RIRS P EKO

Transcription

RIRS P EKO
RIRS P EKO
!
NEW
AHU with heat recovery
Centrales de traitement d’air
avec récupération de chaleur
Lüftungsgeräte mit wärmerückgewinnung
AIR HANDLING UNITS
AHU med varmegenvinding
Air handling units RIRS P EKO 3.0 have high efficiency rotor heat exchanger. AHU is used for ventilation of houses
and other heated areas.
• Energy saving and low noise EC fans.
• Efficiency of heat exchanger up to 80%.
• Integrated electrical heater or optional water heating/cooling.
• Controlled air flow.
• Low noise level.
• Acoustic insulation of the walls – 30 mm.
• RIRS P EKO 3.0 versions can be controlled with Flex, Stouch
remote control devices.
• RIRS P EKO 3.0 housing: powder coated painting RAL 9016.
• Easy mounting.
• Full integrated plug & play control system.
• Integrated pressure switch for filter pollution.
• Optional CO2, pressure or airflow transmitter.
• Extremely low height !
Lüftungsgeräte RIRS P EKO 3.0 mit hocheffizientem Rotationswärmetauscher. WRG sind für Lüftung von Häusern und
anderen beheizten Räumen bestimmt.
• Wirtschaftliche und geräuscharme EC Ventilatoren.
• Hocheffizienter Rotationswärmetauscher bis zu 80%.
• Eingebautes Elektro-Register oder optional Warmawasserregister
oder Wasserkühler für externe Einbau im Rohrsystem.
• Regelung des Luftstomes.
• Zulufttemperatur-Regelung.
• Steurung mittels Fernbedienung Flex, Stouch.
• Schall- und Wärmedämmung – 30mm.
• Gehäuse pulverbeschichtet nach RAL9016.
• Niedriges Geräuscheniveau.
• Montage freundlich.
• Vollständig eingebaute Plug & Play-Steuerung.
• Eingebaute Druckdifferenzschalter für Filterüberwachung.
• Optional CO2, Druck- oder Feuchtefühler
• Extrem niedrige Bauhöhe!
Les centrales de traitement d’air RIRS P EKO 3.0 sont équipées d’un échangeur de chaleur rotatif efficace. Ces centrales de traitement d’air avec la récupération de chaleurs
sont utilisées pour la ventilation des locaux chauffés.
• Ventilateurs EC économes en énergie et silencieux.
• Échangeur de chaleur rotatif efficace, dont le rendement thermique fait jusqu‘à 80%.
• Batterie électrique intégrée et batterie à eau chaude / batterie à
eau glacée en option.
• Possibilité d’inverser le flux d’air.
• Réglage de la température de l’air soufflé.
• Faible niveau de bruit.
• Isolation acoustique des parois – 30 mm.
• RIRS P EKO 3.0 peut être régulée à l’aide des boîtiers de commande Flex, Stouch.
• Caisson peint avec la peinture à poudre, couleur RAL 9016.
• Installation facile et rapide.
• Pré équipement « Plug & play » et carte de contrôle automatique
entièrement intégrée.
• Capteur d’encrassement des filtres intégré.
• Possibilité de connecter les convertisseurs de pression, de CO2
et d’humidité.
• Particulièrement plat!
Ventilationsaggregatet RIRS P EKO 3.0 har en særdeles
effektiv rotorvarmeveksler. AHU anvendes til ventilation af
huse og andre opvarmede områder.
• Energibesparende, støjsvage EC-ventilatorer.
• Virkningsgrad op til 80%.
• Integreret elvarme eller valgfri vandvarme/køle-flade.
• Regulerbar luftmængde.
• Regulerbar indblæsnings-temperatur.
• Lavt støjniveau.
• Støjdæmpende isolering af kabinettet – 30mm.
• Alle varianter kan styres med Flex, Stouch fjernbetjening.
• Pulverlakeret kabinet RAL 9016.
• Nem montering.
• Integreret ”plug & play” kontrolsystem.
• Filter overvågning
• Mulighed for CO2-, tryk- og flow-transmitter.
• Meget lav indbygningshøjde.
Accessories
Control panel
Flex
144
p. 178
Sensor controller
Stouch p. 179
Pressure
transmitter
S-1141
p. 181
CO2 sensors
Duct
humidity sensor
S-RC02-F2 p. 182 S-KFF-U p. 183
Actuator
for dampers
Duct sensor
SP
TJK 10K p. 187
p. 188
The company reserves the right to make changes of technical data without prior notice
Thermic water
valve actuator
SSB
p. 184
RIRS P EKO
RIRS 350 P E EKO 3.0
Equipped with new PRV V2.2 control board
AHU with EC motors
Heater type (E - integrated electrical heater; W - optional water heater)
Housing type (V - vertical, H - horozontal, P - under - ceiling)
AHU size according to air flow range m3/h
AHU with rotor heat-exchanger
W
398
398
RIRS 350PE EKO 3.0
RIRS 350PW EKO 3.0
W1
196
196
W2
550
550
H
610
610
Dimensions [mm]
H1
H2
H3
160
160
83
160
160
83
Type
E
764
764
L
961
961
S
652
652
øD
200
200
AIR HANDLING UNITS
Type
Accessories
Flex
Stouch
S-1141
S-RC02-F2
S-KFF-4
SP
AP
SKG
TJK10K
C04C***
SSB
SSB
Heating Cooling
RIRS 350PE EKO 3.0
+
+
LM230A-TP
200
-
-
RIRS 350PW EKO 3.0
+
+
TF230
200
+
61
RMG
80/600C
RMG
80/400C
VVP/VXP
80/600C
VVP/VXP
80/600C
-
-
-
-
-
81
3-0,63-4
3-0,63-4
45.10-0,63
45.10-0,63
*** - anti-frost thermostat
Accessories
Mixing point
2 and 3
way valves
RMG
VVP/VXP p. 186
p. 185
The company reserves the right to make changes of technical data without prior notice
145
RIRS P EKO
RIRS 350P EKO 3.0
Performance
Power consumption
Air flow [l/s]
28
56
83
111
Power [W]
Static pressure [Pa]
Supply air
90
80
70
60
50
40
30
50%
20
10
50%
100
200
300
Exhaust air
Air flow [l/s]
28
56
83
111
Power [W]
Static pressure [Pa]
0
400
Air flow [m3/h]
RIRS 350P EKO 3.0
AIR HANDLING UNITS
Air intake side (L- left)
View from inspection side
50%
Exhaust air
Article No.
GAGRIRS1762_0028A
GAGRIRS1763_0029A
50%
100
200
300
Static pressure [Pa]
Air flow [l/s]
56
100
SFP=
200
83
300
η [%]
Temperature efficiency
93
28
111
400
Air flow [m3/h]
total power for supply & exhaust fans kW
x 3600
air flow m3/h
Fresh air
Supply air
Version
350PE EKO 3.0 Integrated electrical heater.
350PW EKO 3.0 Optional water heater.
350PE / PW EKO 3.0
400
Air flow [m3/h]
Specific fan power
28
Extract air
Water heater (optional) PW ver.
Electrical heater PE ver. phase/voltage [50Hz/VAC]
[kW]
EC fans
phase/voltage [50Hz/VAC]
exhaust
power/current
[kW/A]
fan speed
[min-1]
supply
power/current
[kW/A]
fan speed
[min-1]
Thermal efficiency up to*
Max power consumption PE / PW
[kW/A]
Control board
Filter class
exhaust/supply
Housing insulation, mineral wool
[mm]
Colour
RAL
white
Weight (net, without packing) PE / PW
[kg]
Comply with ERP
Operation
Housing protection class
IP
AVS 200
~1, 230
0,6
~1, 230
0,083/0,74
3200
0,083/0,74
3200
85%
0,77/4,18 0,171/1,58
PRV V2.2
M5/F7
30
9016
54
53
2015
indoors
34
* Calculated according EN 13141-7.
**For temperatures lower than recommended use electrical pre-heater to
ensure balanced operation.
Air flow [l/s]
56
83
111
350P EKO 3.0
Lwa total,
dB(A)
Supply
69
Extract
64
Surrounding
54
Measured at 356 m3/h, 120 Pa
91
89
87
125 Hz
54
52
40
250 Hz
53
54
39
500 Hz
66
59
48
LWA, dB(A)
1 kHz
2 kHz
64
58
41
60
57
47
4 kHz
58
54
44
8 kHz
55
49
46
85
83
Temperature efficiency (balanced mass flow) EN 13141-7:
Extract air = 20°C/60%RH
Outdoor air = -20°C
81
79
Certifications
77
75 0
146
100
200
300
400
Air flow [m3/h]
EUROVENT certified counter flow heat exchanger performance
The company reserves the right to make changes of technical data without prior notice
RIRS P EKO
RIRS 350PE EKO 3.0 (ceiling mounted) versions with electrical heater
Supply air
Fresh air
Extract air
Exhaust air
PF - fresh air filter (class F7)
IF - extract air filter (class M5)
TL - temperature sensor for fresh air
DTJ -humidity + temperature sensor
AIR HANDLING UNITS
IV - exhaust air fan
PV - supply air fan
RR - rotary heat exchanger
R - rotor motor
KE - electrical heater
RIRS 350PW EKO 3.0 (ceiling mounted) versions with water heater
Supply air
Fresh air
Exhaust air
Extract air
IV - exhaust air fan
PV - supply air fan
RR - rotary heat exchanger
R - rotor motor
PF - fresh air filter (class F7)
IF - extract air filter (class M5)
TL - temperature sensor for fresh air
DTJ -humidity + temperature sensor
AVS - optionally supplied water heater
The company reserves the right to make changes of technical data without prior notice
147