2 pulse outputs module for 2 pulse outputs module for 4 120 53 4

Transcription

2 pulse outputs module for 2 pulse outputs module for 4 120 53 4
87045 LIMOGES Cedex
Telephone : 05 55 06 87 87 – Fax: 05 55 06 88 88
2 pulse outputs module for 4 120 53
Cat. N°: 4 120 59
Contents
Pages
1. Description - Use................................... 1
2. Range ...................................................
................................
1
3. Overall dimensions................................ 1
4. Preparation - Connection ...................... 1
5. General characteristics..........................
characteristics
2
6. Compliance and approvals .................... 2
1. DESCRIPTION - USE
4. FIXING - CONNECTION
2 pulse outputs module.
Fixing:
Allows the remote repetition of the energy counting
Each module is equipped with two independent and isolated
outputs, associable to the count of active and/or reactive energy,
positive and/or negative.
2. RANGE
. Cat. N° 4 120 59:: 2 pulse outputs module; associable only to
multifunction measuring device 4 120 53.
. It is possible to connect a maximum of two modules 4 120 59
obtaining four pulse outputs.
Auxiliary supply:
. Supplied by the multifunction measuring device 4 120 53
3. OVERALL DIMENSIONS
Note:
modules must be connected with the device 4 120 53 not
supplied.
Associability table:
Operating position:
.
Technical data sheet: F02174EN/00
Updated: -
Vertical
Horizontal
Upside down
On the side
Created: 18/09/2015
1 / 2
2 pulse outputs module for 4 120 53
Cat. N°: 4 120 59
4. FIXING - CONNECTION
Screw terminals:
5. GENERAL CHARACTERISTICS
Variables associable to the pulse output:
(continued)
(continued)
. Terminal depth: 8 mm.
. Stripping length: 8 mm
. Positive active energy (Ea+)
. Positive reactive energy (Er+)
. Negative active energy (Ea-)
. Negative reactive energy (Er-)
Screw head:
. Screw slotted.
Pulse output’s characteristics:
Recommended tightening torque:
. 0,6 Nm.
Tools required:
. Optorelays with potential-free SPST-NO contact
. Type S0 (IEC/EN62053-31)
. Voltage U : max. 27 Va.c./d.c.
. Current I : max. 50 mA
. Programmable pulse weight, possible values: 10 – 100 - 1k - 10k 100k - 1M - 10M Wh/imp or varh/imp
. Programmable pulse duration, possible values: 50 - 100 - 200 - 300
ms.
imp
. For terminals: flat screwdriver 3,5 mm
. For fixing the modules to the measuring device: flat screwdriver
max. 5 mm.
Connectable section:
section:
. Copper cables.
imp
Plastic material:
Without ferrule
With ferrule
Rigid cable
0,05 to 4,5 mm²
-
Flexible cable
0,05 to 2,5 mm²
0,05 to 2,5 mm²
. Self-extinguishing polycarbonate.
Ambient operating temperature:
. Min. = - 5 °C Max. = + 55 °C.
Ambient storage temperature:
Wiring diagrams:
. Min. = - 25 °C Max. = + 70 °C.
. Terminals identifications
Impulse withstand voltage:
. Supply / Out 1 - Out 2:
alternate current 50 Hz / 1 min.: 2 kV
. Measuring inputs / Out 1 - Out 2:
alternate current 50 Hz / 1 min.: 2 kV
Note: values referred to combination measuring device + add-on
module.
Average weight per device:
. 0,030 kg.
Volume when packed:
. 0,30 dm3
. Wirings
Consumption:
. Module 4 120 59: ≤ 1 VA
. Measuring device 4 120 53 + 1 Module 4 120 59: ≤ 5 VA
. Measuring device 4 120 53 + 2 Modules 4 120 59: ≤ 6 VA
6. COMPLIANCE AND APPROVALS
Compliance to standards:
5. GENERAL CHARACTERISTICS
Terminals marking:
. Compliance with Directive on electromagnetic compatibility (EMC)
n° 2004/108/EC
. Compliance with low voltage directive no. 73/23/CEE dated 19
February 1973, modified by directive no. 93/68/CEE dated 22 July
1993, modified by directive n° 2006/95/CE.
. By permanent ink pad printing.
Technical data sheet: F02174EN/00
Updated: -
Created: 18/09/2015
2/2