 44 NT604 03 -2016 18ème Ed. pag.6/7 1 SCHEMAS DE RACCORDEMENT WIRING DIAGRAMS F : 0,5A gG S 1000/212 S 1000/220 OUTPUT INPUT IMESYS se réserve à chaque moment de modifier les caractéristiques sans préavis écrit / IMESYS reserves the right to modify the technical characteristics without notice. NT604 03 -2016 18ème Ed. pag.6/7 RS 485 GND Rx / Tx CURRENT VOLTAGE 2 5 8 11 1 3 4 6 + 7 9 AUX. SUPPLY 35 33 34 33 35 a b A B CURRENT 4 6 2 5 8 11 1 3 20 21 7 9 F S1 L1 P1 L2 X 20 21 S1 P1 X S1 P1 X X S1 P1 N X X X Réseau triphasé 4 fils • Three-phase network 4-wire Réseau monophasé • Single-phase network S 1000/282 S 1000/213 OUTPUT INPUT 2 5 8 RS 485 GND Rx / Tx CURRENT VOLTAGE 1 3 6 + 7 9 b a b A L1 B A B AUX. SUPPLY CURRENT VOLTAGE 35 33 34 33 35 20 21 2 5 8 F OUTPUT INPUT – 8 a 2 5 1 3 4 6 7 9 RS 485 GND Rx / Tx + AUX. SUPPLY – 35 33 34 33 35 20 21 8 F S1 P1 X X L2 S1 L3 35 33 34 33 35 – F L3 N 5 AUX. SUPPLY + a A L 2 RS 485 GND Rx / Tx 2 5 8 11 11 2 OUTPUT INPUT VOLTAGE – X P1 Réseau triphasé 3 fils • Three-phase network 3-wire NOTA Les schémas de raccordement se réfèrent aux compteurs équipés d’une sortie impulsions et d’une interface RS485. Pour les versions sans sortie impulsions ou communication RS485, ne pas tenir compte des bornes de sorties concernées. NOTE The wiring diagrams, show the device complete with pulse output and RS485 interface. In case of version without of these features, the corresponding terminals must not be considered.