Process field transmitter with local indicator 4

Transcription

Process field transmitter with local indicator 4
Process field transmitter with local indicator
4-20mA loop powered
type: INP101
• Loop powered (isolated 4-20mA)
INP101V on
thermowell
INP101 on
thermowell
INP101i
inox version
• Local display: 10000 points
• Outside mounting
IP67 protection
• Explosion-proof protection
IECEx and ATEX
• INP101V: radial display version
INP101V
vertical
mounting
• INP101 i: 316 Stainless Steel version
• HART protocol
INP101V
horizontal
mounting
INP101
(available option on all models)
• FDT DTM certified HART drivers
• SIL2 compliance
according to IEC 61508
The INP 101 is a loop powered field indicator-transmitter. It includes in a single case, protected against harsh
conditions (IP67), a programmable converter ( loop powered CNL40IG ) and a 4-digit display.
FUNCTIONALITY :
Temperature measure and process:
- Thermocouples / platinum RTD probes
- Voltage (mV), current (mA) on external shunt.
Functional safety data:
- SIL 2 : f = 457 fit , SFF = 95.4 % , DC = 91.8 %
type B component, HFT = 0
Synoptic
Signal processing:
- square root extraction (on process measures)
- programmable sensor breaking safety value,
- programmable response time from 0.2 to 60 sec,
(measure filtering function)
- reverse or standard output,
- measure offset adjustment,
- neutralization of thermal ambient variation effects
Display :
- LCD liquid crystal display (STN), wide temperature (4 digits),
- 10000 points resolution (physical unit display).
Configuration:
- Configuration by RS232 serial link (all models)
(USB cable supplied separately)
- Communication and configuration online
with standard HART programming handheld terminal
Performance / Environment
- Long-term stability 0.1 %/year.
- Resistant, protected against collisions and vibrations
(silicon coating resin)
Realization, mounting and connection
- Pyrometric thermo well or pipe support mounting (default)
- Protection against reverse polarity
- input/output insulation
(elimination of measure errors due to ground loop)
- IP67 protection
Version and order code :
INP 101 : Aluminium box, epoxy coating, IP67, display side view
INP101V : Aluminium box, epoxy coating, IP67,
(the mounting must be define : Horizontal or Vertical)
option
/H :
HART communication
/ADF : ATEX or IECEX explosion-proof protection
/i :
316 Stainless Steel case (IP 68)
/SIL2 : SIL2 compliant model according to IEC 61508
(All options are combinable)
For a direct mounting on pyrometer probe (consult us)
OUTDOOR TRANSMITTER
E1
90 days accuracy (20 °C +/- 2 °C) DATA SHEET CAN BE DOWNLOADED ON WWW.LOREME.FR
INPUT (24bits resolution)
POWER SUPPLY / OUTPUT (14 bit resolution )
TYPE
RANGE
ACCURACY
Tc B
Tc E
Tc J
Tc K
Tc R
Tc S
Tc T
T° Compensation
200 / 1800 °C
-250 / 1000 °C
-200 / 600 °C
-200 / 1350 °C
0 / 1750 °C
0 / 1600 °C
-250 / 400 °C
-20 to 60 °C
±
±
±
±
±
±
±
±
TYPE
RANGE
ACCURACY
13 to 40Vdc (loop powered)
Current
4 / 20 mA
± 0.01 mA
Load resistance to 24Vdc 550 Ohms
Effect of supply voltage change
0.002 % / V
Effect of load stability
0.004 % / 100 Ohms
2 °C
0.4 °C
0.4 °C
0.4 °C
1 °C
1.5°C
0.5 °C
0.3 °C
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
PT100 2, 3 wires:
± 0.3 °C
RTD measure range
-200 / 800°C
Voltage
0 / 120 mV
Current
0 / 30 mA
(external shunt of 2.5 ohms)
± 0,02 mV
± 0,025 mA
Response time
Sampling rate
~ 200msec
6 per sec.
Input impedance
Sensor current (Pt100)
resistance line influence
> 1 MOhms
300 µA
0.3°C / 10ohms
Minimum current consumption
Security current
<3.6 mA
3.6 ... 22mA
Insulation voltage
Input / Output
TECHNICAL SPECIFICATIONS
ZONE DE
FONCTIONNEMENT
4
8
12
16
20
24
28
32
36
40
ENVIRONMENT
Operating temperature
Storage temperature
Influence (% of full scale)
Weight
MTBF (IEC 62380)
Life time
Electromagnetic compatibility
Generic standards: EN 61000-6-4 / EN 61000-6-2
EN55011
EN61000-4-2
EN61000-4-4
EN61000-4-5
EN61000-4-8
EN61000-4-11
1000 Vrms
continuous
-20 to 60 °C
-20 to +85 °C
< 0.01 % / °C
1,4 Kg (without fastening)
> 2 180 000 Hrs @ 30°C
> 250 000 Hrs @ 30°C
meet
no influence
< +/- 5 %
< +/- 5 %
no influence
< +/- 5 %
group 1 / class A
B EN61000-4-3 < +/- 5 %
B EN61000-4-6 < +/- 5 %
B
A
EMC
2004/108/CE
B
DBT
2006/95/CE
WIRING AND OUTLINE DIMENSIONS:
118
Tête ADF / Explosion-proof Head XD-ADwin
Alliage d'aluminium / Aluminium Alloy
( EN AC-AISi9Cu3 ) - IP 68
Revêtement Epoxy /
Epoxy coating
Presse Etoupe ADF
Laiton Nickele / Brass
Explosion-proof
Cable Gland
M20 ADE1F N°4
pour câble / for cable
Ø 4 à 8.5 mm
Vitre / Glass
130
Afficheur / Display
Borne de masse /
EarthTerminal
13.5
41
17
Passage calibré /
Metering hole
Ø 6.1 H8
Convertisseur
tete de sonde
montage antivibratoire /
In Head Transmitter
antivibratory mounting
Raccord Inox 316L /
316L Ss. Connection
1/2"Gcyl (BSPP)
Soudure TIG / TIG Weld
Raccord Coulissant Inox 316L /
316L Ss. Sliding Connection
Ø 8 mm - 1/2"Gcyl (BSPP)
Raccordement
Internal wiring interne
1 2 3 4 5
1 2
Tube Inox 316L /
316L Ss. Pipe
Ø 8x1 mm
Pt100 Chips
Classe B Selon CEI 751 /
Class B According to IEC 751
E2
1 2 3 4 5
+ -
+
-
Pwr
+24 Vdc
3 4 5
RTD
-
Tc
+
LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: [email protected] - [email protected]
On account of the constant technologies and standards evolution, LOREME keeps the possibility to modify the specifications of the included products without notice.
A
A

Documents pareils

liste provisoire des participants / temporary list of

liste provisoire des participants / temporary list of Sagem is a high-tech company in the SAFRAN Group. It is a world or European leader in solutions and services in optronics, avionics, electronics

Plus en détail