LCD-6000
Installation manual
NOTIFIER ITALIA
a Pittway Company
INDEX
FRONT PANEL
1
LEDs
1
KEYPAD
2
CABINET DIMENSIONS
4
BOARD LAYOUT
5
LCD-6000 PROGRAMMING
6
SW1 DIP SWITCH
6
SW2 DIP SWITCH
6
"CN0" CONNECTOR ON LCD-6000
7
POWER SUPPLY SPECIFICATIONS
8
» NOTE: this LCD-6000 is enabled to operate on AM-6000 control panels with EPROM version
dated 20/05/97 or next.
Eng-ndx.VP
Doc. M-181.1-LCD6000-ENG
Installation manual
Rev. B.1
NOTIFIER ITALIA
FRONT PANEL
GENERAL
ALARM
LED
LIST
ACKNOWLEDGE
SIGNAL SILENCE
GENERAL
SIGNAL SILENCE
TROUBLE
LED
RESET
LAMP TEST
LED
LEDs
The general alarm led (Red) is:
•
•
•
BLINKING when the control panel detects one or more alarms
STEADY ON when the alarm condition has been acknowledged by pressing the ACK key
TURNED OFF when no alarm events exist
The general trouble led is:
•
•
•
BLINKING when on the control panel the following failures are detected:
OFF LINE (LCD6000 OFF line). This message appears on the display.
ZONE TROUBLES
SYSTEM TROUBLES
STEADY ON when the trouble condition has been acknowledged by pressing the ACK key
TURNED OFF when no trouble events exist
The signal silence led turns on if in alarm condition the signal silence key is pressed.
LCD6000-MANU-ist.VP
Doc. M-181.1-LCD6000-ENG
Installation manual
Rev. B.1
Page 1
NOTIFIER ITALIA
KEYPAD
The RESET key allows to clear the alarm events if previously they have been acknowledged by
pressing the ACK key.
Note 1 *
The ACK key allows to perform the Trouble and Alarm acknowledge and the buzzer silence.
Note 1 *
The SIGNAL SILENCE key allows to deactivate the controls activated after an alarm event.
» NOTE. : The controls must be programmed as silenceable.
Note 1*: No password is required to perform this function.
The LAMP TEST key allows to perform a test of LEDs. The test will illuminate the LCD-6000 LEDs
for a timed period and the display backlite.
The LIST key, in case of alarm or trouble events, allows to display the list of the single points in
alarm or trouble condition.
Procedure to display the Event list during a SYTSTEM TROUBLE condition only
SYSTEM
TROUBLE
NOTE: you can leave this menu only
for time out, after 60 seconds.
Press once the
LIST key
Select an event list:
TO SELECT
1 = ZONE ALARMS
2 = ZONE TROUBLES
>
3 = SYSTEM TROUBLES
TO CONFIRM
4 = ZONES EXCLUDED
5 = POINTS EXCLUDED
3= SYSTEM TROUBLES
The 1
st
and the last trouble
are displayed
Page 2
NOTIFIER ITALIA
Press the down cursor key to
Press
scroll the trouble list
the LIST key
Installation manual
Rev. B.1
LCD6000-MANU-ist.VP
Doc. M-181.1-LCD6000-ENG
Procedure to display the Event list during an ALARM/TROUBLE condition
ZONE 1 ALARM
ZONE 20 ALARM
Press once
the LIST key
Display the
ZONE 1 points
NOTE: you can leave this menu only
Press the down cursor key
to
scroll
the
list
of
Press the
the
points in alarm condition.
for time out, after 60 seconds.
LIST key
Select an event list:
>
TO SELECT
1 = ZONE ALARMS
2 = ZONE TROUBLES
TO CONFIRM
3 = SYSTEM TROUBLES
4 = ZONES EXCLUDED
5 = POINTS EXCLUDED
1 = ZONE ALARMS
st
1
ZONE ALARM
LAST ZONE ALARM
Use the cursor key
to select the zone
Press the LIST key to display
the points in alarm condition of
the zone selected.
Press the down cursor key
Press the LIST key
to scroll the list of the points
to escape
in alarm condition.
LCD6000-MANU-ist.VP
Doc. M-181.1-LCD6000-ENG
Installation manual
Rev. B.1
Page 3
NOTIFIER ITALIA
CABINET DIMENSIONS
Page 4
NOTIFIER ITALIA
Installation manual
Rev. B.1
LCD6000-MANU-ist.VP
Doc. M-181.1-LCD6000-ENG
BOARD LAYOUT
LCD6000-MANU-ist.VP
Doc. M-181.1-LCD6000-ENG
Installation manual
Rev. B.1
Page 5
NOTIFIER ITALIA
LCD-6000 PROGRAMMING
“SW1” DIP SWITCH
TERMINAL Nr.
DENOMINATION
USE
1
NOT USED
2
NOT USED
3
NOT USED
4
NOT USED
5
NOT USED
6
IT MUST BE in “ON” position on the last LCD-6000*
7
IT MUST BE in “OFF” position
8
NOT USED
» NOTE: * ON= last device / OFF= intermediate device.
The “LAST DEVICE” is the one connected on the return lines towards the control panel, this
means, those lines directly wired to the terminals 11 and 12 of control panel CN0 connector.
“SW2” DIP SWITCH
TERMINAL Nr.
DENOMINATION
USE
1
NOT USED
2
In “ON” position, the buzzer activate each time an event occurs
3
In “ON” position it enables the RESET key
4
In “ON” position it enables the ACKNOWLEDGE key
5
In “ON” position it enables the SIGNAL SILENCE key
6
OFF= AM6000 serial protocol
7
NOT USED
8
NOT USED
Page 6
NOTIFIER ITALIA
Installation manual
Rev. B.1
LCD6000-MANU-ist-1.VP
Doc. M-181.1-LCD6000-ENG
CN0 CONNECTOR on LCD-6000
TERMINAL
DENOMINATION
NOTE
USE
CABLE COLOUR/NR.
Nr.
1
GROUND
2
NOT USED
3
NOT USED
4
NOT USED
5
NOT USED
6
NOT USED
7
GND
8
LIN + A (OUT)
RS 422 towards the control panel or the next terminal
9
LIN - A (OUT)
RS 422 towards the control panel or the next terminal
10
GND
11
LIN + R (IN)
RS 422 from the control panel or the previous terminal
12
LIN - R (IN)
RS 422 from the control panel or the previous terminal
13
+ 24 V
Positive Power Supply
14
+ 24 V
Positive Power Supply
15
GND
Negative Power Supply
16
GND
Negative Power Supply
Example of LCD-6000 panel connected to the AM-6000 control panel
SHIELDED CABLE
2
AWG 16 (1,31 mm )
MAX LENGHT 1800 m.
NR. OF LCD-6000 CONNECTABLE: 32 MAX
CN0
LCD-6000
AM6000 CONTROL PANEL
“BE600A” BOARD
NOTE: Setting of LCD-6000
SW 1 - DIP 6 = OFF
» NOTE: the power supply wiring is not indicated. If local power supplies are used, the negative line
must be common between the control panel and the LCD-6000.
LCD6000-MANU-ist-1.VP
Doc. M-181.1-LCD6000-ENG
Installation manual
Rev. B.1
Page 7
NOTIFIER ITALIA
Example of LCD-6000 panel connected to the AM-2000 control panel
SHIELDED CABLE
2
AWG 16 (1,31 mm )
MAX LENGHT 1800 m.
LCD-6000
CN1
AM2000 CONTROL PANEL
N.B.: Setting of LCD-6000
SW 1 - DIP 6 = OFF
the terminal emulation software must be programmed with communication speed equals
» NOTE:
to 2400 BAUD
Example of LCD-6000 panels connected in series
1
TO THE
LCD-6000
st
SW1 - DIP 6 = OFF
CONTROL PANEL
2
LCD-6000
nd
SW1 - DIP 6 = OFF
LAST
LCD-6000
SW1 - DIP 6 = ON
SHIELDED CABLE
2
AWG 16 (1,31 mm )
MAX LENGHT 1800 m
POWER SUPPLY SPECIFICATIONS
•
•
•
Power Supply: 15 to 30 VDC
Max current absorption: 180 mA @ 27,6 V
Stand-by current absorption: 80 mA @ 27,6 V
Page 8
NOTIFIER ITALIA
Installation manual
Rev. B.1
LCD6000-MANU-ist-1.VP
Doc. M-181.1-LCD6000-ENG
Document:
M-181.1-LCD6000-ENG
Issue:
06/1999
Rev. :
B.1
All rights reserved.
All specifications are subject to change without notice.
Delivery times depend on product availability.
NOTIFIER ITALIA S.r.l.
Via Grandi, 22 - 20097 San Donato Milanese (MI)
Tel. : 02/51897.1 (ISDN)
Fax : 02/5189730
http://www.notifier.it