Humidity Sensor Capteur d`humidité Sensor de humedad

Transcription

Humidity Sensor Capteur d`humidité Sensor de humedad
Humidity Sensor
Capteur d'humidité
Sensor de humedad
C-7241
Technical Characteristics
Humidity Range............................. 0... 100% relative humidity
Temperature Range ...................... 0... 60 ºC
Impedance <75% HR .................... < 20 k
Impedance <93% HR .................... < 100 k
Impedance >97% HR .................... > 150 k
Interdigital structure ...................... Switch conductance, approx. 10 S
Maximum voltage evaluation …..... <0,8 Vpp ~/= Conductance < 2 Vpp ~
Contacts ........................................ 3 SIL contacts, step 2,54 mm, l = 20 mm
It is a resistive sensor combined with an interdigital structure (conductivity sensor) designed to detect the appearance of
condensation water sensing or condensed liquid state.
The characteristic of the exponential increase of the resistance in the upper region of the humidity, facilitates the processing of
signals simple and stable in the switching threshold of dew formation behavior.
The back side of the ceramic substrate can make thermal contact to pick up moisture from the surface to be controlled.
Il s'agit d'un capteur résistif associé à une structure interdigitale (capteur de conductivité) conçu pour détecter l'apparition de
condensation d'eau ou de détection de l'état ​liquide condensé.
La particularité de l'augmentation exponentielle de la résistance dans la région supérieure de l'humidité facilite le traitement de
signal simple et stable dans le seuil de commutation du comportement de la formation de rosée.
La face arrière du substrat en céramique puisse entrer en contact thermique pour absorber l'humidité de la surface à contrôler.
Es un sensor resistivo combinado con una estructura interdigital (sensor de conductividad) diseñado para detectar la aparición de
condensación con detección de agua en estado líquido o condensado.
La característica del aumento exponencial de la resistencia en la región superior de la humedad, facilita el procesamiento de
señales simples y un comportamiento estable en la conmutación del umbral de la formación de rocío.
El lado posterior del sustrato de cerámica puede realizar el contacto térmico para captar la humedad de la superficie a controlar.
Characteristics
• Detection of high humidity, dew formation or condensation.
• interdigital structure independent detection of water
• application range of 0% to 100% RH, 0 to 60 ° C
• With SIL PCB terminals
• Détection d'une forte humidité, la formation de rosée ou de condensation.
• structure interdigitale détection indépendante de l'eau
• intervalle d'application de 0% à 100% d'humidité relative, de 0 à 60 ° C
• Avec bornes pour circuits imprimés SIL
• Detección de humedad elevada, de formación de rocío o de condensación.
• Estructura interdigital para detección independiente de agua
• Rango de aplicación de 0%a 100%HR, 0 a 60 °C
• Con terminales SIL para circuito impreso
www.cebek.com
-
[email protected]
C-7241
Applications
• Instrumentation for construction, drivers chilled ceilings, air conditioning
• Protection against moisture in electrical switchgear panels
• Monitoring of roofs
• Detection of condensation on the outside of the walls
• Control of ventilation in rooms of hospitals, nursing homes, etc..
• Check for leakage in sealed boxes
• Instrumentation pour la construction, les conducteurs refroidi plafonds, climatisation
• Protection contre l'humidité dans les panneaux d'appareillage électrique
• Suivi des toits
• Détection de la condensation sur la face extérieure des murs
• Contrôle de la ventilation dans les chambres d'hôpitaux, maisons de soins infirmiers, etc.
• Vérifier les fuites dans des boîtes scellées
• Instrumentación para la construcción, controladores de techos fríos, aire acondicionado
• Protección contra la humedad en los paneles de aparellaje eléctrico
• Monitorización de azoteas
• Detección de condensación en la parte exterior de las paredes
• Control de ventilación en habitaciones de hospitales, residencias, etc.
• Control de fugas en cajas estancas
Pin Connections
1 COM Common connection of resistive sensor
2 Optional SEN1 Switch conductance
3 SEN2 resistive sensor element
1 COM connexion commun de capteur résistif
2 Facultatif SEN1 commutateur conductance
3 SEN2 élément capteur résistif
1 COM Conexión común del sensor resistivo
2 SEN1 Conmutador opcional de la conductancia
3 SEN2 Elemento sensor resistivo
www.cebek.com
-
[email protected]