Single inlet centrifugal fans VRD

Transcription

Single inlet centrifugal fans VRD
Single inlet centrifugal fans
VRD
APPLICATION
These single-inlet centrifugal fans are equipped with impulse impellers (backwards included blades). They are designed to handle
high flows at low and medium pressures.
F400 Homologated in accordance with standard EN 12101-3 (CTICM homologation no. CE 1166-CPD-0079), they are suitable for
fume-extraction of car parks or service areas.
DESCRIPTION
The casings, made of pre-galvanised sheet steel, are equipped with a connection sleeve at the inlet and a flange at the discharge.
The paint-finished steel impeller is statically and dynamically balanced and classified as G6.3 in accordance with standard ISO 1940.
The motors supplied as standard have, depending on the application, 230/400V or 400/690V supply voltages. IP55 degree of
protection. Temperature class F.
The bearings are equipped with self-aligning ball-bearings with eccentric ring shaft locking and have a design working life of
approximately 40,000 hours in standard operation (other than fume extraction).
A transmission protection housing (pre-galvanised panels and electro-zinc grille) is supplied as standard.
Housed in a metal angle-bar frame, the casings are positioned in 4 orientations (0°, 90°, 180°, 270°) each available
directions of rotation: clockwise and anti-clockwise (see next page. § “Orientations – Direction of rotation”).
in two
CENTRIFUGAL
S
OPTIONS
►epoxy paint
►special low temperature assembly (-30°C)
DIMENSIONS
400
500
630
710
800
900
1000
A
651
800
999
1121
1255
1408
1541
B
736
918
1157
1303
1460
1648
1810
C
38
50
53
63
74
89
90
D
4.5
5
6
7
7
7
9
E
507
638
801
898
1007
1130
1267
F
256
322
404
453
507
569
638
G
296
372
454
503
557
619
688
H
336
402
504
553
607
669
738
J
355
530
530
630
710
800
900
K
609
748
940
1050
1181
1319
1451
ØP
13x18
13x18
13x18
17x22
17x22
17x22
17x22
L max
400
500
630
710
800
900
1000
a
312
378
460
509
563
625
694
b
563
694
857
954
1063
1186
1323
c
90
90
90
180
180
180
180
d
98
131
172
151.5
178.5
209.5
244
e
200
250
300
400
500
600
700
f
168.5
209
265.5
264
268.5
280
298
g
80
80
80
120
120
120
120
h
50
50
50
50
50
50
50
n
8
8
8
8
12
12
12
Øp
9
9
9
9
9
9
9
Ør
438
541
674
751
837
934
1043
Discharge outlet
DEPENDING ON DRIVE
Inlet
AREM - ZI, chemin des aisières - 45500 Saint-Brisson sur Loire - Tel: 00 33 (0)2.38.36.71.05 - Email : [email protected]
39
Catalogue 2008 Edition
Single inlet centrifugal fans
VRD
ORIENTATION – DIRECTION OF ROTATION
REMINDER ABOUT ORIENTATIONS
For centrifugal fans, whether with single or double inlets at the suction side, the convention states that orientations take the motor
side (direct action) or transmission side as a reference.
If the impeller rotates in the clockwise direction (or “to the right”) its direction will be RD; if it rotates in the anti-clockwise direction its
direction will be LG.
LG 0
POSITIONS
LG 90
OF MOTORS
LG 180
LG 270
RD 0
RD 90
RD 180
RD 270
- CONSTRUCTIONS
CENTRIFUGES
The position of the motor will depend on the space available during the location of the fan. To designate the appropriate position,
specify the orientation (LG or RD) followed by the following motor position number:
1
2
3
4
5
6
ACCESSORIES
1
L
400
400
500
400
630
400
710
450
800
500
900
1
2
SCREEN WITH GRILLE AT DISCHARGE
1000
640
COMPANION FLANGE AT DISCHARGE
LC
400 to 1000
30
2
3
FLEXIBLE SLEEVE AT DISCHARGE
LMR
400 to 1000
195
3
AREM - ZI, chemin des aisières - 45500 Saint-Brisson sur Loire - Tel: 00 33 (0)2.38.36.71.05 - Email : [email protected]
40
Catalogue 2008 Edition
Single inlet centrifugal fans
VRD
ACCESSORIES (cont)
4
FLEXIBLE SLEEVE AT AIR INTAKE
The equipment is supplied equipped with a companion flange at the inlet
whose diameter matches that of the impeller (model size) to receive the
textile F400 approved connection sleeve, fixed using a supplied collar.
4
5
INLET COMPANION FLANGE (with or without joggling)
LM
400 to 1000
65
Used to connect the fan upstream of the flexible hose. A second fixing
strap is required (not supplied).
6
CENTRIFUGAL
S
5
RUN/STOP SWITCH
Accessory fitted pre-wired.
6
7
MOTOR COVER
Provides protection for the motor against rain and against any other spays. It is
fixed directly on the transmission housing.
8
8
ANTI-VIBE MOUNTS
7
LOAD/MOUNT (KG)
A
B
d
Ø60
25
24
76
8,5
Ø80
110
27
100
8,2
Ø100
160
28
124
10
Ø150
250
39
182
12
Generally supplied in quantities of four units.
WEIGHT OF VRD ACCORDING TO HEIGHT OF MOTOR SHAFTS
KG
400
500
630
710
800
900
1000
80
21
30
-
-
-
-
-
90
24
33
46
59
82
100
125
100
33
43
53
71
93
109
135
112
-
45
55
73
95
111
137
132
-
80
90
108
130
146
172
160
-
-
-
-
156
172
197
180
-
-
-
-
-
186
212
200
-
-
-
-
-
-
224
WARNING! These mean values are given only as an indicator
based on motors whose frames are made of aluminium.
AREM - ZI, chemin des aisières - 45500 Saint-Brisson sur Loire - Tel: 00 33 (0)2.38.36.71.05 - Email : [email protected]
41
Catalogue 2008 Edition
Single inlet centrifugal fans
VRD
ASSEMBLY ON CHASSIS
CENTRIFUGAL
S
In the event that a motor may not be adequately supported by the
fan frame alone, chassis mounting is preferred.
This configuration is restricted to standard applications excluding
fume extraction.
AREM - ZI, chemin des aisières - 45500 Saint-Brisson sur Loire - Tel: 00 33 (0)2.38.36.71.05 - Email : [email protected]
42
Catalogue 2008 Edition