Bulk Power Supply Specification
Transcription
Bulk Power Supply Specification
1 2 FF-831 FIELDBUS ISOLATED BULK POWER SUPPLY SPECIFICATION Auxiliary fieldbus equipment Isolated bulk power supplies intended for commonly bussed passive or active FF-641 fieldbus power conditioners. Power bus Isolated bulk power supply * 2 Wire Trunk 2 Wire Trunk * 2 Wire Trunk Redundant option Redundant I limit One, or more, FF-831current limited Power conditioner/s * OR diode 3 4 5 6 7 8 9 Attribute Value Output voltage Load regulation Line regulation Bulk power supply current limit (each) Nominal current per power conditioner Peak current per power conditioner 19.2-32 5 5 N/A 0.5 1.25 Tol. Units V % % A A A Note max max max N/A max max 4 4 10 11 Attribute Level mV p-p 12 13 Noise/ripple 50 Hz to 300 kHz Ripple Common mode noise and ripple Primary/secondary isolation Fitted with integral ‘OR’ diode 300mV 1V 50 Hz to 120 Hz 4 V rms 63 Hz to 2MHz IEC61131-2 Table 17 or equivalent NOT REQUIRED 14 15 16 Frequency Note Tol. Max Max Max 1 3 2 5 17 18 NOTES 19 The remaining specification as per manufacturers standard. 1 For switching power supplies. 2 Sine wave noise and ripple. 3 For linear 50/60 Hz power supplies. 4 Each power conditioner. 5 DO NOT GROUND OR EARTH THE BULK POWER SUPPLY OUTPUTS Pepperl+Fuchs GmbH, Mannheim Germany CAUTION If undetected, two simultaneous faults comprising one pole on one trunk to ground, and one pole on a second trunk to ground, may cause both trunks (or segments) to fail. All remaining segments will not be affected. SPECIFIACTION FORMULATED SPECIFICALLY FOR POWER CONDITIONER MODEL: HD2-FBCL-1.500