LCM-40(DA), LCM-60(DA) installation manual

Transcription

LCM-40(DA), LCM-60(DA) installation manual
LCM-40(DA), LCM-60(DA) installation manual





Features
‧180~295VAC input only
‧Built-in active PFC
‧Output current level selectable by DIP switch
‧Built-in DALI inter face and push dimming function (DA ve rsion)
‧Built-in 0~10Vdc a nd PWM signal dimming function (Non -DA version)
‧Power supp ly synchronization function up to 10 un its
‧Temperature compensation function b y external NTC
‧ClassⅡpo wer unit, ungrounded
‧Buil t-in 12V/50mA auxiliary output
‧Full plastic case enclos ed
‧No l oad power consumption <1W (1.2W for DA ve rsion)
‧Protection s: Short circuit / Over voltage / Over temperature
‧3 year warranty
‧Suit able for intell igent LED lighting
Wiring
‧Housing wi th cabl e clamp for re mote installation
‧Use wires with an adequate cro ss-section (see 5)
‧Use suitable mounting to ols to do the wiring and mounting (see 5)
‧Use a MCB (miniature circuit breaker) with an adequate current rating to protect the lighting system (see 6)
Environmental limitations
‧Maximum ambient temperature must not exceed 6 0℃
‧Always allow adequate ventilation clearances, 50mm, aro und the unit in use to prevent it from overheating
‧Only install the unit in interior environ ments
Cautions
‧This unit must be installe d by a qualified electrician
‧This unit is not suitable for applications that DC/DC converters are connected befor e LED lamps
Settings and connections
1. Output Current Level Settings
The LCM can prov ide various output c urrents by se tting the DIP switch. The settings of the DIP s witch are shown in the tables below.
LCM-40(DA)
Voltage Sel ectable
ran ge
Current
LCM-60(DA)
1
2
3
4
5
6
Voltage Sel ectable
range
Current
1
2
3
4
5
6
2-1 00V
35 0mA
- --
---
- --
---
- --
---
2-90V
50 0mA
---
---
- --
---
- --
---
2-8 0V
50 0mA
ON
---
- --
---
- --
---
2-90V
60 0mA
ON
---
- --
---
- --
---
2-6 7V
60 0mA
ON
ON
- --
---
- --
---
2-86V
70 0mA*
ON
ON
- --
---
- --
---
2-5 7V
70 0mA*
ON
ON
ON
---
- --
ON
2-67V
90 0mA
ON
ON
ON
---
- --
ON
2-4 5V
90 0mA
ON
ON
ON
ON
- --
ON
2-57V
10 50mA
ON
ON
ON
ON
- --
ON
2-4 0V
10 50mA
ON
ON
ON
ON
ON
ON
2-42V
14 00mA
ON
ON
ON
ON
ON
ON
Note : 1.Fac tory d efault setting is 70 0mA.
2.Out put vo ltage a nd output wa ttage must n ot exc eed th e rate d values.
Terminal blocks assignment for LCM
123.5mm
23mm
6 5 4 3 21
ON
-Vo
+Vo
+
+
SYN.
-DIM
+DI M
-NTC
+NTC
-FAN
+FAN
DADA+
PUSH
AC / N
AC / L
2. Connection of LED Lamps
Press down the "push bu tton" by a slo tted screw driver to insert or remove the cable.
VoVo+
AC/N
AC/L
NEUTRAL (Blue o r whit e)
LIVE (Brow n or bl ack)
http: //www.mean well.c om
3. Connection of Dimming Functions
a. 0-10Vdc or 10V PWM (non-DA ver sion only)
b. DALI (DA version only)
-
DIMDIM+
0~ 10V DC
DA+
DA-
+
DALI
control ler
Note : Ma ximum DALI cable length is 300m
(based on a 1.5mm 2 or 14AWG cable)
c. Push dim (DA v ersion only)
PUSH
AC/N
AC/L
Push Bu tto n
NEUTRAL (Bl ue or white)
LIVE (Brown or black)
No te: ON LY use open push button witho ut indi cator l ight.
Warning: Risk of short circuit. The push button can only be linked betwee n the PUSH and the AC/L (brown or bla ck).
DO NOT connect the push button to the AC/N (blue or white).
Dimming control mechanism
Function
Pushing time
Turn ON/OFF
0.1 ~ 1 sec
Dim UP/DOWN
1.5 ~ 1 0 sec
Reset
> 11 sec
None
< 0.05 sec
‧ It will always dim up when light intens ity is lower than 10%, whe reas it will
alwa ys dim down when light intensity is higher than 90%
‧ Factory dimming setting: 100%
d. Sy nchronization ope ration
The lights driven by LC M units (slav es) can be dimmed synchronous ly through a LCM unit (the master) dire ctly controlled via
0-10Vdc, 10V PWM, DALI or push d im dimming function. The wiring is show n as b elow.
Master
Slave 1
Slave 2
SYN.
SYN.
SYN.
- + - +
- + - +
- + - +
‧Mating housing for SYN. connectors : JST B2B-XH or equivalent
‧Maximum number of the LCM units : 10 (1 master + 9 slaves)
‧Maximum cable length be tween each units : 20m (based on a cable with cross-section of 0.15mm 2~0.3mm2 or AWG No. of 22 ~ 26)
Note 1 : DO NOT conne ct dimming circuitry to slaves.
Note 2 : Pl ease make sure all units a re set to 100% dimming setting (factory default) befo re synchronizing.
4. NTC Connection
NTCNTC+
5. Recommended Scre wdriver, Wire and Torque Setting
Type
The cover
(the blue one)
Scr ew ter minal
(FA N±, NT C±, DI M±)
Push terminal
(ACL/N, PUSH, DA±, Vo±)
Solid wire
-----
ψ0.404 -ψ 0.643 mm
ψ1.024 -ψ 1.628mm
2
0.823 - 2.08 mm 2
Stranded wire
-----
0.12 9 - 0.3 26mm
Ameri can w ire gauge
-----
22 - 26AWG
14 - 1 8AWG
Wire strippi ng length
-----
7mm (0.27 ")
10mm (0.39 ")
Screwdriver
6mm Phillips
3mm Philli ps
3mm Phillip s
Recommended tighteni ng tor que
4.6 kgf-cm (4 lb-in)
2.88 kgf-c m (2.5 lb-in)
-----
-----
-----
3 - 4 kp (6.6 1-8.81 lb F)
Suggested push-down strength
6. Suggested Maximum Num ber of the LCM Units that can be Connected to a MCB (miniature circuit breaker ) at 230Vac
Mo del
B10
B16
C1 0
C16
LCM-4 0(DA)
10
16
17
28
LCM-6 0(DA)
9
15
16
26
Note: These calcu lated v alues are ba sed o n MCB S201 series manu factured by A BB.