Introduction Introduction Contents
Transcription
Introduction Introduction Contents
Firmware Release Notes for Remote I/O ComUnit LB/FB 8x09 Page 1 of 2 06.06.2011 distribution The document is intended for users of Pepperl+Fuchs LB/FB Remote I/O abstract The document gives system related information about the available releases and goes beyond the coverage of the standard documentation. The contents of this information can also be found on the CD-ROM supplied with the product. The information about the available releases should help with the decision of whether to implement an available update or not. Deliveries of older releases are possible e.g. to work in redundant systems. The order number is printed on the device label LB8109Hxxxx resp. FB8209Hxxxx (with xxxx as a placeholder for the software version). Introduction This technical document describes the release history of ComUnit 8x09. Contents Introduction ..................................................................................................................1 Contents .......................................................................................................................1 ComUnit Versions and Functionalities ........................................................................2 V9.04 ........................................................................................................................2 V9.03 ........................................................................................................................2 V9.02 ........................................................................................................................2 Authors Norbert Lindner System- and Application Engineer Planetenfeldstr. 97, D-44379 Dortmund, Germany Reviewers Rainer Hillebrand Horst Galm TDOCT-1927A_ENG Versions Page 2 of 2 ComU ComUnit Versions and Functionalities Version 9.04 represents the latest software revision for ComUnit 8x09. V9.04 - HART-Buffer length corrected in comm unit Since the beginning of 2011 all comm units are equipped with a new memory chip. In order to visualize FLASH-memory download activity LEDs 1, 2 and 5 (green, red and yellow) are activated alternately. During this period the comm unit should not be removed from the backplane or switched off. V9.03 - start-up obstacle in 5x04 drivers removed - variable timeout after configuration changes between 1 and 5 seconds depending on the number of slots that have changed - modules 1x07, 1x14, 1x15 (2Byte/4Byte) now available (without time stamp) - new digital output 6x15 - HART work around in the HART master for HART devices which do not respond to the short address 0 - 5x05 can use tables for user defined thermo couples - Easycom: status bits can be switched off individually for analog outputs or for analog inputs using a new parameter - Module 1x03: counter will be deleted after a configuration change - 4x04, 4x05 feature improved Profibus diagnostic - 1 second delay for power supply failure message - Easycom: Diagnose-Offset = 1 introduced as the default value - ExtDiag-Bit returning to GOOD now forces a Diagnose-Refresh - improved Profibus Diagnostics - power supply failure generates a channel error message in the ComUnit V9.02 -new High Level driver for 5x04 -5 sec delay for status bits because of diagnostic messages after configuration changes -delete the special telegram flags in the passive ComUnit - Data delayed by 5 seconds. - variable timeout after configuration changes between 1 and 5 seconds depending on the number of slots that have changed V9.01 -unused memory in the Profibus IO Array set to Zero. example.: 1x02 generates 1 Byte for the 4IO setting. The remaining 3 bytes are set to Zero. V9.00 based on firmware 6.23 of ComUnit 8x05 - introduces Unicom-Modules 2I/2O and 4I/4O tdoct-1927A_eng