INCLUDED MATERIALS
2x2
A. (2) PC-Boards for 2x2 fixture
B. (3) 60702701 SCR-10-16x5/8 PHPD Self Drilling
C. (1) LED Driver
2x4
D. (4) PC-Boards for 2x4 fixture
E. (3) 60702701 SCR-10-16x5/8 PHPD Self Drilling
F. (1) LED Driver
MATERIALS REQUIRED
•
Wiring Nuts of Appropriate Size and Quantity
TOOLS REQUIRED
•
•
•
•
•
•
Tape Measure
Wire cutter / stripper
Personal safety equipment
Electric driver drill, standard jaw chuck,
for removal of old technology
1/4” hex nutdriver bit, for
removal of old technology
Electrical Static Discharge (ESD) Protection
FRANÇAIS - MISES EN GARDE ET SÉCURITÉ:
SE IL VOUS PLAÎT LIRE ATTENTIVEMENT!
•
ENGLISH - WARNINGS & SAFETY INFORMATION:
PLEASE READ CAREFULLY!
•
•
•
•
•
•
•
•
WARNING - Risk of fire or electric shock. Luminaire
wiring and electrical parts may be damaged
when drilling for installation of LED retrofit kit.
Check for enclosed wiring and components.
WARNING - Risk of fire or electric shock. LED Retrofit
Kit installation requires knowledge of luminaires
electrical systems. If not qualified, do not attempt
installation. Contact a qualified electrician.
WARNING - Risk of fire or electric shock. Install this kit only
in the luminaires that have the construction features and
dimensions shown in the photographs and/or drawings.
Only those open holes indicated in the photographs
and/or drawings may be made or altered as a result of
kit installation. Do not leave any other open holes in
an enclosure of wiring or electrical components.
WARNING - To prevent wiring damage or abrasion, do not
expose wiring to edges of sheet metal or other sharp objects.
WARNING - This product is sensitive to Electrical Static
Discharge (ESD). Care should be taken to avoid direct
contact with the LEDs. Installers should be grounded
using a wrist strap or other suitable method of
grounding. Failure to ground the installer may cause
pre-mature failures and void the fixture warranty.
Suitable for damp location fixtures.
THE RETROFIT KIT IS ACCEPTED AS A COMPONENT
OF A LUMINAIRE WHERE THE SUITABILITY OF THE
COMBINATION SHALL BE DETERMINED BY CSA
OR AUTHORITIES HAVING JURISDICTION.
•
•
•
•
•
•
•
AVERTISSEMENT - Risque d'incendie ou de choc
électrique. Câblage du luminaire et pièces électriques
peuvent être endommagés lors du perçage pour
l'installation du kit de conversion à DEL. Vérifier
le câblage et les composants intérieur.
AVERTISSEMENT - Risque d'incendie ou de choc électrique.
Installation du Kit d'adaptation DEL nécessite la connaissance
des systèmes électriques des luminaires. Si non qualifié, ne
essayez pas l'installation. Contactez un électricien qualifié.
AVERTISSEMENT - Risque d'incendie ou de choc
électrique. Installez ce kit dans les luminaires qui ont
les caractéristiques de construction et dimensions
indiquées dans les photographies et/ou dessins.
Seuls les trous ouverts indiqués dans les photographies et/
ou dessins peuvent être effectués ou modifiés à la suite de
l'installation du kit. Ne laissez pas d'autres trous ouverts dans
un ensemble de câblage ou de composants électriques.
AVERTISSEMENT - Pour éviter d'endommager le
câblage ou l'abrasion, ne pas exposer le câblage
aux bords ou d'autres objets pointus.
AVERTISSEMENT - Ce produit est sensible aux décharges
d'électricité statique (ES). Des précautions doivent être
prises pour éviter le contact direct avec les DEL. Les
installateurs doivent être mis à la terre en utilisant un
bracelet ou une autre méthode appropriée de mise à
la terre. Defaut de mécanisme à la terre le programme
d'installation peut provoquer des défaillances
prématurées et annuler la garantie du luminaire.
Convient pour l'emplacement luminaires humides.
LE KIT DE MODIFICATION EST ACCEPTÉ COMME UNE
COMPOSANTE D'UN LUMINAIRE OÙ LA PERTINENCE
DE LA COMBINAISON DOIT ÊTRE DÉTERMINÉE PAR
LA CSA OU LES AUTORITÉS AYANT JURIDICTION.
Page 1/4 - Revised 10/06/15
©2015 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change
specifications without notice. 701 Millenium Blvd. Greenville, SC 29607 / Tel 864-678-1000 / Website www.columbialighting.com
GORK
LED Retrofit Kit
Installation Instructions
INSTALLATION INSTRUCTIONS
1. Compatible with most 2-lamp and 4-lamp
fluorescent fixtures. Not compatible with
most 3-lamp fluorescent fixtures. To avoid the
possibility of electric shock, turn off power.
2. Open the troffer and remove existing lamps, lamp mounts,
ballasts / drivers, interconnection components. Remove but
DO NOT DISCARD BALLAST COVER and ballast screws.
(Fig. 1) Retain existing feed wires.
Fig. 1
3. Dispose of ballast and lamps in accordance
with environmental requirements.
4. Clean dirt and solvents from inside surface of housing.
5. Attach optional magnetic alignment tool to inside
surface of housing by aligning center slots over the
ballast mounting holes along the center of housing,
OR, if no alignment tool then use pre-existing
position of lamps as alignment position (Fig. 2).
Fig. 2
Optional magnetic alignment tool is
compatible with 2L or 4L fluorescent fixtures.
6. Align first set of LED boards: To secure, apply pressure
but DO NOT RUN FINGERS ALONG OR ACROSS
BOARD as this may damage the LED. (Fig. 3).
A. 2x4, 2x2: Align LED board to outside edge of alignment
tool,* with wiring terminals towards fixture end caps.
B. 2x4: Repeat step A. on the other half of the
luminaire. Align boards end-to-end.
*Keep alignment tool for subsequent retrofits.
*Test fit boards without removing thermal tape to
see if lamp sockets need to be removed. Also insure
boards do not overlap in the middle of fixture.
Fig. 3
Page 2/4 - Revised 10/06/15
©2015 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change
specifications without notice. 701 Millenium Blvd. Greenville, SC 29607 / Tel 864-678-1000 / Website www.columbialighting.com
GORK
LED Retrofit Kit
Installation Instructions
INSTALLATION INSTRUCTIONS
7. Install Driver using existing ballast holes and position (Fig. 4).
Fig. 4
Driver
8. Connect LED wiring harness(es) to LED driver.
Standard fixed output (not dimming):
Black, white and green wires provided. Black and white wires
are supplied with a snap-fit wiring harness to the LED driver.
Click = Connection is secure. Green ground wire is loose; green
ground screw provided in parts bag for securing to housing.
Optional 0-10V Dimming:
GORK will be shipped with capped grey/violet
dimming wires; connectors by others
Optional Step Dimming:
GORK will be supplied with two sets of hot leads; connector by others.
9. Connect ground, neutral and hot wires
(main power feed) (Fig. 5).
Ground screw
provided
Fig. 5
10.Reinstall ballast cover through end wireways. Ensure wires
are not pinched along length of ballast cover (Fig. 6).
Fig. 6
Page 3/4 - Revised 10/06/15
©2015 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change
specifications without notice. 701 Millenium Blvd. Greenville, SC 29607 / Tel 864-678-1000 / Website www.columbialighting.com
GORK
LED Retrofit Kit
Installation Instructions
INSTALLATION INSTRUCTIONS
11.Carefully check that all mechanical and
electrical connections are within code (Fig. 7).
Fig. 7
Looking up into troffer from below
12.Installation complete. Reinstall shielding. Apply power to the fixture.
DIMENSIONS
Board Depth .125"
Board Width 1"
2"
th 2
B
ng
d Le
oar
4"
th 2
eng
es L
Wir
LED
ASSEMBLY
DRIVER
*Measurements
approximate
and drawings
are not to scale.
Page 4/4 - Revised 10/06/15
©2015 Columbia Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Columbia Lighting reserves the right to change
specifications without notice. 701 Millenium Blvd. Greenville, SC 29607 / Tel 864-678-1000 / Website www.columbialighting.com

Documents pareils

SLK Installation Guide

SLK Installation Guide wiring and electrical parts may be damaged when drilling for installation of LED retrofit kit. Check for enclosed wiring and components. WARNING - Risk of fire or electric shock. LED Retrofit Kit i...

Plus en détail