comfort becomes a reality

Transcription

comfort becomes a reality
comfort
becomes a reality
Inside
the false ceiling
COADIS
FALSE CEILING
Installation
comfort
COADIS Cassette is an independant terminal air
conditionning unit installed in suspended ceiling
which combines the installation and operating
advantages of central hot/chilled water
production with individual temperature controls
in each room.
c The entire air diffusion system is included
in the intake/outlet panel, with no additional
ducts or grilles.
c To optimise air diffusion, we use nozzles
with a high induction coefficient, causing
the ambient air to be drawn along by the supply
air. This enables the air stream to stick to
the ceiling by the “COANDA effect”.
c This unit is designed for offices until 3 large
frames (3x1,35 for ex.) and 6 m long maxi.
c COADIS Cassette inside the false ceiling instead
of panel (standard 600x600, or 600x1200).
c Easy installation: only four threaded rods
with resilient mounts.
c Hydraulic connections and condensate
evacuation by gravity (without water pump)
become easier according to the pipes installation
in the false ceiling of the corridor which
is generally lower high than in the office room.
Discreet
integration
occupancy volume
office 1
office 2
Hydraulical
piping
TOP VIEW
News, the ciat group possesses
expertise which makes it
a reference in each of its activities
World wide, it means that to be close to our markets with relevant products
reflecting end user expectations, the group has eight production plants, and a
sales & marketing networks in over 60 countries.
Production plants in the world
CRISTOPIA - FRANCE CIAT CHINASIA - CHINE CIAT INDIA - INDE
SIÈGE SOCIAL CIAT
CULOZ - FRANCE
CIAT BELLEY
FRANCE
CIAT CHAUTAGNE
FRANCE
CIAT participates in the certification
programmes, always keeping in mind
the quality and above board factors,
in order to guarantee:
c the validity of its technical
charateristics,
c a common comparison basis on
the products through the Eurovent
directory.
CIATESA - ESPAGNE
HYDRONIC - FRANCE
CIAT is in conformity with the CE marking,
authorizing a free circulation of its units
in all of the European Union territory.
This marking is a safety and protection
for all end users.
Département Unités Terminales
Export Department
Avenue Jean Falconnier
B.P. 14
01350 Culoz
France
Tél. : 04 79 42 42 70
Fax : 04 79 42 42 14
[email protected]
www.ciat.com
Avenue Jean Falconnier
B.P. 14
01350 Culoz
France
Tél. : 33 4 79 42 42 20
Fax : 33 4 79 42 42 12
[email protected]
www.ciat.com
Insign : 04 76 84 29 29 - 0403033
Do not hesitate to contact us,
a team of experts is at your disposal
NA 03-39 A
With Coadis, the
global
“COanda Air DIStribution”
Mastery of an exclusive air diffusion system
“All in one” according to the “Coanda Effect”
Visual comfort
Guarantee a result:
global satisfaction...
c the final user by optional air diffusion
with the guarantee of global comfort
c the architect by discreet integration inside
the false ceiling
c the design office by the proposal
of an innovating solution
c the building hirer by orientating air jet diffusion
c the installer by a complete integral “All in one”
air diffusion system for a low cost installation
c the property developer by real economies:
easy maintenance, low consumption…
ATARI - INFOGRAMMES HEAD OFFICE - LYON - FRANCE
exclusive
air diffusion
system for
unequalled comfort
Respect
Directional
for global design
air diffusion
6M
CLÉ DE RÉGLAGE
4M
The perfect air diffusion
by “Coanda effect“
c By orienting the diffusion outlets
appropriately we can reduce the
longitudinal and increase the lateral
range, ensuring comfort in shorter
rooms.
c An aesthetic key to precisely fix
nozzles position.
c You can set the air stream in any
direction, which means you can
even install the COADIS in a corner
of the office ceiling and still have
optimal air diffusion.
GURANTEE A RESULT
▲
▲▲
▲
▲▲▲
CEILING
COANDA EFFECT
c The COADIS Centrifugal fan pump the air
flow through a punched aluminium air grille.
After filtration the air flow is cooled (or heated)
through a coil. The air flow follows the ceiling
with Coanda effect. The COADIS Cassette uses
high induction nozzles.
c Coanda effect enables the air stream to adhere
perfectly to the ceiling thus avoiding “cold
dumping”. This virtual “casing” avoids
uncomfortable sensation due to the cool
air flow in the room, then the asymetrical
radiance is minimised near windows.
c This air flow which adheres to the ceiling
by “Coanda effect”, discovered by the Romanian
aerodynamic engineer Henri Coanda (1886-1972),
has the beneficial effect of an air flow induction
phenomenon. Thus, the air mixture in the room
is more important, as the heated airstream
is quickly pumped and mixed with the cool
airstream, plus the ambient temperature
in the room is more homogeneous.
c High induction of
the ambiant air flow.
c No By pass phenomenon
between nozzles and air inlet grille.
WINDOWS
c The air flow follow the ceiling.
c Virtual “casing”.
The innovation at our
clients disposal
COADIS Cassette created in accordance with ENIO7730
norm: “Determination of the PMV and PPD indices and
specification of the conditions for comfort”
Thermal
comfort
Isotemperature curves
in medium speed
comfort
COADIS Cassette has been
developped to obtain
the best reduction of all local
discomforts in the occupied
zone (comfort zone):
c air speeds must not
exceed 0,25 m/s,
c temperature vertical
ratio must not exceed 3K,
c asymetrical radiance must
be minimized with good air
mixing (cold wall phenomenon),
c the ground temperature
must be between 23°C and 25°C
for a seated person,
c acoustic comfort, with
low noise level.
Obstacle in the air stream
(beams, light fitting, etc.) should
be avoided as the air jet can
break away from the ceiling and
disturb comfort level. It is clear
that various construction trades
must work together to ensure
thermal and acoustic comfort
and high quality air diffusion.
Use com
Easy m
(M)
Acoustic
The occupied zone (comfort zone)
is defined in accordance with
European working group
CEN/TC/156/WG7:
c distance from floor 1,80 m,
distance from external wall
0,5 m.
(M)
Aeraulic
comfort
Isovelocities curves
in medium speed
(M)
COADIS range
(M)
c 2 models: Classic and Raised.
c 3 sizes: 235/11, 22 and 33.
c Fan motors: 7 speed, factory wired
for 3 speed (high/med/low).
(repère)
(M3/h)
(kW)
(kW)
R#
Qa
Pt
Ps
330
255
150
540
370
250
720
500
350
1,74
1,45
0,97
2,85
2,19
1,62
4,49
3,48
2,63
1,41
1,13
0,73
2,28
1,68
1,21
3,35
2,5
1,84
235/11 GV
MV
PV
235/22 GV
MV
PV
235/33 GV
MV
PV
(kW)
(kW)
P 2T P 4T
5,13
4,23
2,75
8,64
6,39
4,67
12
8,96
6,65
2
1,8
1,39
4,02
3,3
2,67
6,29
5,22
4,26
(W B.élec) (NR) (W mot.)
Re
600
ou
1200
900
ou
1800
1200
1800
2400
Lp Pa
39
33
22
41
32
23
39
31
19
64
46
37
100
78
46
114
79
50
A
design which answered
to actual needs
Visual comfort
VALVE IN OPTION
COADIS is inside the false ceiling instead
of panels 600*600 or 600*1200 (coil, valves,
pan, electrical box included in this space).
c Directionnal nozzles.
c No visible screw.
c White RAL 9010 complet panel.
c Discreet punchet inlet grille.
c Filter not visible behind
the grille.
c Integrated pipings for valve
connection: 40 mm for a 4 way valve.
c Pan height (93 or 159 mm on
the classic or raised version) for
draining the condensates by gravity
directly into the main drain pipe.
c Metallic electrical closed box
with DIN rail included as standard.
mfort
maintenance
▲
▲
c Withdrawal of the filter
without complete removal
of return air grille.
c Easy and economic
maintenance.
(Long x larg x haut mm )
L*l*H*
W*(kg)
595*595*300
22
595*895*300
30
595*1195*300
42
c Withdrawal of the fan
assembly via the return
air grille.
c COADIS Cassette can be
embedded in the false ceiling
instead of panels.
c Pre-cut hole for self control fresh
air module.
c Possibility of standardized
module, diameter: 100 or 125
(15 to 180 m3/h).
c Polymer material smooth drain pan.
c Dry drain pan to avoid water
retention and bacteria proliferation.
c Four reversible drain pan connections
(front or rear): 15, 16, 22 or 28 mm.
a
wide choice
of electronic control system
V20C
control system
The V20C thermostat is a PI control system on water via an
electrothermal valve.
c Potentiometer thermostat in wall version or with display.
c The control of the 3 ventilation speeds is manual or automatic.
c The V20C offers multiple setting options.
c A potential free input can be combined with a window contact or a
programmable clock to coontrol the operating mode : comfort,
economy or anti frost.
V20A
control system
The V20A thermostat combine the simplicity
of electromechanics with the performance
of electronic.
c Individual ON/OFF control system.
c The control of the 3 ventilation speeds
is manual.
c The temperature is set using a potentiometer.
c Possibility to set the neutral zone and
the mid point of the cooling set point.
V200
control system
c V200 control system
The V200 is a PI control
system which
automatically controls
electrothermal valve
opening, the time
proportionnal activation of
the electric coil and the ventilation speeds.
c The Master/Slave fonction authorize the operation of several
units in the same room.
c Comfort/economy contact and windows contact.
c The comfort setting with a simple temperature setpoint potentiometer + /and a comfort/Antifrost switch.
c The control of the 3 ventilation speeds in automatic or manual.
c Centralised single-zone control up to 50 units is available.
ILDH CHILLER
TMF CO3
control system
EXTRACT FAN
COADIS
c The V2000 PI controls the valve(s), electric coil
and the three ventilation speeds according to an
operating algorithm validated in a thermal
chamber.
c The V2000® is equiped with automatic or
manual ventilation speed selection.
c The control system controls 24V 2 way
(3 points) actuators. These actuators make
it possible to stabilise any valve opening from
0 to 100%.
c For optimised energy management, the V2000®
uses an open communication bus to exchange
information.
c A windows contact and a stop emergency
contact.
c Remote consultation and control of operating
parameters and operating statuses is available.
c Compatible with room modifications, changing
the unit settings allows easy configuration.
c Operation in a standalone circuit with no
building control system connection is possible
with the V2000® “Master/Slave” function.
®
Able to control 72 Terminal units equipped with V2000 control systems.
The TMF C03 performs the main functions of a building management system:
c time programming by zone, handling Comfort and economy operating modes,
c control of 6 independent zones, which can each comprise several
Master/Slave functions combined with individual units,
c temperature set point setting for each zone and operating mode,
c time programming of 2 ON/OFF outputs (optionnal):
PAC ; air extractor, etc.,
c smart card backup and programming,
c protection against power cuts,
c …,
c…
COMMUNICATION
CMF 300
VIA MODEM
LIGNE BUS
COADIS
POWER
SUPPLY
CMF 300 BMS, on a windows environment PC:
c able to control 300 Terminal units equipped with V2000
control systems,
c time programming, different set-point temperature
settings, etc.,
c the permanent screen represents the different
drawings of the building,
c remote management is used to access the remote
system via a modem,
c the temperature logs (rooms, set-points) can be
restored on screen or colour printer.
Depending on the required configuration, it can handle:
c 1 Batibus/Jbus gateway,
c 32 status or error inputs,
c 16 On-Off time controlled outputs.
INTERFACE
BATIBUS/JBUS
BUILDING MANAGEMENT SYSTEM
Communicante
V2000®