Progress of Investigation of Power Supply Facilities Failure at
Transcription
Progress of Investigation of Power Supply Facilities Failure at
Progress of Investigation of Power Supply Facilities Failure at Fukushima Daiichi Nuclear Power Station < Reference > March 25, 2013 Tokyo Electric Power Company At around 6:57 PM on March 18, 2013, there was an incident where the power supply facilities in the Main Anti-earthquake Building at Fukushima Daiichi Nuclear Power Station momentarily stopped. Upon investigation, the regular M/C (Metal-clad switch gear) in the Process Building, common M/C4A and Units 3-4 temporary M/C (A) were found to be stopped due to the incident. Power supply system structure of the affected facilities Okuma line 4L Okuma line 3L 66kV Switchyard (GIS) 66kV Switchyard (GIS) Common M/C (1B) Unit 1 SFP alternative cooling system (Secondary system) Common M/C (2B) Backup M/C in the Process Building Recovered at 2:20 PM on Mar. 19 Regular M/C in the Process Building (3A) (3A) (5A) ⑫ transformer Common pool temporary P/C Legend ⑪ transformer Receiving power Affected and suspended facilities Load system switching Circuit breaker opened Cesium adsorption apparatus (Kurion) (5B) Units 3-4 temporary M/C (A) Recovered at 3:00 PM on Mar. 19 Affected facilities which have been recovered Started at 12:01 PM on Mar. 19 Steady flow rate achieved at 12:17 PM. (4B) (4A) Circuit breaker opened Nitrogen separator (B) Power supply suspended Common M/C (2A) Backup M/C at the substation (10A) ⑥-1 transformer ⑥-2 transformer Common P/C 4A Common P/C 4C Diesel generator Common pool cooling system Recovered at 12:12 AM on Mar. 20 (4A) Common M/C 4A Unit 4 SFP alternative cooling system (Secondary system) Unit 3 SFP alternative cooling system (Primary and secondary systems) Temporarily recovered (by power supplied from a Recovered at 10:43 diesel generator) at 4:13 PM on Mar. 19. Suspended PM on Mar. 19 at 6:48 PM. Recovered at 10:26 PM on Mar. 19 (with power supplied from the regular M/C in the Process Building). Unit 4 SFP alternative cooling system (Primary system) Recovered at 1:20 PM on Mar. 19 Unit 3 PCV gas control system (A system) In-service at 5:00 PM on Mar. 19 Analysis of the Power Supply Facilities Failure [Power supply system structure] Since power receiving cable renovation for the regular M/C in the Process Building (as part of Tsunami countermeasures) was ongoing at the time of the incident, the regular M/C was temporarily receiving power from the backup M/C in the Process Building. [Analysis] 1. The ground relay in B system operated : The failure is assumed to have occurred in B system and high voltage power supply system. 2. The circuit breakers of the regular M/C (3A) and (4A) in the Process Building and the backup M/C in the Process Building (3A) tripped due to overcurrent. : The failure is assumed to have occurred in the downstream of the regular M/C in the Process Building (4A). 3. The ground directional relays and the circuit breakers of Units 3-4 temporary M/C (4A), (5A) and (10A) did not operate. : The failure is assumed to have occurred in the upstream of the load systems of Units 3-4 temporary M/C. 4. Fault current was found in Units 3-4 temporary M/C (A) (5B). : The failure is assumed to have occurred in the downstream of Units 3-4 temporary M/C (A) (5B). Okuma line 3L Legend Receiving power Suspended due to tripping 66kV switchyard in the south side Suspended 1 Ground overvoltage Common M/C (2B) relay confirmed Backup M/C at the substation Common M/C (2A) Vo=6.45kV Opened automatically during power supply suspension in order to prevent unnecessary cutting of circuit breakers due to magnetizing inrush current upon restart Ground overvoltage relay confirmed * Vo=6.75kV Backup M/C in the Process Building Regular M/C in the Process Building (1B) (3A) 2 (3A) Circuit breaker operated due to overcurrent Circuit breaker operated due to overcurrent * (4A) (4B) Circuit breaker operated due to overcurrent Units 3-4 temporary M/C (2A) (5B) (6A) (4A) (5A) Circuit breaker operated due to undervoltage Transformer No.10 Fault current confirmed 4 (10A) Protection relays and circuit breakers did not operate Transformer No.12 Common pool temporary P/C (1B) Common M/C (4A) (5A) The failure is assumed to have occurred in Units 3-4 temporary M/C (A). Okuma line 4L Transformer No.11 Transformer No.6-1 Transformer No.6-2 3 Appearance of Units 3-4 Temporary M/C (A) (1) Full view of Units 3-4 temporary M/C (A) (Units 3-4 switchyard) Power panel where soot was found Appearance of Units 3-4 temporary M/C Inspection of Units 3-4 temporary M/C Power panel Power panel door Front side Back side Units 3-4 temporary M/C (A) power panels and their doors Units 3-4 temporary M/C with the power panel door opened (below the power panel where soot was found) Photos taken on March 20, 2013 Appearance of Units 3-4 Temporary M/C (A) (2) Soot found on the instrument current transformer (terminal) of Units 3-4 temporary M/C Power panel where soot was found Soot found on the walls of Units 3-4 temporary M/C Power panel Front side Back side Location where a dead small animal (mouse) was found (on the power panel floor underneath the power panel where soot was found) Units 3-4 temporary M/C (A) power panels and their doors A small animal (mouse) found dead (Photo taken from above) Inspection Results of Units 3-4 Temporary M/C (A) Compared to Sound Condition Regular inspection Visual inspection (check for abnormalities, strange sound/smell from the outside of the power panel) is performed once a week during patrol. No problem was found at a visual inspection performed in the morning of March 18, 2013. Results of inspection of the inside of the power panels after the power supply facilities failure No problem was found with units other than 5A where short circuit occurred. Inside the power panel (5A) after short circuit occurred Sound condition of power panel (6A) Soot Trace of short circuit Photo 1: Inside the power panel after short circuit occurred Photo 2: Sound condition of power panel Cause of Phase Fault Occurred in Units 3-4 Temporary M/C (A) Back side of Units 3-4 temporary M/C (A) and the power panel doors Enlarged image of unit 5A [Site investigation results] - A trace of short circuit was found on the conductor in the back of Units 3-4 temporary M/C (A) (5A). Also, a dead small animal (mouse) with an electric mark was found on the floor of the same unit. - No trace of short circuit or foreign substance was found in other units in Units 3-4 temporary M/C (A) and the main line. Marks from fire damage Conductor 15cm 15cm Cable Approx. 25cm Dead small animal (mouse) A small animal (mouse, 25cm long) getting close to the conductor generated an arc leading to a phase fault which developed into a three-phase short circuit. Discoloration of Units 3-4 M/C (A) Circuit Breakers Vacuum valve Unit 5A Vacuum circuit breaker Discoloration Unit 5B Side view (Transparent view) Discoloration Traces of Short Circuit Found in Units 3-4 Temporary M/C (A) Traces of short circuit found near the terminal of unit 5A Side surface Terminal Top surface Traces of short circuit found on the top surface of unit 5A Traces of short circuit found on the side surface of unit 5A (Legend) Trace of short circuit Electric Mark Found on the Dead Small Animal A dead small animal (mouse (photo 1)) was found on the floor of Units 3-4 temporary M/C (A) unit 5A. An electric mark (photo 2) was found on its Mark from electric shock Photo 1: Dead small animal (mouse) found in unit 5A Photo 2: Enlarged image of the electric mark Condition of the Opening of Units 3-4 Temporary M/C Container Location where the cable is drawn in (Side surface of the container) The opening found in the location where the cable is drawn in has been closed with a sheet. The sheet is removed for inspection (which makes a large opening). Normally, the opening is closed with sheet. Feces of Small Animal Found in Units 3-4 Temporary M/C (A) Units 3-4 temporary M/C (A) Inspection opening of the container Dead small animal Side view (Transparent view) Substances which are assumed to be feces found in unit 5B - A small animal (mouse) may have gotten into the unit from the opening generated by sheet partially coming off. - Since the sheet was removed for investigation, trace of small animal (mouse), etc. could not be confirmed. - Substances which are assumed to be feces of the deal small animal (mouse) were found on the floor of Units 3-4 temporary M/C (A) unit 5B. - No abnormality was found with the appearance of the sheet, etc. at the time of inspection performed in the morning of March 18. Cause of the Power Supply Failure of Units 3-4 Temporary M/C (A) A small animal (mouse) got into Units 3-4 temporary M/C (A) Short circuit occurred due to the small animal (mouse) getting close to the current-carrying area Overcurrent was generated among the backup M/C in the Process Building, regular M/C in the Process Building and Units 3-4 temporary M/C (A) Since the same overcurrent value is set for the M/C circuit breakers above, the circuits were cut simultaneously and power supply failure occurred. Cooling systems for Unit 3 SFP, Unit 4 SFP and the common pool were suspended. M/Cs other than the above were affected by the potential changes accompanying the momentary stop of power supply, Unit 1 SFP alternative cooling system (secondary system) and nitrogen separator (B) were suspended. End