ELESTA energy control AG
Transcription
ELESTA energy control AG
Specification: communication protocol Modbus <--> RDO3xx, datapoints and domains tables S.Stäger, A.Pichonnat 18.06.2013 ELESTA energy control Version: 1.26 Pages: 1 - 35 1. Introduction (English) An other document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) describes the Modbus communication protocole and the calcul of the Modbus datapoint index. Abbreviations: • RDO3xx RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc. • DHW Domestic hot water • DH District heating • R Read only • R/W Read/Write • DP Data point • Appl.ID Application Identification • NaN Not An Number Common definitions: • In this document, hex values will be defined with 0x. For example 0xa (hex) means 10 (dez) Appl.ID: • Main controller (all DP’s which are not indexed): 0 • Heating circuit parameter: 0, 1..7 (appl. ID=0 will be interpreted as 1, 1 = heating circuit 1, 7 = heating circuit 7) • Boiler circuit (cascade) parameter: 0, 11..14 (appl. ID=0 will be interpreted as 11, 11 = boiler circuit 1, 14 = boiler circuit 4) • DHW circuit parameter: 0, 21..24 (appl. ID=0 will be interpreted as 21, 21 = DHW circuit 1, 24 = DHW circuit 4) Remark: RDO3x4 supports only 1 boiler circuit (no cascade) and 1 DHW circuit Data points: • The data points values (always 4 bytes long) is defined by RDO300 as float • A data point means one value. For example: parameter 101 • A list of contiguous data points can be queried. Undefined data points will be returned as NaN (0xffc00000) on RDO383 since V4.00ßA and on RDO374 since V4.10 • By writing data points, it is only possible to query max. 1 data point per message (1 data point: 4 bytes, 2 words) Domains: • The domain values (various length) is defined separately (normally not float) • A domain means a list of values. For example: time/date with hour, min, s, etc. 164302/06.2013 1 • A list of contiguous domains can be queried • By writing domains, it is only possible to query max. 1 domain per message (1 domain: n bytes, n/2 words, domain dependency) Message definitions: • It is possible to query max. 32 words (64 bytes) per message • Always whole datapoints resp. Domain must be treated • Only RTU mode is supported Document overview: • Chapter 2 gives the rules of calculation of the modbus index of data points ans domains starting from the RDO-COM numbers of data points and domains. The reading of this chapter is normally not necessary, go directly to chapter 3 (Table of modbus index) • Chapter 3: listing of the data like the RDO300-MMI. Look at the corresponding RDO3xx User manual for the signification, the format and the layout of the parameter 1. Einleitung (Deutsch) Ein anderes Document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) beschreibt das Modbus Kommunikationsprotokoll und die Berechnung der Modbus-Datenpunkte-Index. Abkürzungen: • RDO3xx RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc. • DHW Warmwasser (WW) • DH Fernwärme • R Nur lesen • R/W Lesen/schreiben • DP Datenpunkt • Appl.ID Applikationsidentifikation • NaN Undefinierter Wert Übersetzungen: • Data point Datenpunkt • Domain Domain • Time/date Zeit/Datum • Holidays Ferien • Clocks Schaltuhr • Heating circuit Heizkreis • Domestic water circuit Warmwasserkreis • Boiler circuit Kesselkreis • Free circuit Freier Uhrenkanal • Swich point Schalpunkt • Set value Sollwert • Actual value Istwert • Sensor Fühler 164302/06.2013 2 • User level Benutzerebene • Specialist level Fachmannebene • Parameter Parameter • Counters Zähler • Relays Relais Allgemeine Definitionen: • In diesem Dokument, sind die Hex-Werte mit 0x definiert. Beispiel 0xa (hex) steht für 10 (dez) Appl.ID: • Hauptregler (alle DP, welche nicht indexiert sind): 0 • Heizkreisparameter: 0, 1..7 (appl.ID=0 ist interpretiert wie 1, 1 = Heizkreis1, 7 = Heizkreis7) • Kesselkreisparameter (Kaskade): 0, 11..14 (appl.ID=0 ist interpretiert wie 11, 11 = Kesselkreis1, 14 = Kesselkreis4) • Warmwasserkreisparameter: 0, 21..24 (appl.ID=0 ist interpretiert wie 21, 21 = Warmwasserkreis1, 24 = Warmwasserkreis4) Bemerkung: RDO3x4 besitzt nur 1 Kesselkreis (keine Kaskade) et 1 Warmwasserkreis Datenpunkte: • Die Datenpunktwerte (immer 4 Bytes lang) sind in den RDO300-Reglern als „float“-Werte definiert • Ein Datenpunkt entspricht ein Wert. Beispiel: Parameter 101 • Die Abfrage einer Liste von benachbarten Datenpunkten ist möglich. Die undefinierte Datenpunkte werden als NaN (0xffc00000) zurückgegeben. Bei RDO383 ab V4.00ßA und bei RDO374 ab V4.10 • Beim schreiben, kann nur ein Datenpunkt per Meldung verarbeitet werden (1 Datenpunkt: 4 Bytes, 2 Words) Domains: • Die Domain-Werte (variable Länge) sind separat definiert (normalerweise nicht „float“) • Ein Domain entspricht eine Wertliste. Beispiel: Zeit/Datum mit Stunden, Minuten, etc. • Die Abfrage einer Liste von benachbarten Domains ist möglich • Beim schreiben, kann nur ein Domain per Meldung verarbeitet werden (1 Domain: n Bytes, n/2 Words, abhängig vom Domain) Meldungsdefinitionen: • Per Meldung können Maximum nur 32 Words (64 Bytes) verarbeitet werden • Es müssen immer ganze Datenpunkte resp. Domain behandelt werden • Nur der RTU Modus ist unterstützt Dokumentsübersicht: • Der Rest des Dokuments wird nicht übersetzt, da der benutzte Wortschatz sehr einfach ist • Kapitel 2 gibt die Rechnungsregeln der Datenpunkt und Domain Index ab den RDO-com Datenpunkt und Domain Nummern. Die Lektüre dieses Kapitels ist normalerweise nicht notwendig, direkt auf Kapitel 3 gehen (Modbus Indextisch) • Kapitel 3: Die Liste der Daten bezieht sich auf die Schnittstelle Mensch-Maschine (MMI) des RDO300. Für die Bedeutung, das Format und die Struktur der Parameter, siehe das entsprechende Benutzerhandbuch RDO3xx. 1. Introduction (Français) Un autre document “Specification: communication protocol, Modbus <--> RDO3xx, basis” (164301) décrit le protocole de communication Modbus et le calcul des index des point de données Modbus. Abréviations: 164302/06.2013 3 • RDO3xx RDO353, RDO373, RDO383, RDO354, RDO374, RDO384, etc. • DHW Eau chaude sanitaire (ECS) • DH Chauffage urbain • R Lecture seulement • R/W Lecture/écriture • DP Point de donnée (PD) • Appl.ID Identification d’application • NaN Valeur indéfinie Traductions: • Data point Point de donnée • Domain Domaine • Time/date Heure/date • Holidays Vacances • Clocks Horloges • Heating circuit Circuit de chauffage • Domestic water circuit Circuit ECS • Boiler circuit Circuit de chaudière • Free circuit Horloge auxiliaire • Swich point Point de commutation • Set value Consigne • Actual value Valeur actuelle • Sensor Sonde • User level Niveau utilisateur • Specialist level Niveau spécialiste • Parameter Paramètre • Counters Compteur • Relays Relais Définitions générales: • Dans ce document, les valeurs hex sont définies par 0x. Par exemple 0xa (hex) représente 10 (déc) Appl.ID: • Régulateur principal (tous les PD qui ne sont pas indexés): 0 • Paramètres des circuits de chauffage: 0, 1..7 (appl.ID=0 est interprété comme 1, 1 = circuit de chauffage 1, 7 = circuit de chauffage 7) • Paramètres des circuits de chaudière (cascade): 0, 11..14 (appl.ID=0 est interprété comme 11, 11 = circuit de chaudière 1, 14 = circuit de chaudière 4) • Paramètres des circuits ECS: 0, 21..24 (appl.ID=0 est interprété comme 21, 21 = circuit ECS 1, 24 = circuit ECS 4) Remarque: RDO3x4 supporte seulement 1 circuit de chaudière (pas de cascade) et 1 circuit ECS Points de donnée: • Les valeurs des points de donnée (toujours 4 bytes de long) sont définies dans les régulateurs RDO300 comme valeurs flottantes • Un points de donnée signifie une valeur. Par exemple: paramètre 101 • L’interrogation d’une liste de points de donnée contigus est possible. Les points de donnée indéfinis sont retournés comme NaN (0xffc00000) par RDO383 depuis V4.00ßA et par RDO374 depuis V4.10 164302/06.2013 4 • En écriture, il n’est possible de traiter qu’un seul point de donnée par message (1 point de donnée: 4 bytes, 2 words) Domaines: • Les valeurs des domaines (de longueur variable) sont définis séparément (normalement pas de valeur flottante) • Un domaine représente une liste de valeurs. Par exemple: heure/date avec heure, minutes, etc. • L’interrogation d’une liste de domaines contigus est possible • En écriture, il n’est possible de traiter qu’un seul domaine par message (1 domaine: n bytes, n/2 words, en fonction du domaine) Définitions des messages: • Il est possible de traiter 32 words (64 bytes) au maximum par message • Les points de données resp. les domaines doivent toujours être traités entièrement • Seul le mode RTU est supporté Vue d’ensemble du document: • Le reste du document n’est pas traduit, le vocabulaire utilisé étant très simple • Le chapitre 2 donne la règle de calcul des index de points de données et de domaine Modbus à partir des numéros de points de données et de domaine RDOcom. La lecture de ce chapitre n’est normalement pas nécessaire, se porter directement chapitre 3 (Table d’index modbus) • Chapitre 3: la liste des données se rapporte à l’interface homme-machine (MMI) du RDO300. Voir le Manuel de l’utilisateur RDO3xx correspondant pour la signification, le format et la structure des paramètres. 164302/06.2013 5 2. Calculation of Modbus index from RDO-com number Circuits (applications) conversion Name • General control • Heating circuit • Boiler circuits • Domestic water circuits • Free circuit RDO 0 1..7 11..14 21..24 91 Modbus 0 1..7 11..14 16..19 (21 => 16, ...) 9 Remarks Heating circuit 1, Domestic water circuit 1, boiler circuit 1, ... 11 = Boiler circuit 1 21 = Domestic water circuit 1 Data points • Basis offset in Modbus index: 0 • Circuit offset factor in Modbus index: 0x800 => Max. 1024 circuit/circuit • Index band: 0x0..0x9fff (40960 words => 20480 datapoints) Remarks: • The Modbus protocol allows only 2 bytes words. So 1 data point will be defined as 2 words (4 bytes). • Only complete circuit can be transferred. So the Modbus index by circuit must always be even. => Modbus index calculation: • (circuit * 0x800) + (data point * 2) Data point Examples • General control, data point 0x15 • Heating circuit 1, data point 0xa • Boiler circuit 1, data point 0x15 • Domestic water circuit 1, data point 0x74 => (0 * 0x800) + (0x15 * 2) = 0x002a => (1 * 0x800) + (0xa * 2) = 0x0814 => (11 * 0x800) + (0x15 * 2) = 0x582a => (16 * 0x800) + (0x74 * 2) = 0x80e8 Domains • Offset factor in Modbus index: 0x40 => Max. 64 bytes/circuit • Index band: 0xa000..0xffff (24576 words) Remarks: • The Modbus protocol allows only 2 bytes words. So domains will be defined as n words (n = domain lenght/2). • Only complete domains can be transferred. So by domains, the Modbus index must always be a factor of the domain length. => Modbus index calculation: Name Length [words] • Time / date (domain 0xa) 4 164302/06.2013 Modbus index calculation 0xa000 6 • Holidays (domain 0x11..0x16) 3 • Switch points (domain 0x21..0x27) 3 • Reserve 0xb000 + (circuit * 0x40) + ((domain-0x11) * 3) 0xc000 + (circuit * 0x40) + ((domain-0x21) * 3) 0xd000..0xffff Domains Examples • Time / date, domain 0xa => 0xa000 • Holidays, heating circuit 1, domain 0x11 => 0xb000 + (1 * 0x40) + ((0x11-0x11) * 3) = 0xb040 • Switch points, heating circuit 1, domain 0x21 => 0xc000 + (1 * 0x40) + ((0x21-0x21) * 3) = 0xc040 • Switch points, domestic water circuit 1, domain 0x22 => 0xc000 + (16 * 0x40) + ((0x22-0x21) * 3) = 0xc403 • Switch points, free circuit, domain 0x23 => 0xc000 + (9 * 0x40) + ((0x23-0x21) * 3) = 0xc246 164302/06.2013 7 3. Table of MODBUS index Menu “Time/date” Time/date domain index RDO MODBUS Index Description Appl. DP Appl. Circuit 0 Time domain 0 10 0 40960 Time/date domain structure Name / Position Reserved, undefined Day of the week Year Month Day of the month Hours Minutes Seconds Domain byte index 0 1 2 3 4 5 6 7 Circuit 1 Format / Unit 1=Monday .. 7=Sunday 95=1995 to 94=2094 1..12 1..31 0..23 0..59 0..59 Remark: The Time/date domain can only be be writen from Bus with par.133=2 164302/06.2013 Circuit 2 8 Circuit 3 Attribute R/W R/W R/W R/W R/W R/W R/W R/W Circuit 4 Circuit 5 Circuit 6 Circuit 7 Menu “Holidays” Holidays domain index RDO Description Holiday domain bloc 1 Holiday domain bloc 2 Holiday domain bloc 3 Holiday domain Bloc 4 Holiday domain Bloc 5 Holiday domain Bloc 6 MODBUS Index Appl. DP Appl. 1 1 1 1 1 1 17 18 19 20 21 22 1 1 1 1 1 1 Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 45120 45123 45126 45129 45132 45135 45184 45187 45190 45193 45196 45199 45248 45251 45254 45257 45260 45263 45312 45315 45318 45321 45324 45327 45376 45379 45382 45385 45388 45391 45440 45443 45446 45449 45452 45455 45504 45507 45510 45513 45516 45519 Remarks: • Holiday data point reset state is 0xff • The holidays have to be programmed like on the controller MMI: • “bloc n+1” can only be filled if “bloc n” is filled • In a bloc the end date must be higher as the begin date • Begin date “bloc n+1” must be higher as the end date “bloc n” • By deleting a bloc, all following blocs will be shifted • Etc. Holidays domain structure Name / Position Year, begin Month, begin Day of the month, begin Year, end Month, end Day of the month, end 164302/06.2013 Domain byte index 0 1 2 3 4 5 Format / Unit 95=1995 to 94=2094 1..12 1..31 95=1995 to 94=2094 1..12 1..31 9 Attribute R/W R/W R/W R/W R/W R/W Menu “Clocks” Switch points domain RDO Description Heating circuit Switch point domain Mo. Switch point domain Tu. Switch point domain We. Switch point domain Th. Switch point domain Fr. Switch point domain Sa. Switch point domain Su. Domestic water circuit Switch point domain Mo. Switch point domain Tu. Switch point domain We. Switch point domain Th. Switch point domain Fr. Switch point domain Sa. Switch point domain Su. Free circuit Switch point domain Mo. Switch point domain Tu. Switch point domain We. Switch point domain Th. Switch point domain Fr. Switch point domain Sa. Switch point domain Su. 164302/06.2013 MODBUS Index Appl. DP Appl. 1 1 1 1 1 1 1 33 34 35 36 37 38 39 21 21 21 21 21 21 21 91 91 91 91 91 91 91 Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 1 1 1 1 1 1 49216 49219 49222 49225 49228 49231 49234 49280 49283 49286 49289 49292 49295 49298 49344 49347 49350 49353 49356 49359 49362 49408 49411 49414 49417 49420 49423 49426 49472 49475 49478 49481 49484 49487 49490 49536 49539 49542 49545 49548 49551 49554 49600 49603 49606 49609 49612 49615 49618 33 34 35 36 37 38 39 16 16 16 16 16 16 16 50176 50179 50182 50185 50188 50191 50194 50240 50243 50246 50249 50252 50255 50258 50304 50307 50310 50313 50316 50319 50322 50368 50371 50374 50377 50380 50383 50386 33 34 35 36 37 38 39 9 9 9 9 9 9 9 49728 49731 49734 49737 49740 49743 49746 10 Switch points structure Name / Position Switch point 1. on Switch point 1. off Switch point 2. on Switch point 2. off Switch point 3. on Switch point 3. off Domain byte index 0 1 2 3 4 5 Signification of the on switch points values: • 0: 00:00 • 1: 00:15 • 2: 00:30 • . • 94: 23:30 • 95: 23:45 • 96: 24:00 • 0xff: undefined 164302/06.2013 Format / Unit on switch point off switch point on switch point off switch point on switch point off switch point Attribute R/W R/W R/W R/W R/W R/W Signification of the off switch points values: 0x80 + 0: 00:00 0x80 + 1: 00:15 0x80 + 2: 00:30 0x80 + 94: 0x80 + 95: 0x80 + 96: 23:30 23:45 24:00 11 Menu “Set values” Set values Remarks: • All set values are R/W RDO Description Heating circuit Set value heating, 1 Set value heating, 2 Set value heating, 3 Domestic water circuit Set value domestic water, 1 Set value domestic water, 2 Set value domestic water, 3 Set value domestic water, 4 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 1 1 60 61 62 1 1 1 120 122 124 2168 2170 2172 4216 4218 4220 6264 6266 6268 8312 8314 8316 10360 10362 10364 12408 12410 12412 14456 14458 14460 21 21 21 21 70 71 72 73 16 16 16 16 140 142 144 146 32908 32910 32912 32914 34956 34958 34960 34962 37004 37006 37008 37010 39052 39054 39056 39058 12 Service, user level II Remarks: • Temperature sensor status: • 0: OK • 1: open • 2: short circuit • All Parameters are here read only, except Parameters: 30, 31, 34, 36, 40, 41, 81, 82 RDO Description Parameter 1, actual value Parameter 1, sensor status Parameter 1, set value Parameter 2, actual value Parameter 2, sensor status Parameter 2, set value Parameter 3, actual value Parameter 3, sensor status Parameter 3, set value Parameter 4, actual value Parameter 4, sensor status Parameter 4, set value Parameter 10, actual value Parameter 10, sensor status Parameter 10, set value Parameter 11, actual value Parameter 11, sensor status Parameter 12, actual value Parameter 12, sensor status Parameter 12, set value Parameter 14, actual value Parameter 14, sensor status Parameter 14, set value 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 21 21 21 21 21 21 21 21 21 21 21 21 1 1 1 0 0 1 1 1 1 1 1 3 95 207 4 97 207 364 366 391 365 367 392 10 91 205 11 313 12 90 208 14 93 209 16 16 16 16 16 16 16 16 16 16 16 16 1 1 1 0 0 1 1 1 1 1 1 6 190 414 8 194 414 728 732 782 730 734 784 20 182 410 22 626 24 180 416 28 186 418 32774 32958 33182 32776 32962 33182 33496 33500 33550 33498 33502 33552 2068 2230 2458 34822 35006 35230 34824 35010 35230 35544 35548 35598 35546 35550 35600 4116 4278 4506 36870 37054 37278 36872 37058 37278 37592 37596 37646 37594 37598 37648 6164 6326 6554 38918 39102 39326 38920 39106 39326 39640 39644 39694 39642 39646 39696 8212 8374 8602 10260 10422 10650 12308 12470 12698 14356 14518 14746 2072 2228 2464 2076 2234 2466 4120 4276 4512 4124 4282 4514 6168 6324 6560 6172 6330 6562 8216 8372 8608 8220 8378 8610 10264 10420 10656 10268 10426 10658 12312 12468 12704 12316 12474 12706 14360 14516 14752 14364 14522 14754 13 RDO Description Parameter 20, actual value Parameter 20, sensor status Parameter 20, set value Parameter 21, actual value Parameter 21, sensor status Parameter 21, set value Parameter 23, actual value Parameter 23, sensor status Parameter 23, alternate value Parameter 24, actual value Parameter 24, sensor status Parameter 24, set value Parameter 25, actual value Parameter 25, sensor status Parameter 25, set value Parameter 27, actual value Parameter 27, sensor status Parameter 27, set value Parameter 28, actual value Parameter 28, sensor status Parameter 28, alternate value Parameter 29, actual value Parameter 29, sensor status Parameter 29, alternate value Parameter 2A, actual value Parameter 2A, sensor status Parameter 2A, alternate value Parameter 2b, actual value Parameter 2b, sensor status Parameter 2c, actual value Parameter 2c, sensor status Parameter 2d, actual value 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 11 11 11 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20 94 237 21 92 331 23 96 156 24 98 281 25 99 281 27 78 263 28 79 264 600 648 601 649 602 660 644 11 11 11 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40 188 474 42 184 662 46 192 312 48 196 562 50 198 562 54 156 526 56 158 528 1200 1296 1202 1298 1204 1320 1288 22568 22716 23002 22570 22712 23190 22574 22720 22840 24616 24764 25050 24618 24760 25238 24622 24768 24888 26664 26812 27098 26666 26808 27286 26670 26816 26936 28712 28860 29146 28714 28856 29334 28718 28864 28984 14 Circuit 5 Circuit 6 Circuit 7 RDO Description Parameter 2d, sensor status Parameter 2d, alternate value Parameter 2E, actual value Parameter 2E, sensor status Parameter 2F, actual value Parameter 2F, sensor status Parameter 2F, alternate value Parameter 2J, actual value Parameter 2J, sensor status Parameter 2L, actual value Parameter 2L, sensor status Parameter 30 Parameter 31 Parameter 34 Parameter 35 Parameter 36 Parameter 37 Parameter 40 Parameter 41 Parameter 45, actual value Parameter 45, set value Parameter 46, actual value Parameter 46, set value Parameter 47 Parameter 81 Parameter 82 Parameter 83, status 1 Parameter 83, status 2 Parameter 85 Parameter 86 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 11 11 0 0 0 0 11 11 11 11 0 0 0 0 0 0 0 0 0 643 646 641 645 664 666 667 30 31 34 35 36 37 40 41 45 258 46 347 47 362 363 662 663 88 89 0 0 0 0 0 0 0 0 0 0 0 11 11 0 0 0 0 11 11 11 11 0 0 0 0 0 0 0 0 0 1286 1292 1282 1290 1328 1332 1334 60 62 68 70 72 74 80 82 90 516 92 694 94 724 726 1324 1326 176 178 Circuit 1 Circuit 2 Circuit 3 Circuit 4 22588 22590 24636 24638 26684 26686 28732 28734 22608 22610 22618 23044 24656 24658 24666 25092 26704 26706 26714 27140 28752 28754 28762 29188 15 Circuit 5 Circuit 6 Circuit 7 RDO Description Parameter 90 Parameter 91 Parameter 92 Parameter 93 Parameter 94 Parameter 95 Parameter 96 Parameter 97 Parameter 98 Parameter 99 Parameter A0 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 240 241 242 243 244 245 246 247 248 249 219 0 0 0 0 0 0 0 0 0 0 0 480 482 484 486 488 490 492 494 496 498 438 Circuit 1 16 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 Service, specialist level I Remarks: • Parameter 164 to 166 are read only RDO Description Parameter 100 Parameter 101 Parameter 102 Parameter 103 Parameter 104 Parameter 105 Parameter 106 Parameter 107 Parameter 108 Parameter 109 Parameter 10A Parameter 10b Parameter 10c Parameter 10d Parameter 10E Parameter 10F Parameter 10h Parameter 10J Parameter 10L Parameter 10n Parameter 10P Parameter 10r Parameter 10t Parameter 10U Parameter 10y Parameter 110 Parameter 111 Parameter 112 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 11 11 0 11 0 0 0 11 11 11 11 0 0 0 11 0 0 0 0 0 0 0 0 0 0 1 100 101 102 103 104 105 106 107 108 109 800 801 802 803 804 805 806 807 808 809 900 901 902 903 904 110 111 112 0 0 11 11 0 11 0 0 0 11 11 11 11 0 0 0 11 0 0 0 0 0 0 0 0 0 0 1 200 202 204 206 208 210 212 214 216 218 1600 1602 1604 1606 1608 1610 1612 1614 1616 1618 1800 1802 1804 1806 1808 220 222 224 Circuit 1 Circuit 2 Circuit 3 Circuit 4 22732 22734 24780 24782 26828 26830 28876 28878 22738 24786 26834 28882 22746 24128 24130 24132 24794 26176 26178 26180 26842 28224 28226 28228 28890 30272 30274 30276 24140 26188 28236 30284 2272 4320 6368 8416 17 Circuit 5 Circuit 6 Circuit 7 10464 12512 14560 RDO Description Parameter 113 Parameter 114 Parameter 115 Parameter 116 Parameter 117 Parameter 118 Parameter 119 Parameter 11A Parameter 11b Parameter 11c Parameter 11d Parameter 11E Parameter 11F Parameter 11J Parameter 11L Parameter 11n Parameter 11P Parameter 11r Parameter 11t Parameter 11U Parameter 11y Parameter 120 Parameter 121 Parameter 122 Parameter 123 Parameter 124 Parameter 125 Parameter 126 Parameter 127 Parameter 128 Parameter 129 Parameter 12A Parameter 12b 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 0 0 21 21 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 0 0 0 0 113 114 115 116 117 118 119 810 811 812 813 814 815 817 818 819 905 906 907 908 909 120 121 122 123 124 125 126 127 128 129 820 821 1 0 0 16 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 0 0 0 0 226 228 230 232 234 236 238 1620 1622 1624 1626 1628 1630 1634 1636 1638 1810 1812 1814 1816 1818 240 242 244 246 248 250 252 254 256 258 1640 1642 2274 4322 6370 8418 10466 12514 14562 33000 33002 35048 35050 37096 37098 39144 39146 22780 24828 26876 28924 18 RDO Description Parameter 12c Parameter 12d Parameter 12E Parameter 12F Parameter 12h Parameter 12J Parameter 12L Parameter 12n Parameter 12P Parameter 12r Parameter 12t Parameter 12U Parameter 12y Parameter 130 Parameter 131 Parameter 132 Parameter 133 Parameter 135 Parameter 136 Parameter 137 Parameter 138 Parameter 139 Parameter 13A Parameter 13b Parameter 13c Parameter 13d Parameter 13E Parameter 13F Parameter 13h Parameter 13J Parameter 13L Parameter 13n Parameter 13P 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 11 11 0 0 0 0 0 0 0 0 822 823 824 825 826 827 828 829 910 911 912 913 914 130 131 132 133 135 136 137 138 139 830 831 832 833 834 835 836 837 838 839 915 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 11 11 0 0 0 0 0 0 0 0 1644 1646 1648 1650 1652 1654 1656 1658 1820 1822 1824 1826 1828 260 262 264 266 270 272 274 276 278 1660 1662 1664 1666 1668 1670 1672 1674 1676 1678 1830 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 3708 24190 24192 5756 26238 26240 7804 28286 28288 9852 30334 30336 11900 13948 15996 19 RDO Description Parameter 13r Parameter 13t Parameter 13U Parameter 13y Parameter 140 Parameter 141 Parameter 142 Parameter 143 Parameter 144 Parameter 145 Parameter 146 Parameter 147 Parameter 148 Parameter 149 Parameter 14A Parameter 14b Parameter 14c Parameter 14d Parameter 14E Parameter 14F Parameter 14h Parameter 14J Parameter 14L Parameter 14n Parameter 14P Parameter 14r Parameter 14t Parameter 14U Parameter 14y Parameter 150 Parameter 151 Parameter 152 Parameter 153 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 11 11 11 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 0 1 916 917 918 919 140 141 142 143 144 145 146 147 148 149 840 841 842 843 844 845 846 847 848 849 920 921 922 923 924 150 151 152 153 0 0 0 0 11 11 11 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 0 1 1832 1834 1836 1838 280 282 284 286 288 290 292 294 296 298 1680 1682 1684 1686 1688 1690 1692 1694 1696 1698 1840 1842 1844 1846 1848 300 302 304 306 Circuit 1 Circuit 2 Circuit 3 Circuit 4 22808 22810 22812 22814 22816 22818 22820 22822 22824 24856 24858 24860 24862 24864 24866 24868 24870 24872 26904 26906 26908 26910 26912 26914 26916 26918 26920 28952 28954 28956 28958 28960 28962 28964 28966 28968 22828 24876 26924 28972 2354 4402 6450 8498 20 Circuit 5 Circuit 6 Circuit 7 10546 12594 14642 RDO Description Parameter 154 Parameter 155 Parameter 156 Parameter 157 Parameter 158 Parameter 159 Parameter 15A Parameter 15b Parameter 15c Parameter 15d Parameter 15E Parameter 15F Parameter 15h Parameter 15J Parameter 15L Parameter 15n Parameter 15P Parameter 15r Parameter 15t Parameter 15U Parameter 15y Parameter 160 Parameter 161 Parameter 162 Parameter 163 Parameter 164 Parameter 165 Parameter 166 Parameter 167 Parameter 168 Parameter 169 Parameter 16A Parameter 16b 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 11 11 11 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0 1 1 0 1 1 1 0 0 154 155 156 157 158 159 850 851 852 853 854 855 856 857 858 859 925 926 927 928 929 160 161 162 163 164 165 166 167 168 169 860 861 1 11 11 11 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0 1 1 0 1 1 1 0 0 308 310 312 314 316 318 1700 1702 1704 1706 1708 1710 1712 1714 1716 1718 1850 1852 1854 1856 1858 320 322 324 326 328 330 332 334 336 338 1720 1722 2356 22838 22840 22842 4404 24886 24888 24890 6452 26934 26936 26938 8500 28982 28984 28986 10548 12596 14644 2366 4414 6462 8510 10558 12606 14654 2368 2370 2372 4416 4418 4420 6464 6466 6468 8512 8514 8516 10560 10562 10564 12608 12610 12612 14656 14658 14660 2376 2378 4424 4426 6472 6474 8520 8522 10568 10570 12616 12618 14664 14666 2382 2384 2386 4430 4432 4434 6478 6480 6482 8526 8528 8530 10574 10576 10578 12622 12624 12626 14670 14672 14674 21 RDO Description Parameter 16c Parameter 16d Parameter 16E Parameter 16F Parameter 16h Parameter 16J Parameter 16L Parameter 16n Parameter 16P Parameter 16r Parameter 16t Parameter 16U Parameter 16y Parameter 170 Parameter 171 Parameter 172 Parameter 173 Parameter 174 Parameter 175 Parameter 176 Parameter 177 Parameter 178 Parameter 179 Parameter 17A Parameter 17b Parameter 17c Parameter 17d Parameter 17E Parameter 17F Parameter 17h Parameter 17J Parameter 17L Parameter 17n 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 862 863 864 865 866 867 868 869 930 931 932 933 934 170 171 172 173 174 175 176 177 178 179 870 871 872 873 874 875 876 877 878 879 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1724 1726 1728 1730 1732 1734 1736 1738 1860 1862 1864 1866 1868 340 342 344 346 348 350 352 354 356 358 1940 1942 1944 1946 1948 1950 1952 1954 1956 1958 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 2388 2390 2392 2394 2396 4436 4438 4440 4442 4444 6484 6486 6488 6490 6492 8532 8534 8536 8538 8540 10580 10582 10584 10586 10588 12628 12630 12632 12634 12636 14676 14678 14680 14682 14684 22 RDO Description Parameter 17P Parameter 17r Parameter 17t Parameter 17U Parameter 17y Parameter 180 Parameter 181 Parameter 182 Parameter 183 Parameter 185 Parameter 186 Parameter 187 Parameter 188 Parameter 18A Parameter 18b Parameter 18c Parameter 18d Parameter 18E Parameter 18F Parameter 18h Parameter 18J Parameter 18L Parameter 18n Parameter 18P Parameter 18r Parameter 18t Parameter 18U Parameter 18y Parameter 190 Parameter 191 Parameter 192 Parameter 193 Parameter 194 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 1 1 1 1 0 1 0 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 21 21 21 21 21 935 936 937 938 939 180 181 182 183 185 186 187 188 880 881 882 883 884 885 886 887 888 889 940 941 942 943 944 190 191 192 193 194 0 0 0 0 0 1 1 1 1 0 1 0 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 16 16 16 16 16 1870 1872 1874 1876 1878 360 362 364 366 370 372 374 376 1760 1762 1764 1766 1768 1770 1772 1774 1776 1778 1880 1881 1882 1883 1884 380 382 384 386 388 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 2408 2410 2412 2414 4456 4458 4460 4462 6504 6506 6508 6510 8552 8554 8556 8558 10600 10602 10604 10606 12648 12650 12652 12654 14696 14698 14700 14702 2420 4468 6516 8564 10612 12660 14708 22904 24952 27000 29048 33148 33150 33152 33154 33156 35196 35198 35200 35202 35204 37244 37246 37248 37250 37252 39292 39294 39296 39298 39300 23 RDO Description Parameter 195 Parameter 196 Parameter 197 Parameter 198 Parameter 199 Parameter 19A Parameter 19b Parameter 19c Parameter 19d Parameter 19E Parameter 19F Parameter 19h Parameter 19J Parameter 19L Parameter 19n Parameter 19P Parameter 19r Parameter 19t Parameter 19U Parameter 19y Parameter 1A0 Parameter 1A1 Parameter 1A2 Parameter 1A3 Parameter 1A4 Parameter 1A5 Parameter 1A6 Parameter 1A7 Parameter 1A8 Parameter 1A9 Parameter 1AA Parameter 1Ab Parameter 1Ac 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 21 21 21 0 21 21 21 21 21 21 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 195 196 197 198 199 890 891 892 893 894 895 896 897 898 899 945 946 947 948 949 400 401 402 403 404 405 406 407 408 409 500 501 502 0 0 16 16 16 0 16 16 16 16 16 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 390 392 394 396 398 1780 1782 1784 1786 1788 1790 1792 1794 1796 1798 1890 1892 1894 1896 1898 800 802 804 806 808 810 812 814 816 818 1000 1002 1004 Circuit 1 Circuit 2 Circuit 3 Circuit 4 33162 33164 33166 35210 35212 35214 37258 37260 37262 39306 39308 39310 34550 34552 34554 34556 34558 34560 36598 36600 36602 36604 36606 36608 38646 38648 38650 38652 38654 38656 40694 40696 40698 40700 40702 40704 24 Circuit 5 Circuit 6 Circuit 7 RDO Description Parameter 1Ad Parameter 1AE Parameter 1AF Parameter 1Ah Parameter 1AJ Parameter 1AL Parameter 1An Parameter 1AP Parameter 1Ar Parameter 1At Parameter 1AU Parameter 1Ay Parameter 1b0 Parameter 1b1 Parameter 1b2 Parameter 1b3 Parameter 1b4 Parameter 1b5 Parameter 1b6 Parameter 1b7 Parameter 1bA Parameter 1bb Parameter 1bc Parameter 1bd Parameter 1bE Parameter 1bF Parameter 1bh Parameter 1bJ Parameter 1bL Parameter 1bn Parameter 1bP Parameter 1br 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 503 504 505 506 507 508 509 950 951 952 953 954 410 411 412 413 414 415 416 417 510 511 512 513 514 515 516 517 518 519 955 956 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1006 1008 1010 1012 1014 1016 1018 1900 1902 1904 1906 1908 820 822 824 826 828 830 832 834 1020 1022 1024 1026 1028 1030 1032 1034 1036 1038 1910 1912 Circuit 1 25 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 RDO Description Parameter 1bt Parameter 1bU Parameter 1by Parameter 1c0 Parameter 1c1 Parameter 1c2 Parameter 1c3 Parameter 1c4 Parameter 1c5 Parameter 1c6 Parameter 1c7 Parameter 1c8 Parameter 1c9 Parameter 1cA Parameter 1dA Parameter 1db Parameter 1dc Parameter 1dd Parameter 1dE Parameter 1E0 Parameter 1E1 Parameter 1E2 Parameter 1E3 Parameter 1E4 Parameter 1E5 Parameter 1E6 Parameter 1E7 Parameter 1E8 Parameter 1E9 Parameter 1EA Parameter 1Eb Parameter 1Ec 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 957 958 959 420 421 422 423 424 425 426 427 428 429 520 530 531 532 533 534 440 441 442 443 444 445 446 447 448 449 540 541 542 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1914 1916 1918 840 842 844 846 848 850 852 854 856 858 1040 1060 1062 1064 1066 1068 880 882 884 886 888 890 892 894 896 898 900 902 904 Circuit 1 26 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 RDO Description Parameter 1Ed Parameter 1EE Parameter 1EF Parameter 1Eh Parameter 1EJ Parameter 1EL Parameter 1En Parameter 1EP Parameter 1Er Parameter 1Et Parameter 1EU Parameter 1Ey Parameter 1F0 Parameter 1F1 Parameter 1F2 Parameter 1F3 Parameter 1F4 Parameter 1F5 Parameter 1F6 Parameter 1F7 Parameter 1F8 Parameter 1h0 Parameter 1h1 Parameter 1h2 Parameter 1h6 Parameter 1J0 Parameter 1J1 Parameter 1J2 Parameter 1J3 Parameter 1J4 Parameter 1J5 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 543 544 545 546 547 548 549 970 971 972 973 974 450 451 452 453 454 455 456 457 458 460 461 462 466 470 471 472 473 474 475 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 906 908 910 912 914 916 918 1940 1942 1944 1946 1948 900 902 904 906 908 910 912 914 916 920 922 924 932 940 942 944 946 948 950 2994 2996 2998 5042 5044 5046 7090 7092 7094 9138 9140 9142 11186 11188 11190 13234 13236 13238 15282 15284 15286 27 RDO Description Parameter 1J6 Parameter 1J7 Parameter 1J8 Parameter 1J9 Parameter 1JA Parameter 1Jb Parameter 1Jc Parameter 1Jd Parameter 1JE Parameter 1JF Parameter 1Jh Parameter 1JJ Parameter 1JL Parameter 1L0 Parameter 1L1 Parameter 1L2 Parameter 1L4 Parameter 1L7 Parameter 1L8 Parameter 1L9 Parameter 1LA Parameter 1Lb Parameter 1n0 Parameter 1n1 Parameter 1n2 Parameter 1n3 Parameter 1n4 Parameter 1n5 Parameter 1n6 Parameter 1n7 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 1 1 1 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 476 477 478 479 570 571 572 573 574 575 576 577 578 480 481 482 484 487 488 489 580 581 490 491 492 493 494 495 496 497 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 952 954 956 958 1140 1142 1144 1146 1148 1150 1152 1154 1156 960 962 964 968 974 976 978 1160 1162 980 982 984 986 988 990 992 994 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 3002 3004 3006 5050 5052 5054 7098 7100 7102 9146 9148 9150 11194 11196 11198 13242 13244 13246 15290 15292 15294 3192 5240 7288 9336 11384 13432 15480 3206 5254 7302 9350 11398 13446 15494 28 RDO Description Parameter 1n8 Parameter 1n9 Parameter 1nA Parameter 1nb Parameter 1nc Parameter 1nd Parameter 1nE Parameter 1nF Parameter 1nh Parameter 1nJ Parameter 1nL Parameter 1nn Parameter 1P0 Parameter 1P1 Parameter 1P2 Parameter 1P3 Parameter 1P4 Parameter 1P5 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 498 499 590 591 592 593 594 595 596 597 598 599 760 761 762 763 764 765 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 996 998 1180 1182 1184 1186 1188 1190 1192 1194 1196 1198 1520 1522 1524 1526 1528 1530 Circuit 1 29 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 Service, specialist level II Remarks: • Appl. ID 0 affects the relays on RDO3xx, if the relays is neither heating circuit nor boiler circuit nor domestic water circuit • The parameters are here read only RDO Description RDO counters Parameter +30 Parameter +31 Parameter +34 Parameter +36 Parameter +37 Parameter +40 Parameter +41 Parameter +47 Parameter +48 (81) Parameter +49 (82) RDO relays Parameter +50 Parameter +51 Parameter +52 Parameter +53 Parameter +54 Parameter +55 Parameter +56 Parameter +57 Parameter +58 Parameter +59 Parameter +5A Parameter +5b Parameter +5c 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 30 31 34 36 37 40 41 47 362 363 0 0 0 0 0 0 0 0 0 0 60 62 68 72 74 80 82 94 724 726 0 0 0 0 0 0 0 0 0 0 0 0 0 80 81 82 83 84 85 86 87 88 89 700 701 702 0 0 0 0 0 0 0 0 0 0 0 0 0 160 162 164 166 168 170 172 174 176 178 1400 1402 1404 Circuit 1 30 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 RDO Description Heating circuit relays Parameter +65 Parameter +66 Parameter +67 Boiler circuit relays Parameter +70 Parameter +71 Parameter +72 Parameter +73 Parameter +75 Parameter +76 Parameter +77 Parameter +78 Domestic water circuit relays Parameter +80 Parameter +81 Parameter +82 Parameter +83 Parameter +84 Parameter +85 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 1 1 344 345 346 1 1 1 688 690 692 2736 2738 2740 4784 4786 4788 6832 6834 6836 8880 8882 8884 10928 10930 10932 12976 12978 12980 15024 15026 15028 11 11 11 11 11 11 11 11 338 339 340 341 354 342 343 88 11 11 11 11 11 11 11 11 676 678 680 682 708 684 686 23204 23206 23208 23210 23236 23212 23214 25252 25254 25256 25258 25284 25260 25262 27300 27302 27304 27306 27332 27308 27310 29348 29350 29352 29354 29380 29356 29358 176 22704 24752 26800 28848 21 21 21 21 21 21 372 373 374 375 376 377 16 16 16 16 16 16 744 746 748 750 752 754 33512 33514 33516 33518 33520 33522 35560 35562 35564 35566 35568 35570 37608 37610 37612 37614 37616 37618 39656 39658 39660 39662 39664 39666 31 RDO Description RDO inputs RDO all inputs RDO input 1 (te. 35) RDO input 2 (te. 34) RDO input 3 (te. 33) RDO input 4 (te. 32) RDO input 5 (te. 31) RDO operation counter 1 (te.3) RDO operation counter 2 (te.4) RDO input 2.1 (te. 34) RDO input 2.2 (te. 34) RDO input 2.3 (te. 34) RDO input 2.4 (te. 34) RDO input 8.1 (te. 28) RDO input 8.2 (te. 28) RDO input 8.3 (te. 28) RDO input 8.4 (te. 28) RDO input 9.1 (te. 27) RDO input 9.2 (te. 27) RDO input 9.3 (te. 27) RDO input 9.4 (te. 27) 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 215 282 283 284 285 286 287 288 613 614 615 616 607 608 609 610 252 253 255 256 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 430 564 566 568 570 572 574 576 1226 1228 1230 1232 1214 1216 1218 1220 504 506 510 512 Circuit 1 32 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 RDO Description Heating circuit inputs Heating circuit inputs Heating circuit input 1 Heating circuit input 2 Boiler circuit inputs Boiler circuit inputs Boiler circuit input 1 Boiler circuit input 2 Boiler circuit op.counter 1 Boiler circuit op.counter 2 Domestic water circuit input Domestic water circuit inputs Domestic water circuit input 1 Domestic water circuit input 2 Dom.water DW-Thermostat Dom.water DW-Electrical 164302/06.2013 MODBUS Index Appl. DP Appl. Circuit 0 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 1 1 1 316 312 311 1 1 1 632 624 622 2680 2672 2670 4728 4720 4718 6776 6768 6766 8824 8816 8814 10872 10864 10862 12920 12912 12910 14968 14960 14958 11 11 11 11 11 317 314 318 321 322 11 11 11 11 11 634 628 636 642 644 23162 23156 23164 23170 23172 25210 25204 25212 25218 25220 27258 27252 27260 27266 27268 29306 29300 29308 29314 29316 21 21 21 21 21 378 379 380 381 382 16 16 16 16 16 756 758 760 762 764 33524 33526 33528 33530 33532 35572 35574 35576 35578 35580 37620 37622 37624 37626 37628 39668 39670 39672 39674 39676 33 Common data points (not available in RDO-MMI) RDO Description MODBUS Index Appl. DP Attr. Appl. Circuit 0 Controller type Software version Software article number Test a) Room sensor calibration Cascade boiler set value Heating circuit mode Boiler circuit mode Domestic water circuit mode Number of heating circuits Number of boiler circuits Number of dom.water circuits Bus boiler set value Bus storage set value Bus cool attribut (Bitmap 0x1) Bus boiler actual value Bus return actual value Bus outside actual value Bus outside actual value b) Bus flag 'standby' Bus flag 'summer' Bus flag 'normal' Bus flag 'reduced' 0 0 0 0 1 0 1 11 21 0 0 0 0 0 0 0 0 1 0 1 1 1 1 1 2 204 239 75 210 213 277 278 350 351 389 368 751 756 369 370 371 371 393 394 395 396 R R R W R/W R R R R R R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W 0 0 0 0 1 0 1 11 16 0 0 0 0 0 0 0 0 1 0 1 1 1 1 2 4 408 478 150 420 426 554 556 700 702 778 736 1502 1512 738 740 Busflag 'Force loading DHW' Busflag ‘Block energy gen’ 21 0 670 301 R/W R/W 16 0 1340 602 Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 5 Circuit 6 Circuit 7 2198 4246 6294 8342 10390 12438 14486 2474 23082 33324 4522 25130 35372 6570 27178 37420 8618 29226 39468 10666 12714 14762 2790 4838 6886 8934 10982 13030 15078 2834 2836 2838 2840 4882 4884 4886 4888 6930 6932 6934 6936 8978 8980 8982 8984 11026 11028 11030 11032 13074 13076 13078 13080 15122 15124 15126 15128 34108 36156 38204 742 786 788 790 792 a) Write Test: • 0: Reset test state • 1: Set test state (timeout 5 min.): LCD clear, inhibit keyboard, reset outputs • 7: Set EEPROM default values • 8: Reset history error memory 164302/06.2013 b) Broadcast for all heating circuits 34 Version history Version Change ( description) 1.11 1.20 First edition Undefined domain answer = NaN RDO3x4 specific data points Translation in french and german Add remarks to the holidays Add datapoints (RDO3x3 V4.xx, RDO3x4 V5.xx) Add datapoints (RDO3x4 V6.xx), error corrections Add datapoints (RDO input 2.x, 8.x, 9.x, DP301, 751, 756) Add hex datapoints (1j3..1Jl, etc.) 1.21 1.22 1.23 1.24 1.25 1.26 164302/06.2013 changed Date 21.04.1999 05.03.2004 Visa Smn Pa 27.04.2005 22.06.2005 18.12.2006 22.10.2007 22.03.2010 Pa Pa Pa Pa Pa 18.07.2013 Pa 35