Application Note 51297
WARNING—DANGER OF DEATH OR PERSONAL INJURY
WARNING—FOLLOW INSTRUCTIONS
Read this entire manual and all other publications pertaining to the work to be performed
before installing, operating, or servicing this equipment. Practice all plant and safety
instructions and precautions. Failure to follow instructions can cause personal injury and/or
property damage.
WARNING—OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify
that you have the latest revision, be sure to check the Woodward website:
www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The
latest version of most publications is available at:
www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get
the latest copy.
WARNING—OVERSPEED PROTECTION
The engine, turbine, or other type of prime mover should be equipped with an overspeed
shutdown device to protect against runaway or damage to the prime mover with possible
personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover control
system. An overtemperature or overpressure shutdown device may also be needed for
safety, as appropriate.
WARNING—PROPER USE
Any unauthorized modifications to or use of this equipment outside its specified
mechanical, electrical, or other operating limits may cause personal injury and/or property
damage, including damage to the equipment. Any such unauthorized modifications: (i)
constitute "misuse" and/or "negligence" within the meaning of the product warranty
thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product
certifications or listings.
CAUTION—POSSIBLE DAMAGE TO EQUIPMENT OR PROPERTY
CAUTION—BATTERY CHARGING
To prevent damage to a control system that uses an alternator or battery-charging device,
make sure the charging device is turned off before disconnecting the battery from the system.
CAUTION—ELECTROSTATIC DISCHARGE
Electronic controls contain static-sensitive parts. Observe the following precautions to
prevent damage to these parts.
•
Discharge body static before handling the control (with power to the control turned off,
contact a grounded surface and maintain contact while handling the control).
•
Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit
boards.
•
Do not touch the components or conductors on a printed circuit board with your hands
or with conductive devices.
•
IMPORTANT DEFINITIONS
A WARNING indicates a potentially hazardous situation which, if not avoided, could result in
•
A CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
•
A NOTE provides other helpful information that does not fall under the warning or caution
death or serious injury.
damage to equipment or property.
categories.
Woodward Governor Company reserves the right to update any portion of this publication at any time.
Information provided by Woodward Governor Company is believed to be correct and reliable. However, no
responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken.
© Woodward 2007
All Rights Reserved
Application Note 51297
Service Pack for MicroNet Plus RTN Module
Service Pack Installation Instructions
for MicroNet™ Plus RTN Module
The Install Service Pack command enables the user to install an update to the
footprint on a control.
Service Pack installations are not allowed if an application is currently running on
the control.
This Process is for one RTN module at a time. If your system has multiple RTN
modules, please repeat this process for all module.
1.
2.
3.
4.
Connect to the MicroNet™ Plus control via AppManager and stop all
running applications.
Set the computer that will be connected/communicating to the RTN modules
to a fixed IP address of 172.16.100.2 and a sub-mask of 255.255.0.0.
Remove the RTN module from the chassis.
Remove the RJ45 (Ethernet) plug from port 1 of the RTN module (see
Figure 1).
Figure 1. Remote RTN Module
Woodward
1
Service Pack for MicroNet Plus RTN Module
5.
Application Note 51297
Note the switch settings on the RTN module, so you can set them back to
their original positions after the Service Pack is installed. Set the module
configuration switches to the CPU, Main Chassis configuration (see
Figure 2).
Figure 2. RTN Module Switch Settings
6.
Install the RTN module into the chassis.
7.
Plug in an Ethernet cable to Ethernet port 1 of the RTN module, and plug
the other end of the Ethernet cable into the computer that was set with the
fixed IP address (from step 2). Start AppManager.
8.
Once the RTN module has booted, it will appear on the AppManager
controls list. Highlight the RTN module.
NOTE
The RTN module will have IP address 172.16.100.1.
9.
Select the Install Service Pack command, and a dialog box will be displayed
asking the user to select the Service Pack filename.
10. Press Open to start the installation. The file will be copied to the control and
executed. Status information will be shown in the Status Message Window.
11. When the Service Pack has been successfully installed, the user will be
prompted to reboot the control. Select the Yes button. If there were any
errors during the Service Pack installation, they will be displayed in the
Status Message Display Window.
2
Woodward
Application Note 51297
Service Pack for MicroNet Plus RTN Module
12. Once the RTN module has booted properly, it will appear on the
AppManager controls list. Double click on the control to view the controls
information. Verify that the Foot Print shows the correct footprint number
and revision:
•
5503-335, 5503-336 will show 5418-2408 C
•
5466-1035, 5466-1036, 5466-1037 will show 5418-2566 B
13. Unplug the Ethernet cable from Ethernet port 1 of the RTN module. Reinstall
the Ethernet port 1 plug back into the RTN module.
14. Remove the RTN from the chassis and set the module configuration
switches back to the original configuration (see Figure 2).
15. Install the RTN module into the chassis and verify that all cables are
returned to original location.
Woodward
3
We appreciate your comments about the content of our publications.
Send comments to: [email protected]
Please include the manual number from the front cover of this publication.
PO Box 1519, Fort Collins CO 80522-1519, USA
1000 East Drake Road, Fort Collins CO 80525, USA
Phone +1 (970) 482-5811 • Fax +1 (970) 498-3058
Email and Website—www.woodward.com
Woodward has company-owned plants, subsidiaries, and branches,
as well as authorized distributors and other authorized service and sales facilities throughout the world.
Complete address / phone / fax / email information for all locations is available on our website.
2007/1/Fort Collins