Data Sheet (English)

Transcription

Data Sheet (English)
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
■ A special software (function module)
for integration in PLC systems is not required.
■ Cable max. 50 m between interface and
read/write head
■ 2 decimal rotary coding switches for the
adjustment of the Profibus address
■ Maximum transmission rate to the fieldbus 12 Mbps
■ Sub-D female, 9-pin, for fieldbus connection
■ Screw terminals for voltage supply
■ LEDs for display of supply voltage,
group and bus errors as well as status
and diagnostics
TI-BL20-DPV1-S-4
1545075
4
85.1 x 128.9 x 74.4 mm
Rated voltage from the supply terminal
Supply voltage
System power supply
Field supply
Admissible range
Max. field supply current
Max. system supply current
24 VDC
24 VDC
24 VDC / 5 VDC
24 VDC
18…30 VDC
10
1.2
Fieldbus transmission rate
Fieldbus address range
Fieldbus addressing
Service Interface
Fieldbus connection technology
Voltage supply connection
Fieldbus termination
9.6 kbps … 12 Mbps
1...99
2 rotary switches
PS/2 socket
1 x female sub-D connector
screw terminals
external
Transmission rate
Cable length
Electrical isolation
115.2 kbps
50 m
isolation of electronics and field level via optocouplers
Connection technology
screw, tension spring
Sensor supply
0.25 A per channel, short-circuit proof
Number of diagnostics bytes
Number of diagnostics bytes
Number of parameter bytes
Number of parameter bytes
Number of input bytes
Number of output bytes
4
3
8
5
24
24
■ Connection of up to 4 read/write heads
via BL ident extension cables
■ Mixed operation of HF and UHF read/
write heads
Edition • 2016-11-03T07:20:49+01:00
Type designation
Ident no.
Number of channels
Dimensions (W x L x H)
1/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
Operating temperature
Storage temperature
Relative humidity
Vibration test
Shock test
Drop and topple
Electro-magnetic compatibility
Protection class
included in delivery
0…+55 °C
Field/System Supply
-25…+85 °C
5 to 95% (internal), Level RH-2, no condensation (at 45 °C storage)
acc. to EN 61131
acc. to IEC 68-2-27
acc. to IEC 68-2-31 and free fall to IEC
68-2-32
acc. to EN 50,082-2
IP20
2 x end brackets BL20-WEW-35/2-SW, 1 x
end plate BL20-ABPL
Functional principle
The BL ident® system can be installed in
many different ways.
Various fieldbus standards, such as
PROFIBUS-DP, EtherNet/IP, Ethernet Modbus TCP, EtherCAT, DeviceNet, CANopen and
PROFINET IO allow flexible integration.
BL ident® simple electronic modules
(BL20-2RFID-S, BL67-2RFID-S) can be integrated in existing control or host systems without function block, since standard input/output
process data is used for communication.
Programmable gateways with peripheral preprocessing function relieve the control system
and fieldbus level.
Edition • 2016-11-03T07:20:49+01:00
Preassembled sets (2, 4, 6 or 8-port), easily
mounted, available for all fieldbus networks.
2/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
Anschlussübersicht
Power Supply
The U system supply feeds power to the gateway and
the I/O modules.
The U field supply feeds power to the sensors and actuators.
SYS
L
Edition • 2016-11-03T07:20:49+01:00
PROFIBUS-DP
Fieldbus cable (example):
D9T451-2M (ident no. 6915759) or
RSSW-D9T451-2M (ident no. 6915779)
3/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
Compatible base modules
Type
Pin configuration
BL20-S4T-SBBS
6827046
Tension spring connection
…/S2500 Connectors
BL20-S4S-SBBS
6827047
Screw connection
…/S2501 Connectors
Edition • 2016-11-03T07:20:49+01:00
Connectors …/S2503
4/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
LED display
LED
D
Color
RED
RED
RW0 / RW1
FLASHING (0.5 Hz)
OFF
ON
FLASHING (2 Hz)
ON
FLASHING (2 Hz)
Meaning
Error report or diagnostics active.
Failure of MODBUS communication Check if more than 2
adjacent electronic modules are pulled. Relevant modules
are located between gateway and this module.
Upcoming module diagnostics
No tag, diagnostics disabled
Tag available
Data exchange with tag enabled
Read/write head fault
Short-circuit in the supply line of read/write head
Edition • 2016-11-03T07:20:49+01:00
GREEN
GREEN
RED
RED
Status
OFF
ON
5/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
I/O Data Mapping
Channel 0
Channel 1
OUTPUT
Channel 0
DONE
BUSY
Error Code
Error Code 1
Reserved
READ DATA (8 Byte)
ERROR
XCVR CON XCVR ON
TP
TFR
Reserved
DONE
BUSY
Error Code
Error Code 1
Reserved
READ DATA (8 Byte)
ERROR
XCVR CON XCVR ON
TP
TFR
Reserved
Bit 7
XCVR
Reserved
Bit 5
TAG ID
Bit 4
READ
Bit 3
WRITE
Bit 2
TAG INFO
Byte Count
2
Bit 1
XCVR INFO
Byte Count
1
Bit 0
RESET
Byte Count
0
m+2
m+3
m+4
m+5
…
m+10
m+11
m+12
m+13
Address high byte
Address low byte
WRITE DATA (8 Byte)
TAG ID
READ
WRITE
TAG INFO XCVR INFO RESET
Byte Count Byte Count Byte Count
2
1
0
m+14
m+15
m+16
m+17
…
m+22
m+23
Address high byte
Address low byte
WRITE DATA (8 Byte)
XCVR
Reserved
Bit 6
NEXT
NEXT
Edition • 2016-11-03T07:20:49+01:00
Channel 1
n
n+1
n+2
n+3
n+4
n+5
…
n+10
n+11
n+12
n+13
n+14
n+15
n+16
n+17
…
n+22
n+23
BYTE
m
m+1
6/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com
Set for simple I/O communication via PROFIBUS-DP in IP20
TI-BL20-DPV1-S-4
Accessories
Type code
Ident no.
Description
FW-D9TLEDKU9PGW-FC-ME-SH-8,5
6604220
PROFIBUS-DP field-wireable 9-pin Sub-D connector,
male/female, angled, insulation displacement contact,
metal housing, 12 Mbps, switchable terminating resistor
FW-D9TLEDKU9XX-G- 6604221
FC-ME-SH-8,5
PROFIBUS-DP field-wireable 9-pin Sub-D male,
straight, cutting clamp contact, metal housing, 12
Mbps, switchable terminating resistor
I/O-ASSISTANT-KABEL-BL20/BL67
RS232 service cable for Gateways with PS2 interface
6827133
Shield terminal and strain relief for bus cable
Edition • 2016-11-03T07:20:49+01:00
BS3511/KLBUE4-31.5 6827342
7/7
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com