On-site diagnosis for cast-resin transformers
Transcription
On-site diagnosis for cast-resin transformers
ON-SITE DIAGNOSIS FOR CAST-RESIN TRANSFORMERS SUMMARY B Louyot FRANCE - TRANSFO, France Cast-resin transformers have been widely used for a long time. These transformers have the advantage of easy installation and improved fire behaviour in case of class F1. To improve even more reliability during operation, an inspection of the transformers may be carried out: onsite partial discharges measurements are a mean to undertake this inspection. ON-SITE PARTIAL DISCHARGES MEASUREMENTS PURPOSE During operation, transformers may be severely stressed: overloading, overvoltages, pollution, conductive particles deposit… Installation conditions may be more or less severe: closely cables, high connection resistance… Some of these installation and operating conditions may lead to deterioration and PD inception. ON-SITE MEASUREMENT TECHNIQUES PD measurements are difficult ones, but are well mastered when they are carried out in workshops after manufacturing. The challenge is to carry out these measurements on site where the transformers are installed and operating. There are some difficulties: lack of accessibility around the transformer, ambient disturbances. To take into account these difficulties, several kinds of detection and localisation may be used: Detection in the Ultrasonic frequency range of the acoustic waves created by PD Detection of the electromagnetic waves created by PD. Electrical measurement with portable instrument All of these kinds of measurement may have advantages and disadvantages. They may be used together to give more pieces of information. ON-SITE MEASUREMENT EXAMPLES For onsite measurements, these 3 kinds of measurements may be used alone or together. It depends on installation conditions, space around the transformer, switching off opportunities. First example: The aim of the measurement was to check transformer electrical ageing. Measurements with US detector and electrical portable instrument were used. Ultrasonic noises coming from the magnetic core were detected: laminates magnetostriction gives noises which frequency range may go up to several ten kHz. Second example: The upper part of the transformer coils was dusty. The aim was to check if this deposit could be harmful by creating partial discharges. Measurements with ultrasonic detector and detection of electromagnetic waves were used: In this case, onsite measurements showed that this dust deposit did not bring measurable partial discharges. Third example: The aim was to check transformer installation. Measurements with US detector and electrical portable instrument were used. In this case, an abnormality was detected: a cable too close from one of the coils. Ultrasonic detection pinpointed this source. Because of rather high level noise, it was not possible to detect these partial discharges by electrical means. CONCLUSIONS The aim of the above examples was to check the operating conditions. Some bad operating conditions may be detected, such as: metal or conducting particles in high electrical field, small clearances between all feeding cables and the surface of the transformer coils. These examples showed feasibility of undertaking an inspection of transformers. Depending on the case, this inspection may be more or less sensitive. Carrying out three kinds of measurements should allow undertaking transformer inspection in many cases. These onsite measurement techniques are a mean to develop diagnosis and help users in improving preventive maintenance. DIAGNOSTIC SUR SITE POUR TRANSFORMATEURS ENROBES RESUME B Louyot FRANCE - TRANSFO, France L’utilisation des transformateurs enrobés est maintenant largement répandue. Ces transformateurs présentent l’avantage de la simplicité d’installation et d’un comportement au feu amélioré avec la classe F1. Pour augmenter la fiabilité en service du matériel, il est intéressant de pouvoir faire un état des lieux des transformateurs en exploitation. Les mesures de décharges partielles sur site sont un moyen prometteur pour faire cet état des lieux. INTERET DES MESURES DE DECHARGES PARTIELLES SUR SITE En exploitation, les transformateurs sont soumis à diverses contraintes : surcharges, surtensions, pollution, dépôt de particules éventuellement conductrices, … Les conditions d’installation peuvent être plus ou moins contraignantes : proximité des câbles d’alimentation, mauvais contacts au niveau des raccordements, … Certaines de ces conditions d’installation et d’exploitation peuvent conduire à des détériorations et à l’apparition de décharges partielles. conditions d’installations, de la place disponible autour du transformateur, des possibilités de consignation. Premier exemple : Le but des mesures était d’évaluer le vieillissement électrique du transformateur. Les mesures par détecteur ultrasons et les mesures électriques par couplage galvanique ont été utilisées. Une émission ultrasonore en provenance du circuit magnétique a été détectée : la magnétostriction des tôles engendre des bruits dont le spectre de fréquence peut monter jusqu’à plusieurs dizaines de kHz. Deuxième exemple : La partie supérieure du transformateur était poussiéreuse. Le but de l’inspection était d’estimer le danger de ces poussières. Les mesures par détecteur ultrason et la détection des ondes électromagnétiques ont été utilisées : les mesures ont montré que le dépôt de poussières n’apportait pas de décharges partielles mesurables. LES TECHNIQUES DE MESURES SUR SITE Troisième exemple : Les mesures de décharges partielles sont des mesures délicates mais maîtrisées quand elles sont effectuées en usine en fin de chaîne de fabrication des transformateurs enrobés. La problématique est donc d’effectuer de telles mesures sur les sites d’installation et d’exploitation des transformateurs. Les difficultés sont les suivantes : manque d’accessibilité autour du transformateur, perturbations ambiantes rayonnées ou transmises dans la gamme de fréquences du phénomène de décharges partielles. Compte tenu de ces difficultés, plusieurs types de détection et de localisation peuvent être utilisées : Détection des ondes acoustiques générés par les décharges partielles, dans le domaine des ultrasons Détection des ondes électromagnétiques générés par les décharges partielles Mesure électrique avec matériel portable Chacun de ces types de mesure a ses avantages et inconvénients. Tous ces types peuvent être complémentaires. Le but était de vérifier l’installation du transformateur. Les mesures par détecteur ultrasons et les mesures électriques par couplage galvanique ont été utilisées. Un défaut a été détecté : un câble passait trop près d’une des bobines. La détection ultrasonique l’a très bien mis en évidence alors que la mesure électrique n’était pas sensible du fait d’un bruit de fond important. CONCLUSIONS Le but des essais cités était de vérifier les conditions d’exploitation des transformateurs. Certaines conditions d’exploitation anormales peuvent être détectées : particules métalliques ou conductrices dans un champ électrique élevé, distances insuffisantes entre câbles et surface des bobines. Ces exemples montrent la faisabilité d’inspection de transformateurs. Suivant les cas, ce diagnostic peut être plus ou moins sensible. La mise en œuvre de trois types de mesures différentes devrait permettre d’entreprendre un diagnostic dans beaucoup de cas. EXEMPLES DE MESURES SUR SITE Pour les mesures sur site, toutes ou partie des types de mesures peuvent être utilisées, en fonction des Ces techniques de mesures sur site permettent de développer le diagnostic et d’aider les exploitants dans l’amélioration de la maintenance préventive. ON-SITE DIAGNOSIS FOR CAST-RESIN TRANSFORMERS B Louyot FRANCE - TRANSFO, France Cast-resin transformers have been widely used for a long time. These transformers have the advantage of easy installation and improved fire behaviour in case of class F1. Climatic and environmental classification tests E2 and C2 show these transformers have a good behaviour under severe operating conditions. Experience shows their good reliability. To improve even more this reliability during operation, an inspection of the transformers may be carried out: on-site partial discharges measurements are a mean to undertake this inspection. These onsite diagnoses could show abnormal situations such as: too stressed operating conditions, too severe installation conditions, abnormal ageing of the transformer, … All these events may create partial discharges. In this case, transformer life-time may be shortened, depending on partial discharge harmfulness. ON-SITE PARTIAL DISCHARGE MEASUREMENT PURPOSE Partial discharge measurements were measured on HV terminals according to IEC 270, during an inducedvoltage test up to 1.5 Um (Um = 24 kV for this transformer). Results (see table 1) show that for some conductive path, partial discharges appear for voltages lower than rated voltage. These partial discharges are located on the surface of the coil on the conductive path border. With time, they may lead to electrical breakdown. TABLE 1 – Partial Discharge measurements Voltage (kV) Partial discharge (pC) <5 <5 55 10 <5 <5 425 20 Without With two With one large patch patches patch 170 mm 30x30 mm height, 30 mm wide Examples of conductive patches on outer side of HV cast-resin coil: After transformer manufacturing, several quality control tests are carried out. Among these, checking that they are partial discharge free. No manufacturing defect nor design defect should bring partial discharge inception at voltages around rated voltage. If there is such defect, its harmfulness will lead to transformer collapse, more or less rapidly. During operation, transformers may be more or less severely stressed: overloading, overvoltages, pollution, conductive particles deposit… Installation conditions may be more or less severe: closely cables, high connection resistance, … Some of these installation and operating conditions may lead to deterioration and partial discharge inception. EXAMPLES OF PARTICULAR OPERATING CONDITIONS With two patches 30x30 mm With one large patch 170 mm height, 30 mm wide Conductive particles deposit Examples of ageing under partial discharges Laboratory experiments have been carried out to simulate the effect of conductive particles deposit on cast-resin HV coils. For these experiments, silver lack was used to simulate conductive patches on outer side of coil, for a 400 kVA, 20 kV transformer. Behaviour of electromechanical materials Laboratory experiments have been carried out to assess the behaviour of electromechanical materials operating with partial discharges. Partial discharges can be measured continuously during operation until breakdown. But measurement analysis and interpretation vs. life duration are still in progress. FIGURE 1 – partial discharges during operation for a 30 kV rotating machine bar Life duration for enamelled wire Life duration under electrical field was assessed for enamelled wires. Voltage was applied between the two wires of a twisted pair as shown on photograph. The twisted pairs may be cast or not. For cast-resin twisted pairs, no partial discharge occurred before breakdown. For bare twisted pairs, partial discharges appeared around 800 V. In this case, life duration under partial discharges vs electrical field could be assessed. FIGURE 2 – partial discharges measurement on bare twisted pair FIGURE 3 – life duration under partial discharges vs electrical field 100000 10000 Time Failure time to failure (h) 1000 100 10 1 5 7 9 electrical field (kV/mm) 11 13 ON-SITE MEASUREMENT TECHNIQUES Partial discharge measurements are difficult ones, but are well mastered when they are carried out in workshops after manufacturing. The challenge is to carry out these measurements on site where the transformers are installed and operating. There are some difficulties: Lack of accessibility around the transformer Ambient disturbances To take into account these difficulties, several kinds of detection and localisation may be used: Detection in the ultrasonic frequency range of the acoustic waves created by partial discharges Detection of the electromagnetic waves created by partial discharges. Electrical measurement All of these kinds of measurement may have advantages and disadvantages. They may be used together to give more pieces of information. Detection in the ultrasonic frequency range of the acoustic waves created by partial discharge Discharges in air or on solid insulation material surfaces create acoustic pressure waves that may be detected by an ultrasonic receiver. Within ultrasonic frequency range, detection sensitivity is rather good and noise level rather low. Measuring system is made of an ultrasonic sensor, a parabolic reflector. The ultrasonic signals are converted into audible signals via an earphone. Detection level is around some 10 picoCoulombs or so. Partial discharge searching is made around the transformer with a clearance according to safety rules. This kind of detection method does not allow detecting internal partial discharge within the windings, due to bad propagation within polymeric materials. This method detects as well other acoustic wave sources than partial discharges: for example magnetic laminates vibrations. It may as well be disturbed by wave reflections. This method is a very good one to pinpoint ultrasonic sources in air. Detection of the electromagnetic waves created by partial discharges Electromagnetic transients created by partial discharges may be picked-up and measured by means of capacitive or inductive sensors. Searching may be made with the apparatus around the transformer with a clearance according to safety rules. Sensitivity is nevertheless rather poor. If switching off the transformer is possible, the apparatus may be placed closer to the transformer on an insulated tripod. Sensitivity is then fine. Detection and localisation within the transformer is then possible. Electrical measurement When electrical measurement is possible, it must be carried out according to IEC 726 standard, dealing with dry-transformers. It needs a lot of materials. For example, for a 3-phase transformer: a 3-phase supply, 3 capacitors, and partial discharge measuring device. It is the only way to carry out measurements that give reliable results. Unfortunately, there are often disturbances in electrical areas and noise level is rather high. In case such a measurement is not possible, some portable device may be used: it is connected to one of the transformer terminals and isolated from ground or any metallic part. The measured signal is transmitted by means of an optic fibre and processed. This method which allows measurement on terminals, may detect internal and external partial discharges and is a sensitive one. But it may give erroneous results: measurements conditions are not at all the same than according to IEC 726, concerning potential to earth for example. Thus, one must consider that this method gives only indication. ON-SITE MEASUREMENT EXAMPLES For onsite measurements, these 3 kinds of measurements may be used alone or together. It depends on installation conditions, space around the transformer, switching off opportunities. First example: The aim of the measurement was to check transformer electrical ageing. Measurements with US detector and electrical portable instrument were used: first, searching with the ultrasonic detector showed noises in the upper part of the transformers, near the magnetic core. Then, electrical measurements with galvanic coupling were carried out: they showed there was no partial discharges above the noise level (3 pC). It seemed that the detected ultrasonic noises were coming from the magnetic core: laminates magnetostriction gives noises which frequency range may go up to several ten kHz. Second example: The upper part of the transformer coils was dusty. The aim was to check if this deposit could be harmful by creating partial discharges. Measurements with ultrasonic detector and detection of electromagnetic waves were used: ultrasonic noises were detected but only near the magnetic core. For detection of electromagnetic waves, the instrument was put on an isolated tripod very near the transformer, during interruption of high voltage. It was placed where the ultrasonic noises had been located. In these conditions, detection level was relatively low. These last measurements showed there were no partial discharge above the noise level (15 pC). In this case, onsite measurements showed that this dust deposit did not bring measurable partial discharges. Third example: The aim was to check transformer installation. Measurements with US detector and electrical portable instrument were used: First, searching with the ultrasonic detector showed noises in the upper part of the transformers, near the magnetic core. Noise was also detected between one of the transformer coil and a LV cable situated along the coil, 10 cm from its surface. Then, electrical measurements with galvanic coupling were carried out: they showed there was no partial discharges above the noise level (50 pC). In this case, an abnormality was detected: a cable too close from one of the coils. Ultrasonic detection pinpointed this source. Because of rather high level noise, it was not possible to detect these partial discharges by electrical means. CONCLUSIONS Partial discharge measurements on site are not contractual for transformers. Their aim is to check operating conditions. Some bad operating conditions may be detected, such as: metal or conducting particles in high electrical field, small clearances between all feeding cables and the surface of the transformer coils. The above examples showed feasibility of undertaking an inspection of transformers. Depending on the case, this inspection may be more or less sensitive. Carrying out three kinds of measurements should allow undertaking transformer inspection in many cases. These onsite measurement techniques are a mean to develop diagnosis and help users in improving preventive maintenance. References: Kreuger F.H, 1989, “partial discharge detection in high-voltage equipment”, Butterworth & Co, London, UK . IEC 60270, 1981, “partial discharge measurement, Geneva, Switzerland . Bartnikas R and McMahon E.J., 1984, “Engineering dielectrics: corona measurement and interpretation”, volume 1,ASTM, Philadelphia, USA .