ELESTA energy control AG

Transcription

ELESTA energy control AG
Specification: communication protocol
Modbus <--> RDO3xx,
datapoints and domains tables
S.Stäger, A.Pichonnat
18.06.2013
ELESTA
energy control
Version: 1.26
Pages: 1 - 35
1. Introduction (English)
An other document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) describes the Modbus communication protocole and the calcul of
the Modbus datapoint index.
Abbreviations:
• RDO3xx
RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc.
• DHW
Domestic hot water
• DH
District heating
• R
Read only
• R/W
Read/Write
• DP
Data point
• Appl.ID
Application Identification
• NaN
Not An Number
Common definitions:
• In this document, hex values will be defined with 0x. For example 0xa (hex) means 10 (dez)
Appl.ID:
• Main controller (all DP’s which are not indexed): 0
• Heating circuit parameter: 0, 1..7 (appl. ID=0 will be interpreted as 1, 1 = heating circuit 1, 7 = heating circuit 7)
• Boiler circuit (cascade) parameter: 0, 11..14 (appl. ID=0 will be interpreted as 11, 11 = boiler circuit 1, 14 = boiler circuit 4)
• DHW circuit parameter: 0, 21..24 (appl. ID=0 will be interpreted as 21, 21 = DHW circuit 1, 24 = DHW circuit 4)
Remark: RDO3x4 supports only 1 boiler circuit (no cascade) and 1 DHW circuit
Data points:
• The data points values (always 4 bytes long) is defined by RDO300 as float
• A data point means one value. For example: parameter 101
• A list of contiguous data points can be queried. Undefined data points will be returned as NaN (0xffc00000) on RDO383 since V4.00ßA and on RDO374 since
V4.10
• By writing data points, it is only possible to query max. 1 data point per message (1 data point: 4 bytes, 2 words)
Domains:
• The domain values (various length) is defined separately (normally not float)
• A domain means a list of values. For example: time/date with hour, min, s, etc.
164302/06.2013
1
• A list of contiguous domains can be queried
• By writing domains, it is only possible to query max. 1 domain per message (1 domain: n bytes, n/2 words, domain dependency)
Message definitions:
• It is possible to query max. 32 words (64 bytes) per message
• Always whole datapoints resp. Domain must be treated
• Only RTU mode is supported
Document overview:
• Chapter 2 gives the rules of calculation of the modbus index of data points ans domains starting from the RDO-COM numbers of data points and domains. The
reading of this chapter is normally not necessary, go directly to chapter 3 (Table of modbus index)
• Chapter 3: listing of the data like the RDO300-MMI. Look at the corresponding RDO3xx User manual for the signification, the format and the layout of the
parameter
1. Einleitung (Deutsch)
Ein anderes Document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) beschreibt das Modbus Kommunikationsprotokoll und die
Berechnung der Modbus-Datenpunkte-Index.
Abkürzungen:
• RDO3xx
RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc.
• DHW
Warmwasser (WW)
• DH
Fernwärme
• R
Nur lesen
• R/W
Lesen/schreiben
• DP
Datenpunkt
• Appl.ID
Applikationsidentifikation
• NaN
Undefinierter Wert
Übersetzungen:
• Data point
Datenpunkt
• Domain
Domain
• Time/date
Zeit/Datum
• Holidays
Ferien
• Clocks
Schaltuhr
• Heating circuit
Heizkreis
• Domestic water circuit
Warmwasserkreis
• Boiler circuit
Kesselkreis
• Free circuit
Freier Uhrenkanal
• Swich point
Schalpunkt
• Set value
Sollwert
• Actual value
Istwert
• Sensor
Fühler
164302/06.2013
2
• User level
Benutzerebene
• Specialist level
Fachmannebene
• Parameter
Parameter
• Counters
Zähler
• Relays
Relais
Allgemeine Definitionen:
• In diesem Dokument, sind die Hex-Werte mit 0x definiert. Beispiel 0xa (hex) steht für 10 (dez)
Appl.ID:
• Hauptregler (alle DP, welche nicht indexiert sind): 0
• Heizkreisparameter: 0, 1..7 (appl.ID=0 ist interpretiert wie 1, 1 = Heizkreis1, 7 = Heizkreis7)
• Kesselkreisparameter (Kaskade): 0, 11..14 (appl.ID=0 ist interpretiert wie 11, 11 = Kesselkreis1, 14 = Kesselkreis4)
• Warmwasserkreisparameter: 0, 21..24 (appl.ID=0 ist interpretiert wie 21, 21 = Warmwasserkreis1, 24 = Warmwasserkreis4)
Bemerkung: RDO3x4 besitzt nur 1 Kesselkreis (keine Kaskade) et 1 Warmwasserkreis
Datenpunkte:
• Die Datenpunktwerte (immer 4 Bytes lang) sind in den RDO300-Reglern als „float“-Werte definiert
• Ein Datenpunkt entspricht ein Wert. Beispiel: Parameter 101
• Die Abfrage einer Liste von benachbarten Datenpunkten ist möglich. Die undefinierte Datenpunkte werden als NaN (0xffc00000) zurückgegeben. Bei RDO383
ab V4.00ßA und bei RDO374 ab V4.10
• Beim schreiben, kann nur ein Datenpunkt per Meldung verarbeitet werden (1 Datenpunkt: 4 Bytes, 2 Words)
Domains:
• Die Domain-Werte (variable Länge) sind separat definiert (normalerweise nicht „float“)
• Ein Domain entspricht eine Wertliste. Beispiel: Zeit/Datum mit Stunden, Minuten, etc.
• Die Abfrage einer Liste von benachbarten Domains ist möglich
• Beim schreiben, kann nur ein Domain per Meldung verarbeitet werden (1 Domain: n Bytes, n/2 Words, abhängig vom Domain)
Meldungsdefinitionen:
• Per Meldung können Maximum nur 32 Words (64 Bytes) verarbeitet werden
• Es müssen immer ganze Datenpunkte resp. Domain behandelt werden
• Nur der RTU Modus ist unterstützt
Dokumentsübersicht:
• Der Rest des Dokuments wird nicht übersetzt, da der benutzte Wortschatz sehr einfach ist
• Kapitel 2 gibt die Rechnungsregeln der Datenpunkt und Domain Index ab den RDO-com Datenpunkt und Domain Nummern. Die Lektüre dieses Kapitels ist
normalerweise nicht notwendig, direkt auf Kapitel 3 gehen (Modbus Indextisch)
• Kapitel 3: Die Liste der Daten bezieht sich auf die Schnittstelle Mensch-Maschine (MMI) des RDO300. Für die Bedeutung, das Format und die Struktur der
Parameter, siehe das entsprechende Benutzerhandbuch RDO3xx.
1. Introduction (Français)
Un autre document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) décrit le protocole de communication Modbus et le calcul des
index des point de données Modbus.
Abréviations:
164302/06.2013
3
• RDO3xx
RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc.
• DHW
Eau chaude sanitaire (ECS)
• DH
Chauffage urbain
• R
Lecture seulement
• R/W
Lecture/écriture
• DP
Point de donnée (PD)
• Appl.ID
Identification d’application
• NaN
Valeur indéfinie
Traductions:
• Data point
Point de donnée
• Domain
Domaine
• Time/date
Heure/date
• Holidays
Vacances
• Clocks
Horloges
• Heating circuit
Circuit de chauffage
• Domestic water circuit
Circuit ECS
• Boiler circuit
Circuit de chaudière
• Free circuit
Horloge auxiliaire
• Swich point
Point de commutation
• Set value
Consigne
• Actual value
Valeur actuelle
• Sensor
Sonde
• User level
Niveau utilisateur
• Specialist level
Niveau spécialiste
• Parameter
Paramètre
• Counters
Compteur
• Relays
Relais
Définitions générales:
• Dans ce document, les valeurs hex sont définies par 0x. Par exemple 0xa (hex) représente 10 (déc)
Appl.ID:
• Régulateur principal (tous les PD qui ne sont pas indexés): 0
• Paramètres des circuits de chauffage: 0, 1..7 (appl.ID=0 est interprété comme 1, 1 = circuit de chauffage 1, 7 = circuit de chauffage 7)
• Paramètres des circuits de chaudière (cascade): 0, 11..14 (appl.ID=0 est interprété comme 11, 11 = circuit de chaudière 1, 14 = circuit de chaudière 4)
• Paramètres des circuits ECS: 0, 21..24 (appl.ID=0 est interprété comme 21, 21 = circuit ECS 1, 24 = circuit ECS 4)
Remarque: RDO3x4 supporte seulement 1 circuit de chaudière (pas de cascade) et 1 circuit ECS
Points de donnée:
• Les valeurs des points de donnée (toujours 4 bytes de long) sont définies dans les régulateurs RDO300 comme valeurs flottantes
• Un points de donnée signifie une valeur. Par exemple: paramètre 101
• L’interrogation d’une liste de points de donnée contigus est possible. Les points de donnée indéfinis sont retournés comme NaN (0xffc00000) par RDO383
depuis V4.00ßA et par RDO374 depuis V4.10
164302/06.2013
4
• En écriture, il n’est possible de traiter qu’un seul point de donnée par message (1 point de donnée: 4 bytes, 2 words)
Domaines:
• Les valeurs des domaines (de longueur variable) sont définis séparément (normalement pas de valeur flottante)
• Un domaine représente une liste de valeurs. Par exemple: heure/date avec heure, minutes, etc.
• L’interrogation d’une liste de domaines contigus est possible
• En écriture, il n’est possible de traiter qu’un seul domaine par message (1 domaine: n bytes, n/2 words, en fonction du domaine)
Définitions des messages:
• Il est possible de traiter 32 words (64 bytes) au maximum par message
• Les points de données resp. les domaines doivent toujours être traités entièrement
• Seul le mode RTU est supporté
Vue d’ensemble du document:
• Le reste du document n’est pas traduit, le vocabulaire utilisé étant très simple
• Le chapitre 2 donne la règle de calcul des index de points de données et de domaine Modbus à partir des numéros de points de données et de domaine RDOcom. La lecture de ce chapitre n’est normalement pas nécessaire, se porter directement chapitre 3 (Table d’index modbus)
• Chapitre 3: la liste des données se rapporte à l’interface homme-machine (MMI) du RDO300. Voir le Manuel de l’utilisateur RDO3xx correspondant pour la
signification, le format et la structure des paramètres.
164302/06.2013
5
2. Calculation of Modbus index from RDO-com number
Circuits (applications) conversion
Name
• General control
• Heating circuit
• Boiler circuits
• Domestic water circuits
• Free circuit
RDO
0
1..7
11..14
21..24
91
Modbus
0
1..7
11..14
16..19 (21 => 16, ...)
9
Remarks
Heating circuit 1, Domestic water circuit 1, boiler circuit 1, ...
11 = Boiler circuit 1
21 = Domestic water circuit 1
Data points
• Basis offset in Modbus index: 0
• Circuit offset factor in Modbus index: 0x800 => Max. 1024 circuit/circuit
• Index band: 0x0..0x9fff (40960 words => 20480 datapoints)
Remarks:
• The Modbus protocol allows only 2 bytes words. So 1 data point will be defined as 2 words (4 bytes).
• Only complete circuit can be transferred. So the Modbus index by circuit must always be even.
=> Modbus index calculation:
• (circuit * 0x800) + (data point * 2)
Data point Examples
• General control, data point 0x15
• Heating circuit 1, data point 0xa
• Boiler circuit 1, data point 0x15
• Domestic water circuit 1, data point 0x74
=> (0 * 0x800) + (0x15 * 2) = 0x002a
=> (1 * 0x800) + (0xa * 2) = 0x0814
=> (11 * 0x800) + (0x15 * 2) = 0x582a
=> (16 * 0x800) + (0x74 * 2) = 0x80e8
Domains
• Offset factor in Modbus index: 0x40 => Max. 64 bytes/circuit
• Index band: 0xa000..0xffff (24576 words)
Remarks:
• The Modbus protocol allows only 2 bytes words. So domains will be defined as n words (n = domain lenght/2).
• Only complete domains can be transferred. So by domains, the Modbus index must always be a factor of the domain length.
=> Modbus index calculation:
Name
Length [words]
• Time / date (domain 0xa)
4
164302/06.2013
Modbus index calculation
0xa000
6
• Holidays (domain 0x11..0x16)
3
• Switch points (domain 0x21..0x27) 3
• Reserve
0xb000 + (circuit * 0x40) + ((domain-0x11) * 3)
0xc000 + (circuit * 0x40) + ((domain-0x21) * 3)
0xd000..0xffff
Domains Examples
• Time / date, domain 0xa
=> 0xa000
• Holidays, heating circuit 1, domain 0x11
=> 0xb000 + (1 * 0x40) + ((0x11-0x11) * 3) = 0xb040
• Switch points, heating circuit 1, domain 0x21 => 0xc000 + (1 * 0x40) + ((0x21-0x21) * 3) =
0xc040
• Switch points, domestic water circuit 1, domain 0x22 => 0xc000 + (16 * 0x40) + ((0x22-0x21) * 3) = 0xc403
• Switch points, free circuit, domain 0x23
=> 0xc000 + (9 * 0x40) + ((0x23-0x21) * 3) =
0xc246
164302/06.2013
7
3. Table of MODBUS index
Menu “Time/date”
Time/date domain index
RDO
MODBUS Index
Description
Appl.
DP
Appl.
Circuit 0
Time domain
0
10
0
40960
Time/date domain structure
Name / Position
Reserved, undefined
Day of the week
Year
Month
Day of the month
Hours
Minutes
Seconds
Domain byte index
0
1
2
3
4
5
6
7
Circuit 1
Format / Unit
1=Monday .. 7=Sunday
95=1995 to 94=2094
1..12
1..31
0..23
0..59
0..59
Remark: The Time/date domain can only be be writen from Bus with par.133=2
164302/06.2013
Circuit 2
8
Circuit 3
Attribute
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Circuit 4
Circuit 5
Circuit 6
Circuit 7
Menu “Holidays”
Holidays domain index
RDO
Description
Holiday domain bloc 1
Holiday domain bloc 2
Holiday domain bloc 3
Holiday domain Bloc 4
Holiday domain Bloc 5
Holiday domain Bloc 6
MODBUS Index
Appl.
DP
Appl.
1
1
1
1
1
1
17
18
19
20
21
22
1
1
1
1
1
1
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
45120
45123
45126
45129
45132
45135
45184
45187
45190
45193
45196
45199
45248
45251
45254
45257
45260
45263
45312
45315
45318
45321
45324
45327
45376
45379
45382
45385
45388
45391
45440
45443
45446
45449
45452
45455
45504
45507
45510
45513
45516
45519
Remarks:
• Holiday data point reset state is 0xff
• The holidays have to be programmed like on the controller MMI:
• “bloc n+1” can only be filled if “bloc n” is filled
• In a bloc the end date must be higher as the begin date
• Begin date “bloc n+1” must be higher as the end date “bloc n”
• By deleting a bloc, all following blocs will be shifted
• Etc.
Holidays domain structure
Name / Position
Year, begin
Month, begin
Day of the month, begin
Year, end
Month, end
Day of the month, end
164302/06.2013
Domain byte index
0
1
2
3
4
5
Format / Unit
95=1995 to 94=2094
1..12
1..31
95=1995 to 94=2094
1..12
1..31
9
Attribute
R/W
R/W
R/W
R/W
R/W
R/W
Menu “Clocks”
Switch points domain
RDO
Description
Heating circuit
Switch point domain Mo.
Switch point domain Tu.
Switch point domain We.
Switch point domain Th.
Switch point domain Fr.
Switch point domain Sa.
Switch point domain Su.
Domestic water circuit
Switch point domain Mo.
Switch point domain Tu.
Switch point domain We.
Switch point domain Th.
Switch point domain Fr.
Switch point domain Sa.
Switch point domain Su.
Free circuit
Switch point domain Mo.
Switch point domain Tu.
Switch point domain We.
Switch point domain Th.
Switch point domain Fr.
Switch point domain Sa.
Switch point domain Su.
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
1
1
1
1
1
1
1
33
34
35
36
37
38
39
21
21
21
21
21
21
21
91
91
91
91
91
91
91
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
1
1
1
1
1
1
49216
49219
49222
49225
49228
49231
49234
49280
49283
49286
49289
49292
49295
49298
49344
49347
49350
49353
49356
49359
49362
49408
49411
49414
49417
49420
49423
49426
49472
49475
49478
49481
49484
49487
49490
49536
49539
49542
49545
49548
49551
49554
49600
49603
49606
49609
49612
49615
49618
33
34
35
36
37
38
39
16
16
16
16
16
16
16
50176
50179
50182
50185
50188
50191
50194
50240
50243
50246
50249
50252
50255
50258
50304
50307
50310
50313
50316
50319
50322
50368
50371
50374
50377
50380
50383
50386
33
34
35
36
37
38
39
9
9
9
9
9
9
9
49728
49731
49734
49737
49740
49743
49746
10
Switch points structure
Name / Position
Switch point 1. on
Switch point 1. off
Switch point 2. on
Switch point 2. off
Switch point 3. on
Switch point 3. off
Domain byte index
0
1
2
3
4
5
Signification of the on switch points values:
• 0:
00:00
• 1:
00:15
• 2:
00:30
• .
• 94:
23:30
• 95:
23:45
• 96:
24:00
• 0xff:
undefined
164302/06.2013
Format / Unit
on switch point
off switch point
on switch point
off switch point
on switch point
off switch point
Attribute
R/W
R/W
R/W
R/W
R/W
R/W
Signification of the off switch points values:
0x80 + 0:
00:00
0x80 + 1:
00:15
0x80 + 2:
00:30
0x80 + 94:
0x80 + 95:
0x80 + 96:
23:30
23:45
24:00
11
Menu “Set values”
Set values
Remarks:
• All set values are R/W
RDO
Description
Heating circuit
Set value heating, 1
Set value heating, 2
Set value heating, 3
Domestic water circuit
Set value domestic water, 1
Set value domestic water, 2
Set value domestic water, 3
Set value domestic water, 4
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
1
1
60
61
62
1
1
1
120
122
124
2168
2170
2172
4216
4218
4220
6264
6266
6268
8312
8314
8316
10360
10362
10364
12408
12410
12412
14456
14458
14460
21
21
21
21
70
71
72
73
16
16
16
16
140
142
144
146
32908
32910
32912
32914
34956
34958
34960
34962
37004
37006
37008
37010
39052
39054
39056
39058
12
Service, user level II
Remarks:
• Temperature sensor status:
• 0:
OK
• 1:
open
• 2:
short circuit
• All Parameters are here read only, except Parameters: 30, 31, 34, 36, 40, 41, 81, 82
RDO
Description
Parameter 1, actual value
Parameter 1, sensor status
Parameter 1, set value
Parameter 2, actual value
Parameter 2, sensor status
Parameter 2, set value
Parameter 3, actual value
Parameter 3, sensor status
Parameter 3, set value
Parameter 4, actual value
Parameter 4, sensor status
Parameter 4, set value
Parameter 10, actual value
Parameter 10, sensor status
Parameter 10, set value
Parameter 11, actual value
Parameter 11, sensor status
Parameter 12, actual value
Parameter 12, sensor status
Parameter 12, set value
Parameter 14, actual value
Parameter 14, sensor status
Parameter 14, set value
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
21
21
21
21
21
21
21
21
21
21
21
21
1
1
1
0
0
1
1
1
1
1
1
3
95
207
4
97
207
364
366
391
365
367
392
10
91
205
11
313
12
90
208
14
93
209
16
16
16
16
16
16
16
16
16
16
16
16
1
1
1
0
0
1
1
1
1
1
1
6
190
414
8
194
414
728
732
782
730
734
784
20
182
410
22
626
24
180
416
28
186
418
32774
32958
33182
32776
32962
33182
33496
33500
33550
33498
33502
33552
2068
2230
2458
34822
35006
35230
34824
35010
35230
35544
35548
35598
35546
35550
35600
4116
4278
4506
36870
37054
37278
36872
37058
37278
37592
37596
37646
37594
37598
37648
6164
6326
6554
38918
39102
39326
38920
39106
39326
39640
39644
39694
39642
39646
39696
8212
8374
8602
10260
10422
10650
12308
12470
12698
14356
14518
14746
2072
2228
2464
2076
2234
2466
4120
4276
4512
4124
4282
4514
6168
6324
6560
6172
6330
6562
8216
8372
8608
8220
8378
8610
10264
10420
10656
10268
10426
10658
12312
12468
12704
12316
12474
12706
14360
14516
14752
14364
14522
14754
13
RDO
Description
Parameter 20, actual value
Parameter 20, sensor status
Parameter 20, set value
Parameter 21, actual value
Parameter 21, sensor status
Parameter 21, set value
Parameter 23, actual value
Parameter 23, sensor status
Parameter 23, alternate value
Parameter 24, actual value
Parameter 24, sensor status
Parameter 24, set value
Parameter 25, actual value
Parameter 25, sensor status
Parameter 25, set value
Parameter 27, actual value
Parameter 27, sensor status
Parameter 27, set value
Parameter 28, actual value
Parameter 28, sensor status
Parameter 28, alternate value
Parameter 29, actual value
Parameter 29, sensor status
Parameter 29, alternate value
Parameter 2A, actual value
Parameter 2A, sensor status
Parameter 2A, alternate value
Parameter 2b, actual value
Parameter 2b, sensor status
Parameter 2c, actual value
Parameter 2c, sensor status
Parameter 2d, actual value
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
11
11
11
11
11
11
11
11
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
20
94
237
21
92
331
23
96
156
24
98
281
25
99
281
27
78
263
28
79
264
600
648
601
649
602
660
644
11
11
11
11
11
11
11
11
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
40
188
474
42
184
662
46
192
312
48
196
562
50
198
562
54
156
526
56
158
528
1200
1296
1202
1298
1204
1320
1288
22568
22716
23002
22570
22712
23190
22574
22720
22840
24616
24764
25050
24618
24760
25238
24622
24768
24888
26664
26812
27098
26666
26808
27286
26670
26816
26936
28712
28860
29146
28714
28856
29334
28718
28864
28984
14
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Parameter 2d, sensor status
Parameter 2d, alternate value
Parameter 2E, actual value
Parameter 2E, sensor status
Parameter 2F, actual value
Parameter 2F, sensor status
Parameter 2F, alternate value
Parameter 2J, actual value
Parameter 2J, sensor status
Parameter 2L, actual value
Parameter 2L, sensor status
Parameter 30
Parameter 31
Parameter 34
Parameter 35
Parameter 36
Parameter 37
Parameter 40
Parameter 41
Parameter 45, actual value
Parameter 45, set value
Parameter 46, actual value
Parameter 46, set value
Parameter 47
Parameter 81
Parameter 82
Parameter 83, status 1
Parameter 83, status 2
Parameter 85
Parameter 86
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
11
11
0
0
0
0
11
11
11
11
0
0
0
0
0
0
0
0
0
643
646
641
645
664
666
667
30
31
34
35
36
37
40
41
45
258
46
347
47
362
363
662
663
88
89
0
0
0
0
0
0
0
0
0
0
0
11
11
0
0
0
0
11
11
11
11
0
0
0
0
0
0
0
0
0
1286
1292
1282
1290
1328
1332
1334
60
62
68
70
72
74
80
82
90
516
92
694
94
724
726
1324
1326
176
178
Circuit 1
Circuit 2
Circuit 3
Circuit 4
22588
22590
24636
24638
26684
26686
28732
28734
22608
22610
22618
23044
24656
24658
24666
25092
26704
26706
26714
27140
28752
28754
28762
29188
15
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Parameter 90
Parameter 91
Parameter 92
Parameter 93
Parameter 94
Parameter 95
Parameter 96
Parameter 97
Parameter 98
Parameter 99
Parameter A0
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
240
241
242
243
244
245
246
247
248
249
219
0
0
0
0
0
0
0
0
0
0
0
480
482
484
486
488
490
492
494
496
498
438
Circuit 1
16
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
Service, specialist level I
Remarks:
• Parameter 164 to 166 are read only
RDO
Description
Parameter 100
Parameter 101
Parameter 102
Parameter 103
Parameter 104
Parameter 105
Parameter 106
Parameter 107
Parameter 108
Parameter 109
Parameter 10A
Parameter 10b
Parameter 10c
Parameter 10d
Parameter 10E
Parameter 10F
Parameter 10h
Parameter 10J
Parameter 10L
Parameter 10n
Parameter 10P
Parameter 10r
Parameter 10t
Parameter 10U
Parameter 10y
Parameter 110
Parameter 111
Parameter 112
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
11
11
0
11
0
0
0
11
11
11
11
0
0
0
11
0
0
0
0
0
0
0
0
0
0
1
100
101
102
103
104
105
106
107
108
109
800
801
802
803
804
805
806
807
808
809
900
901
902
903
904
110
111
112
0
0
11
11
0
11
0
0
0
11
11
11
11
0
0
0
11
0
0
0
0
0
0
0
0
0
0
1
200
202
204
206
208
210
212
214
216
218
1600
1602
1604
1606
1608
1610
1612
1614
1616
1618
1800
1802
1804
1806
1808
220
222
224
Circuit 1
Circuit 2
Circuit 3
Circuit 4
22732
22734
24780
24782
26828
26830
28876
28878
22738
24786
26834
28882
22746
24128
24130
24132
24794
26176
26178
26180
26842
28224
28226
28228
28890
30272
30274
30276
24140
26188
28236
30284
2272
4320
6368
8416
17
Circuit 5
Circuit 6
Circuit 7
10464
12512
14560
RDO
Description
Parameter 113
Parameter 114
Parameter 115
Parameter 116
Parameter 117
Parameter 118
Parameter 119
Parameter 11A
Parameter 11b
Parameter 11c
Parameter 11d
Parameter 11E
Parameter 11F
Parameter 11J
Parameter 11L
Parameter 11n
Parameter 11P
Parameter 11r
Parameter 11t
Parameter 11U
Parameter 11y
Parameter 120
Parameter 121
Parameter 122
Parameter 123
Parameter 124
Parameter 125
Parameter 126
Parameter 127
Parameter 128
Parameter 129
Parameter 12A
Parameter 12b
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
0
0
21
21
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
0
0
0
0
0
113
114
115
116
117
118
119
810
811
812
813
814
815
817
818
819
905
906
907
908
909
120
121
122
123
124
125
126
127
128
129
820
821
1
0
0
16
16
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
0
0
0
0
0
226
228
230
232
234
236
238
1620
1622
1624
1626
1628
1630
1634
1636
1638
1810
1812
1814
1816
1818
240
242
244
246
248
250
252
254
256
258
1640
1642
2274
4322
6370
8418
10466
12514
14562
33000
33002
35048
35050
37096
37098
39144
39146
22780
24828
26876
28924
18
RDO
Description
Parameter 12c
Parameter 12d
Parameter 12E
Parameter 12F
Parameter 12h
Parameter 12J
Parameter 12L
Parameter 12n
Parameter 12P
Parameter 12r
Parameter 12t
Parameter 12U
Parameter 12y
Parameter 130
Parameter 131
Parameter 132
Parameter 133
Parameter 135
Parameter 136
Parameter 137
Parameter 138
Parameter 139
Parameter 13A
Parameter 13b
Parameter 13c
Parameter 13d
Parameter 13E
Parameter 13F
Parameter 13h
Parameter 13J
Parameter 13L
Parameter 13n
Parameter 13P
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
11
11
0
0
0
0
0
0
0
0
822
823
824
825
826
827
828
829
910
911
912
913
914
130
131
132
133
135
136
137
138
139
830
831
832
833
834
835
836
837
838
839
915
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
11
11
0
0
0
0
0
0
0
0
1644
1646
1648
1650
1652
1654
1656
1658
1820
1822
1824
1826
1828
260
262
264
266
270
272
274
276
278
1660
1662
1664
1666
1668
1670
1672
1674
1676
1678
1830
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
3708
24190
24192
5756
26238
26240
7804
28286
28288
9852
30334
30336
11900
13948
15996
19
RDO
Description
Parameter 13r
Parameter 13t
Parameter 13U
Parameter 13y
Parameter 140
Parameter 141
Parameter 142
Parameter 143
Parameter 144
Parameter 145
Parameter 146
Parameter 147
Parameter 148
Parameter 149
Parameter 14A
Parameter 14b
Parameter 14c
Parameter 14d
Parameter 14E
Parameter 14F
Parameter 14h
Parameter 14J
Parameter 14L
Parameter 14n
Parameter 14P
Parameter 14r
Parameter 14t
Parameter 14U
Parameter 14y
Parameter 150
Parameter 151
Parameter 152
Parameter 153
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
11
11
11
11
11
11
11
11
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
0
0
1
916
917
918
919
140
141
142
143
144
145
146
147
148
149
840
841
842
843
844
845
846
847
848
849
920
921
922
923
924
150
151
152
153
0
0
0
0
11
11
11
11
11
11
11
11
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
0
0
1
1832
1834
1836
1838
280
282
284
286
288
290
292
294
296
298
1680
1682
1684
1686
1688
1690
1692
1694
1696
1698
1840
1842
1844
1846
1848
300
302
304
306
Circuit 1
Circuit 2
Circuit 3
Circuit 4
22808
22810
22812
22814
22816
22818
22820
22822
22824
24856
24858
24860
24862
24864
24866
24868
24870
24872
26904
26906
26908
26910
26912
26914
26916
26918
26920
28952
28954
28956
28958
28960
28962
28964
28966
28968
22828
24876
26924
28972
2354
4402
6450
8498
20
Circuit 5
Circuit 6
Circuit 7
10546
12594
14642
RDO
Description
Parameter 154
Parameter 155
Parameter 156
Parameter 157
Parameter 158
Parameter 159
Parameter 15A
Parameter 15b
Parameter 15c
Parameter 15d
Parameter 15E
Parameter 15F
Parameter 15h
Parameter 15J
Parameter 15L
Parameter 15n
Parameter 15P
Parameter 15r
Parameter 15t
Parameter 15U
Parameter 15y
Parameter 160
Parameter 161
Parameter 162
Parameter 163
Parameter 164
Parameter 165
Parameter 166
Parameter 167
Parameter 168
Parameter 169
Parameter 16A
Parameter 16b
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
11
11
11
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
1
1
0
1
1
1
0
0
154
155
156
157
158
159
850
851
852
853
854
855
856
857
858
859
925
926
927
928
929
160
161
162
163
164
165
166
167
168
169
860
861
1
11
11
11
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
1
1
0
1
1
1
0
0
308
310
312
314
316
318
1700
1702
1704
1706
1708
1710
1712
1714
1716
1718
1850
1852
1854
1856
1858
320
322
324
326
328
330
332
334
336
338
1720
1722
2356
22838
22840
22842
4404
24886
24888
24890
6452
26934
26936
26938
8500
28982
28984
28986
10548
12596
14644
2366
4414
6462
8510
10558
12606
14654
2368
2370
2372
4416
4418
4420
6464
6466
6468
8512
8514
8516
10560
10562
10564
12608
12610
12612
14656
14658
14660
2376
2378
4424
4426
6472
6474
8520
8522
10568
10570
12616
12618
14664
14666
2382
2384
2386
4430
4432
4434
6478
6480
6482
8526
8528
8530
10574
10576
10578
12622
12624
12626
14670
14672
14674
21
RDO
Description
Parameter 16c
Parameter 16d
Parameter 16E
Parameter 16F
Parameter 16h
Parameter 16J
Parameter 16L
Parameter 16n
Parameter 16P
Parameter 16r
Parameter 16t
Parameter 16U
Parameter 16y
Parameter 170
Parameter 171
Parameter 172
Parameter 173
Parameter 174
Parameter 175
Parameter 176
Parameter 177
Parameter 178
Parameter 179
Parameter 17A
Parameter 17b
Parameter 17c
Parameter 17d
Parameter 17E
Parameter 17F
Parameter 17h
Parameter 17J
Parameter 17L
Parameter 17n
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
862
863
864
865
866
867
868
869
930
931
932
933
934
170
171
172
173
174
175
176
177
178
179
870
871
872
873
874
875
876
877
878
879
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1724
1726
1728
1730
1732
1734
1736
1738
1860
1862
1864
1866
1868
340
342
344
346
348
350
352
354
356
358
1940
1942
1944
1946
1948
1950
1952
1954
1956
1958
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
2388
2390
2392
2394
2396
4436
4438
4440
4442
4444
6484
6486
6488
6490
6492
8532
8534
8536
8538
8540
10580
10582
10584
10586
10588
12628
12630
12632
12634
12636
14676
14678
14680
14682
14684
22
RDO
Description
Parameter 17P
Parameter 17r
Parameter 17t
Parameter 17U
Parameter 17y
Parameter 180
Parameter 181
Parameter 182
Parameter 183
Parameter 185
Parameter 186
Parameter 187
Parameter 188
Parameter 18A
Parameter 18b
Parameter 18c
Parameter 18d
Parameter 18E
Parameter 18F
Parameter 18h
Parameter 18J
Parameter 18L
Parameter 18n
Parameter 18P
Parameter 18r
Parameter 18t
Parameter 18U
Parameter 18y
Parameter 190
Parameter 191
Parameter 192
Parameter 193
Parameter 194
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
1
1
1
1
0
1
0
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
21
21
21
21
21
935
936
937
938
939
180
181
182
183
185
186
187
188
880
881
882
883
884
885
886
887
888
889
940
941
942
943
944
190
191
192
193
194
0
0
0
0
0
1
1
1
1
0
1
0
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
16
16
16
16
16
1870
1872
1874
1876
1878
360
362
364
366
370
372
374
376
1760
1762
1764
1766
1768
1770
1772
1774
1776
1778
1880
1881
1882
1883
1884
380
382
384
386
388
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
2408
2410
2412
2414
4456
4458
4460
4462
6504
6506
6508
6510
8552
8554
8556
8558
10600
10602
10604
10606
12648
12650
12652
12654
14696
14698
14700
14702
2420
4468
6516
8564
10612
12660
14708
22904
24952
27000
29048
33148
33150
33152
33154
33156
35196
35198
35200
35202
35204
37244
37246
37248
37250
37252
39292
39294
39296
39298
39300
23
RDO
Description
Parameter 195
Parameter 196
Parameter 197
Parameter 198
Parameter 199
Parameter 19A
Parameter 19b
Parameter 19c
Parameter 19d
Parameter 19E
Parameter 19F
Parameter 19h
Parameter 19J
Parameter 19L
Parameter 19n
Parameter 19P
Parameter 19r
Parameter 19t
Parameter 19U
Parameter 19y
Parameter 1A0
Parameter 1A1
Parameter 1A2
Parameter 1A3
Parameter 1A4
Parameter 1A5
Parameter 1A6
Parameter 1A7
Parameter 1A8
Parameter 1A9
Parameter 1AA
Parameter 1Ab
Parameter 1Ac
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
21
21
21
0
21
21
21
21
21
21
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
195
196
197
198
199
890
891
892
893
894
895
896
897
898
899
945
946
947
948
949
400
401
402
403
404
405
406
407
408
409
500
501
502
0
0
16
16
16
0
16
16
16
16
16
16
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
390
392
394
396
398
1780
1782
1784
1786
1788
1790
1792
1794
1796
1798
1890
1892
1894
1896
1898
800
802
804
806
808
810
812
814
816
818
1000
1002
1004
Circuit 1
Circuit 2
Circuit 3
Circuit 4
33162
33164
33166
35210
35212
35214
37258
37260
37262
39306
39308
39310
34550
34552
34554
34556
34558
34560
36598
36600
36602
36604
36606
36608
38646
38648
38650
38652
38654
38656
40694
40696
40698
40700
40702
40704
24
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Parameter 1Ad
Parameter 1AE
Parameter 1AF
Parameter 1Ah
Parameter 1AJ
Parameter 1AL
Parameter 1An
Parameter 1AP
Parameter 1Ar
Parameter 1At
Parameter 1AU
Parameter 1Ay
Parameter 1b0
Parameter 1b1
Parameter 1b2
Parameter 1b3
Parameter 1b4
Parameter 1b5
Parameter 1b6
Parameter 1b7
Parameter 1bA
Parameter 1bb
Parameter 1bc
Parameter 1bd
Parameter 1bE
Parameter 1bF
Parameter 1bh
Parameter 1bJ
Parameter 1bL
Parameter 1bn
Parameter 1bP
Parameter 1br
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
503
504
505
506
507
508
509
950
951
952
953
954
410
411
412
413
414
415
416
417
510
511
512
513
514
515
516
517
518
519
955
956
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1006
1008
1010
1012
1014
1016
1018
1900
1902
1904
1906
1908
820
822
824
826
828
830
832
834
1020
1022
1024
1026
1028
1030
1032
1034
1036
1038
1910
1912
Circuit 1
25
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Parameter 1bt
Parameter 1bU
Parameter 1by
Parameter 1c0
Parameter 1c1
Parameter 1c2
Parameter 1c3
Parameter 1c4
Parameter 1c5
Parameter 1c6
Parameter 1c7
Parameter 1c8
Parameter 1c9
Parameter 1cA
Parameter 1dA
Parameter 1db
Parameter 1dc
Parameter 1dd
Parameter 1dE
Parameter 1E0
Parameter 1E1
Parameter 1E2
Parameter 1E3
Parameter 1E4
Parameter 1E5
Parameter 1E6
Parameter 1E7
Parameter 1E8
Parameter 1E9
Parameter 1EA
Parameter 1Eb
Parameter 1Ec
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
957
958
959
420
421
422
423
424
425
426
427
428
429
520
530
531
532
533
534
440
441
442
443
444
445
446
447
448
449
540
541
542
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1914
1916
1918
840
842
844
846
848
850
852
854
856
858
1040
1060
1062
1064
1066
1068
880
882
884
886
888
890
892
894
896
898
900
902
904
Circuit 1
26
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Parameter 1Ed
Parameter 1EE
Parameter 1EF
Parameter 1Eh
Parameter 1EJ
Parameter 1EL
Parameter 1En
Parameter 1EP
Parameter 1Er
Parameter 1Et
Parameter 1EU
Parameter 1Ey
Parameter 1F0
Parameter 1F1
Parameter 1F2
Parameter 1F3
Parameter 1F4
Parameter 1F5
Parameter 1F6
Parameter 1F7
Parameter 1F8
Parameter 1h0
Parameter 1h1
Parameter 1h2
Parameter 1h6
Parameter 1J0
Parameter 1J1
Parameter 1J2
Parameter 1J3
Parameter 1J4
Parameter 1J5
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
543
544
545
546
547
548
549
970
971
972
973
974
450
451
452
453
454
455
456
457
458
460
461
462
466
470
471
472
473
474
475
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
906
908
910
912
914
916
918
1940
1942
1944
1946
1948
900
902
904
906
908
910
912
914
916
920
922
924
932
940
942
944
946
948
950
2994
2996
2998
5042
5044
5046
7090
7092
7094
9138
9140
9142
11186
11188
11190
13234
13236
13238
15282
15284
15286
27
RDO
Description
Parameter 1J6
Parameter 1J7
Parameter 1J8
Parameter 1J9
Parameter 1JA
Parameter 1Jb
Parameter 1Jc
Parameter 1Jd
Parameter 1JE
Parameter 1JF
Parameter 1Jh
Parameter 1JJ
Parameter 1JL
Parameter 1L0
Parameter 1L1
Parameter 1L2
Parameter 1L4
Parameter 1L7
Parameter 1L8
Parameter 1L9
Parameter 1LA
Parameter 1Lb
Parameter 1n0
Parameter 1n1
Parameter 1n2
Parameter 1n3
Parameter 1n4
Parameter 1n5
Parameter 1n6
Parameter 1n7
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
1
1
1
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
476
477
478
479
570
571
572
573
574
575
576
577
578
480
481
482
484
487
488
489
580
581
490
491
492
493
494
495
496
497
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
952
954
956
958
1140
1142
1144
1146
1148
1150
1152
1154
1156
960
962
964
968
974
976
978
1160
1162
980
982
984
986
988
990
992
994
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
3002
3004
3006
5050
5052
5054
7098
7100
7102
9146
9148
9150
11194
11196
11198
13242
13244
13246
15290
15292
15294
3192
5240
7288
9336
11384
13432
15480
3206
5254
7302
9350
11398
13446
15494
28
RDO
Description
Parameter 1n8
Parameter 1n9
Parameter 1nA
Parameter 1nb
Parameter 1nc
Parameter 1nd
Parameter 1nE
Parameter 1nF
Parameter 1nh
Parameter 1nJ
Parameter 1nL
Parameter 1nn
Parameter 1P0
Parameter 1P1
Parameter 1P2
Parameter 1P3
Parameter 1P4
Parameter 1P5
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
498
499
590
591
592
593
594
595
596
597
598
599
760
761
762
763
764
765
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
996
998
1180
1182
1184
1186
1188
1190
1192
1194
1196
1198
1520
1522
1524
1526
1528
1530
Circuit 1
29
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
Service, specialist level II
Remarks:
• Appl. ID 0 affects the relays on RDO3xx, if the relays is neither heating circuit nor boiler circuit nor domestic water circuit
• The parameters are here read only
RDO
Description
RDO counters
Parameter +30
Parameter +31
Parameter +34
Parameter +36
Parameter +37
Parameter +40
Parameter +41
Parameter +47
Parameter +48 (81)
Parameter +49 (82)
RDO relays
Parameter +50
Parameter +51
Parameter +52
Parameter +53
Parameter +54
Parameter +55
Parameter +56
Parameter +57
Parameter +58
Parameter +59
Parameter +5A
Parameter +5b
Parameter +5c
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
30
31
34
36
37
40
41
47
362
363
0
0
0
0
0
0
0
0
0
0
60
62
68
72
74
80
82
94
724
726
0
0
0
0
0
0
0
0
0
0
0
0
0
80
81
82
83
84
85
86
87
88
89
700
701
702
0
0
0
0
0
0
0
0
0
0
0
0
0
160
162
164
166
168
170
172
174
176
178
1400
1402
1404
Circuit 1
30
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Heating circuit relays
Parameter +65
Parameter +66
Parameter +67
Boiler circuit relays
Parameter +70
Parameter +71
Parameter +72
Parameter +73
Parameter +75
Parameter +76
Parameter +77
Parameter +78
Domestic water circuit relays
Parameter +80
Parameter +81
Parameter +82
Parameter +83
Parameter +84
Parameter +85
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
1
1
344
345
346
1
1
1
688
690
692
2736
2738
2740
4784
4786
4788
6832
6834
6836
8880
8882
8884
10928
10930
10932
12976
12978
12980
15024
15026
15028
11
11
11
11
11
11
11
11
338
339
340
341
354
342
343
88
11
11
11
11
11
11
11
11
676
678
680
682
708
684
686
23204
23206
23208
23210
23236
23212
23214
25252
25254
25256
25258
25284
25260
25262
27300
27302
27304
27306
27332
27308
27310
29348
29350
29352
29354
29380
29356
29358
176
22704
24752
26800
28848
21
21
21
21
21
21
372
373
374
375
376
377
16
16
16
16
16
16
744
746
748
750
752
754
33512
33514
33516
33518
33520
33522
35560
35562
35564
35566
35568
35570
37608
37610
37612
37614
37616
37618
39656
39658
39660
39662
39664
39666
31
RDO
Description
RDO inputs
RDO all inputs
RDO input 1 (te. 35)
RDO input 2 (te. 34)
RDO input 3 (te. 33)
RDO input 4 (te. 32)
RDO input 5 (te. 31)
RDO operation counter 1 (te.3)
RDO operation counter 2 (te.4)
RDO input 2.1 (te. 34)
RDO input 2.2 (te. 34)
RDO input 2.3 (te. 34)
RDO input 2.4 (te. 34)
RDO input 8.1 (te. 28)
RDO input 8.2 (te. 28)
RDO input 8.3 (te. 28)
RDO input 8.4 (te. 28)
RDO input 9.1 (te. 27)
RDO input 9.2 (te. 27)
RDO input 9.3 (te. 27)
RDO input 9.4 (te. 27)
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
215
282
283
284
285
286
287
288
613
614
615
616
607
608
609
610
252
253
255
256
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
430
564
566
568
570
572
574
576
1226
1228
1230
1232
1214
1216
1218
1220
504
506
510
512
Circuit 1
32
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
RDO
Description
Heating circuit inputs
Heating circuit inputs
Heating circuit input 1
Heating circuit input 2
Boiler circuit inputs
Boiler circuit inputs
Boiler circuit input 1
Boiler circuit input 2
Boiler circuit op.counter 1
Boiler circuit op.counter 2
Domestic water circuit input
Domestic water circuit inputs
Domestic water circuit input 1
Domestic water circuit input 2
Dom.water DW-Thermostat
Dom.water DW-Electrical
164302/06.2013
MODBUS Index
Appl.
DP
Appl.
Circuit 0
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
1
1
1
316
312
311
1
1
1
632
624
622
2680
2672
2670
4728
4720
4718
6776
6768
6766
8824
8816
8814
10872
10864
10862
12920
12912
12910
14968
14960
14958
11
11
11
11
11
317
314
318
321
322
11
11
11
11
11
634
628
636
642
644
23162
23156
23164
23170
23172
25210
25204
25212
25218
25220
27258
27252
27260
27266
27268
29306
29300
29308
29314
29316
21
21
21
21
21
378
379
380
381
382
16
16
16
16
16
756
758
760
762
764
33524
33526
33528
33530
33532
35572
35574
35576
35578
35580
37620
37622
37624
37626
37628
39668
39670
39672
39674
39676
33
Common data points (not available in RDO-MMI)
RDO
Description
MODBUS Index
Appl.
DP
Attr.
Appl.
Circuit 0
Controller type
Software version
Software article number
Test a)
Room sensor calibration
Cascade boiler set value
Heating circuit mode
Boiler circuit mode
Domestic water circuit mode
Number of heating circuits
Number of boiler circuits
Number of dom.water circuits
Bus boiler set value
Bus storage set value
Bus cool attribut (Bitmap 0x1)
Bus boiler actual value
Bus return actual value
Bus outside actual value
Bus outside actual value b)
Bus flag 'standby'
Bus flag 'summer'
Bus flag 'normal'
Bus flag 'reduced'
0
0
0
0
1
0
1
11
21
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1
2
204
239
75
210
213
277
278
350
351
389
368
751
756
369
370
371
371
393
394
395
396
R
R
R
W
R/W
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0
0
0
0
1
0
1
11
16
0
0
0
0
0
0
0
0
1
0
1
1
1
1
2
4
408
478
150
420
426
554
556
700
702
778
736
1502
1512
738
740
Busflag 'Force loading DHW'
Busflag ‘Block energy gen’
21
0
670
301
R/W
R/W
16
0
1340
602
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Circuit 5
Circuit 6
Circuit 7
2198
4246
6294
8342
10390
12438
14486
2474
23082
33324
4522
25130
35372
6570
27178
37420
8618
29226
39468
10666
12714
14762
2790
4838
6886
8934
10982
13030
15078
2834
2836
2838
2840
4882
4884
4886
4888
6930
6932
6934
6936
8978
8980
8982
8984
11026
11028
11030
11032
13074
13076
13078
13080
15122
15124
15126
15128
34108
36156
38204
742
786
788
790
792
a) Write Test:
• 0: Reset test state
• 1: Set test state (timeout 5 min.): LCD clear, inhibit keyboard, reset outputs
• 7: Set EEPROM default values
• 8: Reset history error memory
164302/06.2013
b) Broadcast for all heating circuits
34
Version history
Version
Change ( description)
1.11
1.20
First edition
Undefined domain answer = NaN
RDO3x4 specific data points
Translation in french and german
Add remarks to the holidays
Add datapoints (RDO3x3 V4.xx, RDO3x4 V5.xx)
Add datapoints (RDO3x4 V6.xx), error corrections
Add datapoints (RDO input 2.x, 8.x, 9.x, DP301, 751,
756)
Add hex datapoints (1j3..1Jl, etc.)
1.21
1.22
1.23
1.24
1.25
1.26
164302/06.2013
changed
Date
21.04.1999
05.03.2004
Visa
Smn
Pa
27.04.2005
22.06.2005
18.12.2006
22.10.2007
22.03.2010
Pa
Pa
Pa
Pa
Pa
18.07.2013
Pa
35