Installation and Maintenance Liquid Level Switches
Transcription
Installation and Maintenance Liquid Level Switches
General Information Renseignements Généraux 1. Switches should be installed rigidly so the float or floats are free to move as the liquid level changes. 2. Switches should be mounted in a tank area free of severe turbulence or protected from such turbulence by appropriate and adequate slosh shields. 3. Vertical switch stems should be vertical for best results, but satisfactory operation is possible in most liquids with the stem at up to a 30˚ angle from vertical. 4. Side mount switch stems must be mounted with the arrow vertically either up or down depending on switch operation. 5. Care should be taken that switches are always operated within electrical ratings. 6. Orientation for standard Vertical switches can be changed from normally open to normally closed dry or vice versa by removing the float and reversing it in the stem, except with the M3326. 1. On doit installer les commutateurs solidement pour que le flotteur ou les flotteurs puissent se déplacer librement quand le niveau de liquide change. 2. On doit installer les commutateurs dans un endroit du réservoir sans turbulence ou protégé contre une telle turbulence par des caches anti-remous appropriés et adéquats. 3. Les meilleurs résultats sont atteints si les tubes des commutateurs sont verticales, mais une opération satisfaisante est possible dans la plupart des liquides avec un tube à un angle de 30° à la verticale. 4. Les tubes des commutateurs montés du côté doivent être montés avec la flèche verticalement vers le haut ou vers le bas suivant l’opération du commutateur. 5. Il faut assurer que les commutateurs sont toujours opérés dans les conditions des valeurs nominales électriques. 6. L’Orientation pour des Commutateurs Verticales Standard peuvent être changés de normalement ouvert à normalement fermé à sec ou vice-versa, en démontant le flotteur et en l’inversant sur le tube, excepté avec le M3326. Maintenance Cautions Précautions Maintenance should consist of inspection to see that the float is free to move and not coated with any substance, which would change its weight or volume significantly. If this occurs, the float should be cleaned. This is easily accomplished without disturbing the installation. In addition, the stem may be wiped down to remove any build-up. 1. The pressure, temperature and electrical limitations shown for the specified level switches must not be exceeded. 2. The pressures and temperatures must take into consideration possible surges in the temperature and pressure of the system. 3. The liquids used must be compatible with the materials of construction. Specifications of materials will be given upon request. 4. Life expectancy of the switch varies with applications. Contact the factory if life cycle testing is required. 5. Ambient temperature changes can affect switch set points, since specific gravities of liquids vary with temperature. Consult factory for assistance. 6. Level switches have been designed to be shock and vibration resistant. For maximum life, both shock and vibration should be minimized. Consult factory for assistance. 7. Excessive contaminants in fluid may inhibit float operation, and occasional wipe down may be necessary. 8. Level switches must not be field repaired 9. Physical damage to product may render product unserviceable. 10. Installation in a vessel made from magnetic materials may affect operation. 1. On ne doit pas dépasser les limites de pression, de température et electriques indiquées pour les commutateurs de niveau specifiés. 2. Ces pressions et températures doivent prendre en considération les possibilités de montée de température et de pression du système. 3. On doit utiliser des liquides compatibles avec les matériaux de construction. On peut obtenir sur demande le détail des matériaux. 4. La durée de vie des commutateurs varie selon les applications. Consultez l’usine s’il faut un cycle d’essai de durée de vie. 5. Les variations de température ambiante peuvent affecter les points de consigne des commutateurs puisque le poids volumique des liquides varie selon la température. Consultez l’usine pour obtenir de l’aide. 6. Les commutateurs de niveau ont été conçus pour résister aux chocs et aux vibrations. Mais pour une durée de vie maximale, il est préférable de les minimiser. Consultez l’usine pour obtenir de l’aide. 7. Une teneur excessive de contaminants dans le liquide peut enrayer le mécanisme de flottaison et un nettoyage occasionel peut être requis. 8. Les commutateurs de niveau ne doivent pas être réparés sur place. 9. Des dommages matériels peuvent rendre le produit inutilisable. 10. Installation dans un vaisseau magnétique peut affecter l’opération. Installation and Maintenance Liquid Level Switches English • Français Madison Company 27 Business Park Drive Branford, CT 06405 (203) 488-4477 • Fax (203) 481-5036 E-mail: [email protected] www.madisonco.com ISO 9001 Certified ECN #5936 • Effective Date 10/2011 • MF-002, Rev. F The only repair possible in the field is replacement of either the float or stem. Dents or nicks on the float are usually of no consequence to operation. Entretien L’entretien devrait comporter une inspection afin de vérifier que le flotteur se déplace librement et qu’il n’est pas recouvert d’une substance quelconque pouvant en modifier le poids ou le volume de manière importante. Si cela se produit, il faut enlever le flotteur et le nettoyer, ce qui se fait facilement sans troubler l’installation. De plus, il faut essuyer le tube pour enlever toute accumulation qui s’y trouve. La seule réparation possible sur place est le remplacement du flotteur ou du tube. Normalement, des bosses ou encoches dans le flotteur n’influencent pas l’opération. Installation Operation is stated in the tank dry position. Vertical Switches: NC Operation: SS Floats: Witness mark (round circle) down. Plastic Floats: Magnets up. NO Operation: SS Floats: Witness mark (round circle) up. Plastic Floats: Magnets down. *Note: M3326, M3326-NO are not reversible. The M3326 is Normally Closed. The M3326-NO is Normally Open Side Mounted Switches: NC Operation: Arrow mounted vertically pointed down. NO Operation: Arrow mounted vertically pointed up. Installation L’Opération est indiquée dans une position à sec du réservoir. Commutateurs Verticaux: NC Opération: SS Flotteur: Marque de repère (cercle rond) vers le bas. Flotteurs en plastique: Aimants vers le haut. NO Opération: SS Flotteurs: Marque de repère (cercle rond) vers le haut. Flotteurs en plastique: Aimants vers le bas. *Remarque: M3326, M3326-NO sont irreversibles. Normalement, le M3326 est Fermé Normalement, le M3326-NO est Ouvert. Commutateurs montés du côté: NC Opération: Flèche montée verticalement vers le bas. NO Opération: Flèche montée verticalement vers le haut. Wiring Typical Current and Voltage Ratings * Note: The ratings at right are for resistive loads only. For inductive loads, maximum switch life will be achieved if appropriate arc suppression is used. Watts 15 30 * Remarque: Les valeurs nominales à droite sont uniquement pour les charges résistives. Pour les charges, la durée de vie maximale sera atteinte si une suppression d’arc appropriée est utilisée. 60 100 Voltage Current Amps 240 AC 120 AC 100 DC 24 DC 240 AC 120 AC 120 DC 24 DC 240 AC 120 AC 120 DC 24 DC 240 AC 120 AC 120 DC 24 DC 0.30 0.30 0.14 0.28 0.07 0.28 0.40 0.50 0.20 0.50 0.40 1.00 0.40 1.00 Approvals Autorisations (See details for part number specific approvals on reverse.) (voir les détails au verso pour les autorisations spécifiques du numéro de partie). 1. UL 2. UL Haz Loc 3. Ulc 4. CSA 5. CSA Haz Loc 6. CE 7. NSF 8. Demko CEX Madison Part Number: Madison Numéro de Partie: Switch Location (from bottom of fitting) Colors Watt Rating Switch Type Dry Position Liquid Level Switch Details by Part Number Part Number Materials Max. Temp. Mounting Max. Pressure Elec. Rating Approvals Notes (PSIG) (Watts) (see reverse for key) (see reverse for key) 60 60 60 60 60 60 60 60 60 60 100 100 100 100 2, 5, 6, 7, 8 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 6, 7 6, 7 6 6, 7 6 300 300 100 100 100 150 150 150 150 15 50 50 30 30 30 30 30 30 30 30 30 30 15 15 1, 4, 6, 7 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 6, 7 1, 6 1, 6 300 300 300 100 100 100 100 100 100 100 100 100 100 300 100 100 100 100 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 2, 4, 6, 7, 8 2, 4, 6, 7 2, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 200 200 150 150 100 100 100 15 300 300 150 150 100 100 100 200 100 60 60 60 60 60 60 60 60 30 30 30 30 30 30 30 60 30 2, 5, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 6 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6 1, 4, 6, 7 (stem, float) Standard Full-Size Vertical M5600 M5400 M5917 M8800 M8600 M8400 M7800 M4300 M4600 M9800 M5600-PR M8060-PR M8800-PR M7800-PR 316 SS Brass, 316 SS 316 SS Polypropylene 316 SS, Polypropylene Brass, Polypropylene PBT, Buna-N Brass, Buna-N 316 SS, Buna-N Kynar 316 SS CPVC, Polypropylene Polypropylene PBT, Buna-N 200˚C 200˚C 250˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C 105˚C 105˚C 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 200 200 200 100 100 100 150 150 150 15 500 100 100 150 1 1 Standard Miniature Vertical M5000 M5040 M8000 M8020 M8040 M7000 M4500 M4400 M4008 M9000 M3326 M3326-NO 316 SS Brass, 316 SS Polypropylene 316 SS, Polypropylene Brass, Polypropylene PBT, Buna-N Brass, Buna-N 316 SS, Buna-N Polypropylene, Buna-N Kynar Polypropylene Polypropylene 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C M5900 M5910 M5920 M7790 M7740 M7700 M7725 M7750 M8700 M8725 M8740 M8750 M8790 M5010 M4010 M9700 M9750 M9740 316 SS 316 SS 316 SS PBT PBT PBT PBT PBT Polypropylene Polypropylene Polypropylene Polypropylene Polypropylene 316 SS Brass, Buna-N Kynar Kynar Kynar 200˚C 200˚C 200˚C 150˚C 150˚C 150˚C 150˚C 150˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C 105˚C 105˚C 105˚C M5602-XXXX M5402-XXXX M4302-XXXX M4602-XXXX M8802-XXXX M8602-XXXX M8402-XXXX M9802-XXXX M5002-XXXX M5042-XXXX M4502-XXXX M4402-XXXX M8002-XXXX M8042-XXXX M8080-XXXX M5605 M8085 316 SS Brass, 316 SS Brass, Buna-N 316 SS, Buna-N Polypropylene 316 SS, Polypropylene Brass, Polypropylene Kynar 316 SS Brass, 316 SS Brass, Buna-N 316 SS, Buna-N 316 SS, Polypropylene Brass, Polypropylene Polypropylene 316 SS Polypropylene 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 3/8-16 BH 3/8-16 BH 1 2 2 Standard Horizontal 1 x 1/2 NPT 1/2 x 1/4 NPT 1/2 x 1/2 NPT 5/8-11 BH 3/4-16 x 7/8-14 1/2 x 1/2 NPT 1/2 NPT 1/2 NPT 1/2 x 1/2 NPT 1/2 NPT 3/4-16 x 7/8-14 1/2 NPT 5/8-11 BH 3/8-24 BH 3/8-24 BH 1/2 x 1/2 NPT 1/2 NPT 3/4-16 x 7/8-14 1 1 1 1 1 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 Configured (Multi-Level) X X X X X X X X X X X X X X X 1/2 NPT 1/4 NPT Notes: 1. PBT is not for use in water above 65˚C (150˚F). 2. The M3326 is Normally Closed. The M3326-NO is Normally Open. 3. Model No. Switch Location Colors Watt Rating Switch Type Dry Position (from bottom of fitting) M5605 M8085 1.25" 5.75" 0.75" 5.75" Red Black Red Black 60 60 60 60 SPST SPST SPST SPST NC NC NC NC 3 3 Détails pour le Commutateur de Niveau de Liquide par Numéro de Partie Numéro de Partie (tube, flotteur) M5600 M5400 M5917 M8800 M8600 M8400 M7800 M4300 M4600 M9800 M5600-PR M8060-PR M8800-PR M7800-PR 316 SS Laiton, 316 SS 316 SS Polypropylène 316 SS, Polypropylène Laiton, Polypropylène PBT, Buna-N Laiton, Buna-N 316 SS, Buna-N Kynar 316 SS CPVC, Polypropylène Polypropylène PBT, Buna-N 200˚C 200˚C 250˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C 105˚C 105˚C M5000 M5040 M8000 M8020 M8040 M7000 M4500 M4400 M4008 M9000 M3326 M3326-NO 316 SS Laiton, 316 SS Polypropylène 316 SS, Polypropylène Laiton, Polypropylène PBT, Buna-N Laiton , Buna-N 316 SS, Buna-N Polypropylène, Buna-N Kynar Polypropylène Polypropylène 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C M5900 M5910 M5920 M7790 M7740 M7700 M7725 M7750 M8700 M8725 M8740 M8750 M8790 M5010 M4010 M9700 M9750 M9740 316 SS 316 SS 316 SS PBT PBT PBT PBT PBT Polypropylène Polypropylène Polypropylène Polypropylène Polypropylène 316 SS Laiton, Buna-N Kynar Kynar Kynar 200˚C 200˚C 200˚C 150˚C 150˚C 150˚C 150˚C 150˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C 105˚C 105˚C 105˚C M5602-XXXX M5402-XXXX M4302-XXXX M4602-XXXX M8802-XXXX M8602-XXXX M8402-XXXX M9802-XXXX M5002-XXXX M5042-XXXX M4502-XXXX M4402-XXXX M8002-XXXX M8042-XXXX M8080-XXXX M5605 M8085 316 SS Laiton, 316 SS Laiton, Buna-N 316 SS, Buna-N Polypropylène 316 SS, Polypropylène Laiton, Polypropylène Kynar 316 SS Laiton, 316 SS Laiton, Buna-N 316 SS, Buna-N 316 SS, Polypropylène Laiton, Polypropylène Polypropylène 316 SS Polypropylène 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 200˚C 105˚C 105˚C 105˚C 105˚C 105˚C 200˚C 105˚C Matériaux Temp. Max. Le Montage Max. Pression Électricité Autorisations Remarques (PSIG) (Watts) (voir au verso pour la légende) (voir au verso pour la légende) Niveau Grand Format Vertical Standard 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 1/4 NPT 200 200 200 100 100 100 150 150 150 15 500 100 100 150 60 60 60 60 60 60 60 60 60 60 100 100 100 100 2, 5, 6, 7, 8 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 6, 7 6, 7 6 6, 7 6 1 1 Niveau Miniature Vertical Standard 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 1/8 NPT 3/8-16 BH 3/8-16 BH 30 30 30 30 30 30 30 30 30 30 15 15 1, 4, 6, 7 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 6, 7 1, 6 1, 6 300 300 300 100 100 100 100 100 100 100 100 100 100 300 100 100 100 100 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 2, 4, 6, 7, 8 2, 4, 6, 7 2, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 200 200 150 150 100 100 100 15 300 300 150 150 100 100 100 200 100 60 60 60 60 60 60 60 60 30 30 30 30 30 30 30 60 30 2, 5, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6 1, 6 1, 4, 6, 7 1, 4, 6 1, 4, 6 1, 4, 6 1, 4, 6, 7 1, 4, 6 1, 4, 6, 7 300 300 100 100 100 150 150 150 150 15 50 50 1 2 2 Niveau Horizontal Standard 1 x 1/2 NPT 1/2 x 1/4 NPT 1/2 x 1/2 NPT 5/8-11 BH 3/4-16 x 7/8-14 1/2 x 1/2 NPT 1/2 NPT 1/2 NPT 1/2 x 1/2 NPT 1/2 NPT 3/4-16 x 7/8-14 1/2 NPT 5/8-11 BH 3/8-24 BH 3/8-24 BH 1/2 x 1/2 NPT 1/2 NPT 3/4-16 x 7/8-14 1 1 1 1 1 1, 4, 6, 7 1, 4, 6, 7 1, 4, 6, 7 Configuré (Multiniveaux) X X X X X X X X X X X X X X X 1/2 NPT 1/4 NPT Remarques : 1. PBT n’est pas pour être utilisé dans l’eau au-dessus 65°C (150°F). 2. Normalement, le M3326 est Fermé. Normalement, le M3326-NO est Ouvert. 3. Model No. Switch Location Colors Watt Rating Switch Type Dry Position (from bottom of fitting) M5605 M8085 1.25" 5.75" 0.75" 5.75" Red Black Red Black 60 60 60 60 SPST SPST SPST SPST NC NC NC NC 3 3