ASCO Model 142 Installation Manual

Transcription

ASCO Model 142 Installation Manual
Series 100
Model 142 (Edco SRA64 Series)
1 Pair Data/Signal
Surge Protective Device
Technical Documentation
The ASCO Model 142 surge suppressor is a single pair
cube implementing three-stage hybrid technology. This
cube addresses over voltage transients with gas tubes and
silicon avalanche components. In addition, sneak and fault
currents are mitigated with resettable fuses (PTCs). The PTCs
increase resistance several orders of magnitude when overcurrents exceed safe levels. A normal state resumes when
over-currents are removed. The ability to self restore in this
manner significantly increases suppressor performance and
survivability.
The standard Model 142 second stage clamps are placed from each signal line-to
ground. In certain cases, where ground potentials vary from site-to-site, a line-toline only second stage clamp may be preferred. This variation uses an “X” in position
12 of the model number. In other cases, line-to-line and line-to-ground second stage
clamps may be preferred. This variation uses an “X” in position 12 of the part number.
A variety of clamping voltages are available as standard. Reference the “Ordering
Information” section to insure that a complete part number and description is
obtained.
Operating Voltage
5, 12, 24, 30, 36, 52, or 120 VDC
Clamping Voltage
8, 15, 30, 36, 43, 60, or 150 VDC
Operating Current
0.15 A
10 kA (8 x 20 μs)
SPD Technology
GDT, SAD, w/ Series PTC
Response Time
< 1 nanosecond
Resistance
5Ω (typical)
Operating Temperature
-40°C to+85°C
Dimensions (in / mm)
1.15˝ [29.2 mm] Cube
Weight (oz / kg)
2 oz [.06 kg]
Mounting Stud (standard)
• Voltage: 0-120 VDC
• Current: 150 mA
• Connection: Wire Leads
(provided) and 10-32 Ground Stud
• Mounting: 10-32 x 1/2”
Ground Stud
*See Ordering Information for model number selection
Features
• Lightning protection for balanced
low voltage signal lines
• Three stage hybrid protection
General Technical Specifications
Peak Surge Current
Key Specs
No.10-32 x 1/2˝ [12.7 mm]
Warranty
5 years
Caution
Do not place this product in service on any signal line capable of continuously supplying more than 150 mA.
Attention
Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en permanence plus de 150 mA.
V DANGER!
Only qualified personnel should install or service this system. Electrical safety pre-cautions must be followed
when installing or servicing this equipment. To prevent risk of electrical shock, turn off and lock out all power
sources to the unit before making electrical connections or servicing.
Seulement le personnel qualifié doit installer ou maintenir ce systéme. Des précautions de sécurité en électricité
doivent être suivis lors de l’installation ou de la maintenance de cet equipement. Pour eviter tout risque de choc
électrique, débranchez et verouiller toutes les sources d’alimentation de cet equipement avant de.
• Sneak/fault current protection
• Differential and common mode
protection
• Automatic recovery
• Fast response time
• Flame retardant epoxy
encapsulated
• 5 year warranty
Wiring Assignments
UNPROTECTED
PROTECTED
Black
White
FIELD SIDE
ELECTRONICS SIDE
(Outside Plant)
(Equipment)
Black/Red
White/Red
Ordering Information
MODEL
Former Model Name
OPERATING
VOLTAGE
CLAMPING
VOLTAGE
142D008S10KAG4N0
5 VDC
8 VDC
142D015S10KAG4N0
12 VDC
15 VDC
142D030S10KAG4N0
24 VDC
30 VDC
142D036S10KAG4N0
30 VDC
36 VDC
142D043S10KAG4N0
36 VDC
43 VDC
142D060S10KAG4N0
52 VDC
60 VDC
142D150S10KAG4N0
120 VDC
*150 VDC
Edco SRA64C-008
Edco SRA64C-015
Edco SRA64C-030
Edco SRA64C-036
Edco SRA64C-043
Edco SRA64C-060
Edco SRA64C-150
NOTE: Each Signal Line-to-Ground Protection (Standard)
*Not UL Listed
For Line-to-Line Protection only, use a “D” in the 12th position of the model
number.
For Line-to-Ground and Line-to-Line Protection, use a “X” in the 12th position of the model number.
14550 58th Street North
Clearwater, Florida 33760
P (800) 237-4567
P (727) 535-6339
F (727) 539-8955
E [email protected]
While every precaution has been taken to ensure accuracy and completeness herein, ASCO Power Technologies assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for
any errors or omissions. Specifications are subject to change without notice.
ID-50125 Rev- 07-16