Data Sheet TP75 Heating Controller Programmable Room

Transcription

Data Sheet TP75 Heating Controller Programmable Room
Data Sheet
TP75 Heating Controller Programmable
Room Thermostats
Application & Features
Typical System
Connections
The TP75 is a true seven-day programmable
thermostat incorporating many useful features.
An optional Optimum Start function will enable a
required comfort temperature to be achieved by
a programmed time, without wasting fuel
because the heating plant started earlier than
necessary. The chrono-proportional control logic
ensures optimum comfort with minimal fuel
consumption.
The basic model incorporates a temperature
sensor within the casing, but a remote sensor
version is also available. Both can be converted
to operate as an electronic thermostat, controlling
at a constant, user selected, temperature. The
Holiday Mode uses this temperature for a
selected number of days, before automatically
returning to programmable thermostat mode.
Versions are available for use with a third- party
telephone line switching device so that frost
mode or holiday mode can be cancelled whilst
away from home.
● Battery powered, programme unaffected
by mains power failures
● Volt-free output contacts, rated 10 to
250Vac, 50/60Hz, or dc 10mA to 2(1)Amp.
● Integral or remote temperature sensing
● Up to 6 programmable temperature
changes per day, including a
programmable "OFF" function
● Selectable 7 day or 5/2 day programme
● Selectable time or temperature display
● Temperature range, 5°C to 30°C, in
increments of 0.5°C.
● Selectable Chrono-proportional control
or On/Off control
● Optional Optimum Start
● Frost protection function
● Thermostat function for constant
temperature setting
● Holiday function, up to 99 days at a
constant, selectable temperature
● Extend override, maintains existing set
temperature for a further 1, 2 or 3 hours
● Selectable All Day programme, 1st event
temperature lasts until 6th event becomes
active
● Remote reset of Frost or Holiday functions
possible
Direct Burner Control
Zone control with motor open/
motor close two port valve
Wallplate teminals
Live
Input
Heating
On Off
Heating
On Off
A B C 1 2 3 4 5 6
A B C 1 2 3 4 5 6
N
E
3 amp
fuse
Live
Input
Wallplate teminals
EARTHS NOT SHOWN.
ENSURE EARTH
CONTINUITY
THROUGHOUT
N
E
3 amp
fuse
N
N
L N E
Mains
N
L N E
Mains
1
Data Sheet
TP75 Heating Controller
Specifications
Integral
temperature
sensor
Feature
3* or 6 cycles per hour,
chrono-proportional control
12* or 6 cycles per hour,
chrono-proportional control
Programmes
User overrides
Factory pre-set programme,
all may be changed
Note: An "OFF" event can
also be programmed
DIL switch options
at the time of installation
Voltage Rating
Contact Current Rating
Switching Action
Main Batteries
Memory Retention
Max. Ambient Temperature
Dimensions mm
Fixing clearances,
internal wiring & DIL
switch settings
Model Designations
Remote
Remote
temperature
teleswitch
sensor
reset
TP75
TP75A
TP75B
TP75AB
TP75C
TP75AC
TP75BC
TP75ABC
Profiled - (up to 6 temperature changes per day)
All Day - ( 1st event temperature lasts until 6th event time)
Raise or lower temperature setting
Extend duration of existing temperature setting by 1, 2 or 3 hours
Select Profiled or All Day programme
Monday to Friday
Event
Saturday & Sunday
20°C at 06:30
1
20°C at 07:30
15°C at 08:30
2
20°C at 09:30
20°C at 11:30
3
20°C at 11:30
15°C at 13:30
4
20°C at 13:30
21°C at 16:30
5
21°C at 16:30
15°C at 22:30
6
15°C at 22:30
DIL Switch No.
Factory Pre-set
Installer Alternative
1
7 day programme
5/2 day programme
Optimum Start
Optimum Start
2
Control Disabled
Control Enabled
On/Off control
Chrono control
3
enabled
enabled
3 or 12 control cycles
6 control cycles
4
per hour (see above *)
per hour
10-250Vac, 50/60Hz or 10-250Vdc
10mA to 2 Amp (res), 1 Amp (ind)
SPDT voltage free
2 x AA alkaline dry cells (Duracell preferred) to be renewed every
24 months
Sufficient to remove and replace batteries within one minute
45°C
135 wide x 88 high x 32 deep
Internal wiring
Terminals
30 mm
minimum
Factory pre-set DIL
switch settings
Outline of unit
A B C
Wall or plaster
box mounting
holes
N&E
looping
terminals
ELECTRONICS
5/2 day
A B C 1 2 3 4 5 6
Clearance
for
screwdriver
access
Remote Control
Functions
External Connections
* NOTE: Remote start-up
connections vary with model.
Remote temp
sensor &
teleswitch reset
A B C
Remote
Sensor
Knockouts for
bottom cable
entry
1
2
TP75A
TP75AC
3
4
5
Live
Input
Aperture for rear
cable entry
6
A B C
Remote
start-up
circuit
1
2
3
* TP75B
TP75BC
4
5
6
On Off
Heating
7 day
OSC ON
OSC OFF
CHRONO
ON/OFF
Chrono 6
Chrono 3 or 12
A B C
Remote
Sensor
1
2
Remote
start-up
circuit
3
4
5
6
* TP75AB
TP75ABC
Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material, and reserves the right to
alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent
changes being necessary in specifications already agreed.
Danfoss Randall Limited
Ampthill Road
Bedford, MK42 9ER
Tel: (01234) 364621 Fax: (01234) 219705
Email: [email protected]
Website: www.danfoss-randall.co.uk
2
Part No. 320 Iss.7. 03/99