Test Report - DSF Technologies
Transcription
Test Report - DSF Technologies
We help ideas meet the real world Test Report DANAK Reg. no. 19 EMC immunity test of SELCO Arc Detecting and Protection System according to EU specifications Performed for SELCO A/S DANAK-197671 Project no.: E502289-1 Page 1 of 14 2 annexes 02 November 2004 DELTA Danish Electronics, Light & Acoustics Venlighedsvej 4 2970 Hørsholm Denmark Tel. (+45) 72 19 40 00 Fax (+45) 72 19 40 01 www.delta.dk This report is issued under the rules of DANAK (Danish Accreditation). Further information about DANAK can be found at www.danak.dk. The report must not be reproduced, except in full, without the written approval of DELTA. 20dan-uk-k DANAK-197671 DELTA-E502289-1 Page 2 of 14 Title EMC immunity test of SELCO Arc Detecting and Protection System according to EU specifications Test object SELCO Arc Detecting and Protection Systems Report no. DANAK-197671 Project no. E502289-1 Test period 28 July to 7 October 2004 Client SELCO A/S Meterbuen 6-12 P.O.Box 40 2740 Skovlunde Denmark Telephone (+45) 70 26 11 22 Fax (+45) 70 26 25 22 Contact person Mr. Erik Mikkelsen Manufacturer SELCO A/S Specifications EN 50263:1999 Electromagnetic compatibility (EMC) Product standard for measuring relays and protection equipment Results No mal functions were detected. The criteria for compliance are listed in Section 3.2 Test personnel Poul Østergarrd Madsen Date 02 November 2004 Project manager Poul Østergaard Madsen Project Manager - EMC DELTA Responsible Per Thåstrup Jensen Business Manager DELTA PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 3 of 14 Table of contents Page 1. Summary of tests 4 2. 2.1 2.2 2.3 2.4 Test objects and auxiliary equipment Test object 1 - Arc detection relay Test object 2 - Junction box Test object 3 - Detector AUX equipment - Circuit breaker 5 5 5 5 5 3. 3.1 3.2 General test conditions Test set-up Criteria for compliance 6 6 7 4. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Test and results Immunity to radio frequency electromagnetic field Immunity to conducted radio frequency interference Immunity to electrostatic discharges, ESD Immunity to electrical fast transients, Bursts Immunity to 1 MHz burst Immunity to surge transients Immunity to voltage dips and interruptions Annex 1 Text (1 pages) Annex 2 Photos (8 pages) PMa/BLJ 8 8 9 10 11 12 13 14 DANAK-197671 DELTA-E502289-1 Page 4 of 14 1. Summary of tests Tests Test methods Results Conducted radio frequency interference EN 61000-4-6:1996+A1 Passed Electrical fast transients EN 61000-4-4:1995+A1+A2 Passed 1 MHz burst IEC 60255-22-1 Electrostatic discharges EN 61000-4-2:1995+A1+A2 Passed Radio frequency electromagnetic fields EN 61000-4-3:1996+A1+A2 Passed Surge transients EN 61000-4-5:1995+A1 Passed Voltage dips and interruptions IEC 60255-11 Passed Immunity to rated power frequency magnetic field EN 61000-4-8:1993+A1 Not applicable 1) Passed 1) As the test objects do not contain equipment or parts, which are sensitive to a magnetic field, this test is not applicable. Conclusion The test objects mentioned in this report meet the requirements of the standard stated below as to the test phenomena mentioned above. • EN 50263:1999. The test results relate only to the objects tested. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 5 of 14 2. Test objects and auxiliary equipment 2.1 Test object 1 - Arc detection relay Category Manufacturer Model / type Part no. Serial no. Supply voltage Operational mode 2.2 Test object 2 - Junction box Category Manufacturer Model / type Part no. Serial no. Supply voltage Operational mode 2.3 Electrical relays SELCO A/S A0200/0300 From test object 2 Normal AUX equipment - Circuit breaker Manufacturer Model / type Part no. Serial no. Supply voltage PMa/BLJ Electrical relays SELCO A/S D0400 From test object 1 Normal Test object 3 - Detector Category Manufacturer Model / type Part no. Serial no. Supply voltage Operational mode 2.4 Electrical relays SELCO A/S D0900 230 VAC Normal Mitsubishi Electronics NF100-CS 230 VAC DANAK-197671 DELTA-E502289-1 Page 6 of 14 3. General test conditions 3.1 Test set-up 230 VAC 2.1 Test object 1 Arc detecting relay D0900 2.4 AUX Circuit breaker NF100-CS PMa/BLJ 2.2 Test object 2 Junction box D0400 2.3 Test object 3 Detector A0200/0300 DANAK-197671 DELTA-E502289-1 Page 7 of 14 3.2 Criteria for compliance The SELCO Arc Detecting and Protection System was set for detection of an arc. During the tests no trips must occur. During the immunity tests to radio frequency electromagnetic fields and conducted frequency interference, it was checked that an arc will be detected. Before and after performing the individual tests the trip function was tested. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 8 of 14 4. Test and results 4.1 Immunity to radio frequency electromagnetic field Client Item Manufacturer Type Serial no. Test method(s) Temperature Frequency range SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S EN 61000-4-3:1996+A1+A2 23.0°C Modulation Sheet Project no. Date Sign. Test site A - 1-1 E502289-1 2004-07-28 PMa Room B Humidity 36.0% R.H. Polarisa- Amplitude Remarks tion [V/m] (Description of reaction) 80-1000 MHz 80% AM - 1 kHz Horizontal 10 No reaction 80-1000 MHz 80% AM - 1 kHz Vertical 10 No reaction 200 Hz pulse Vertical 10 No reaction Horizontal 10 No reaction 895-905 MHz 50% duty cycle 895-905 MHz 200 Hz pulse 50% duty cycle Compliant Yes. Comment(s) None. Uncertainty on test level +/-1.7 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 9 of 14 4.2 Immunity to conducted radio frequency interference Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S EN 61000-4-6:1996+A1 23.8°C Sheet Project no. Date Sign. Test site B - 1-1 E502289-1 2004-07-28 PMa Midilab Humidity 32.0% R.H. Manufacturers Test standards Coupling Frequency range name of port name of port network [MHz] Modulation AC port 230 VAC AC Power CDN 29813 0.15 - 80 MHz 80% AM - 1 kHz 10 Vrms Process port 230 Out CDN 29816 0.15 - 80 MHz 80% AM - 1 kHz 10 Vrms No reaction Signal port Signal port CDN 29746 0.15 - 80 MHz 80% AM - 1 kHz 10 Vrms No reaction Compliant Yes. Comment(s) None. Uncertainty on test level +/-3.0 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ Amplitude Remarks [Vrms] (Description of reaction) No reaction DANAK-197671 DELTA-E502289-1 Page 10 of 14 4.3 Immunity to electrostatic discharges, ESD Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S EN 61000-4-2:1995+A1+A2 21.3°C Sheet Project no. Date Sign. Test site E - 1-1 E502289-1 2004-10-07 PMa Room A Humidity 44.3% R.H. Surface under Amplitude Discharge type Coupling plane Polarity Susceptible Remarks test [kV] (Air/Contact) (HCP/VCP) (+/-) (Yes/No) (Description of reaction) Enclosure 2, 4, 6 Contact HCP +/- No 2, 4, 6 Contact VCP +/- No No reaction Enclosure (Switch) 2, 4, 6 Contact - +/- No No reaction Enclosure 2, 4 8 Air - +/- No No reaction Compliant Yes. Comment(s) Number of discharges: Air: 25(-) and 25(+) at each level. Contact: 25(-) and 25(+) at each level. No reaction Identification of discharge areas: Contact discharges have been submitted to all conductive parts of the EUT enclosure and connectors. In addition contact discharges have been submitted to the horizontal coupling plane and a vertical coupling plane 10 cm from the EUT enclosure. Air discharges have been submitted to all non-conductive parts of the EUT enclosure. Uncertainty on test level +/-0.5 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 11 of 14 4.4 Immunity to electrical fast transients, Bursts Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S EN 61000-4-4:1995+A1+A2 24.1°C Sheet Project no. Date Sign. Test site L - 1-1 E502289-1 2004-07-29 PMa Midilab Humidity 33.5% R.H. Test characteristics Burst duration Spike repetition frequency Manufacturers Test standards name of port name of port AC port – AC Power 15 ms 5 kHz Coupling Amplitude Polarity Susceptible Remarks [kV] (+/-) (Yes/ No) (Description of reaction) 1 +/- No No reaction L - GP 230 VAC N - GP 1 +/- No No reaction PE - GP 1 +/- No No reaction L - GP 2 +/- No No reaction N - GP 2 +/- No No reaction PE - GP 2 +/- No No reaction Process port 230 VAC Out Clamp 1 +/- No No reaction 2 +/- No No reaction Signal port Signal port Clamp 1 +/- No No reaction 2 +/- No No reaction Compliant Yes. Comment(s) None. Uncertainty on test level +/-1.1 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 12 of 14 4.5 Immunity to 1 MHz burst Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S IEC 60255-22-1 24.1°C Sheet Project no. Date Sign. Test site X - 1-1 E502289-1 2004-07-29 PMa Midilab Humidity 33.5% R.H. Test characteristics Burst duration Spike repetition frequency Manufacturers Test standards name of port name of port AC port - 230 VAC AC Power 15 ms 400 Hz Coupling Amplitude Polarity Susceptible Remarks [kV] (+/-) (Yes/ No) (Description of reaction) L - GP 1 +/- No No reaction N - GP 1 +/- No No reaction PE - GP 1 +/- No No reaction L-N 2.5 +/- No No reaction L-N 2.5 +/- No No reaction Compliant Yes. Comment(s) None. Uncertainty on test level +/-1.1 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 13 of 14 4.6 Immunity to surge transients Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCO A/S D0900, D0400 and A0200/0300 SELCO A/S EN 61000-4-5:1995+A1 21.3°C Sheet Project no. Date Sign. Test site M - 1-1 E502289-1 2004-10-07 PMa Room A Humidity 44.3% R.H. Test characteristics Open circuit voltage waveform Short circuit current waveform Manufacturers Test name of port standards Coupling 1.2/50 µs 8/20 µs Amplitude Phase [kV] name of Generator No. of Polarity Susceptible Remarks angle impedance pulses (+/-) (Yes/No) (Description of reac- [deg] [Ohm] port AC port – (each tion) mode) AC Power L -PE 0.5 0, 90, 230 VAC 12 5 +/- No No reaction 12 5 +/- No No reaction 12 5 +/- No No reaction 12 5 +/- No No reaction 12 5 +/- No No reaction 12 5 +/- No No reaction 2 5 +/- No No reaction 2 5 +/- No No reaction 270 1 0, 90, 270. 2 0, 90, 270 N - PE 0,5 0, 90, 270. 1 0, 90, 270 2 0, 90, 270. L-N 0.5 0, 90, 270 1 0, 90, 270 Compliant Yes. Comment(s) None. Uncertainty on test level +/-1.0 dB. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Page 14 of 14 4.7 Immunity to voltage dips and interruptions Client Item Manufacturer Type Serial no. Test method(s) Temperature SELCA A/S D0900, D0400 and A0200/0300 SELCO A/S IEC 60255-11 21.3°C Sheet Project no. Date Sign. Test site V - 1-1 E502289-1 2004-10-07 PMa Room A Humidity 44.3% R.H. Manufacturers Nominal Changed voltage Voltage Duration Changed Remarks name of port voltage [Vrms] change [sec. or msec.] frequency (Description of reaction) [Vrms] AC port 230 VAC 230 VAC [%] [Hz] 0 Vrms 100% 5 msec - No reaction 0 Vrms 100 % 10 msec - No reaction 0 Vrms 100 % 20 msec - No reaction 0 Vrms 100 % 50 msec - No reaction 0 Vrms 100 % 100 msec - No reaction 0 Vrms 100 % 200 msec - No reaction Compliant Yes. Comment(s) None. Criteria for compliance See Section 3.2. Results No malfunction was detected. PMa/BLJ DANAK-197671 DELTA-E502289-1 Annex 1 Text (1 pages) PMa/BLJ DANAK-197671 DELTA-E502289-1 NO. DESCRIPTION MANUFACTURER TYPE NO. 29614 ESD GENERATOR, AIR AND CONTACT DISCHARGE 3 CHANNEL SIGNAL INJECTION BOX HIGH FREQ. GEN. 10 kHz - 1 GHz. SAMPLING OSCILLOSCOPE, 100 MHz, 500 MS/s SHIELD-LINE CDN NETWORK, IEC 61000-4-6 2-LINE CDN NETWORK, IEC 61000-4-6 3-LINE CDN NETWORK, IEC 61000-4-6 -40 dBc VOLTAGE SAMPLER, DC-100 MHz CAPACITIVE COPLING CLAMP AC SOURCE W. HARMONIC/FLICKER TEST OPTION BROADBAND POWER AMPLIFIER, 10 kHz - 250 MHz, 75 W DIGITAL MULTIMETER W. HPIB ELECTRICAL FAST TRANSIENT (BURST) GENERATOR ELECTRONIC SURGE GENERATOR COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST RF POWER ATTENUATOR, 50 OHM, 6 dB, 150 W 1 MHz HFD RELAY TESTER GENERATOR POWER METER ANTENNA AMPLIFIER POWER SENSOR CABLE KEYTEK MZ-15 EC MARCONI TEKTRONIX DELTA EMC DEPT. MEB MEB DELTA EMC DEPT. DELTA EMC HEWLETT-PACKARD DS 5103 2022 TDS 320 SHIELD-LINE CDN M2 M3 SAMPLER_VER_2 IEC 1000-4-4 6842A 29645 29704 29732 29746 29813 29816 29843 29864 29859 29904 29911 29913 29914 29964 29977 49007 49159 49177 49175 49179 49182 49204 PMa/BLJ AMPLIFIER RESEARCH 75A250 HEWLETT-PACKARD EM TEST 34401A EFT 500 EM TEST HEWLETT-PACKARD VCS 500 8471D NARDA HAEFELEY MARCONI BIRD AR AR BIRD SUHNER 769-6 P3, WO580333 2024 4421 AT1080 100W1000M1 4022 RG214U DANAK-197671 DELTA-E502289-1 Annex 2 Photos (8 pages) PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.1 Immunity to radio frequency electromagnetic field. SELCO Arc Detecting and Protection System. Photo A2.2 Immunity to radio frequency electromagnetic field. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.3 Immunity to conducted radio frequency interference. SELCO Arc Detecting and Protection System. Photo A2.4 Immunity to conducted radio frequency interference. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.5 Immunity to conducted radio frequency interference. SELCO Arc Detecting and Protection System. Photo A2.6 Immunity to electrostatic discharge - ESD. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.7 Immunity to electrostatic discharge - ESD. SELCO Arc Detecting and Protection System. Photo A2.8 Immunity to electrostatic discharge - ESD. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.9 Immunity to electrostatic discharge - ESD. SELCO Arc Detecting and Protection System. Photo A2.10 Immunity to electrical fast transients - Bursts. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.11 Immunity to electrical fast transients - Bursts. SELCO Arc Detecting and Protection System. Photo A2.12 Immunity to 1 MHz bursts. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.13 Immunity to 1 MHz bursts. SELCO Arc Detecting and Protection System. Photo A2.14 Immunity to 1 MHz burst. SELCO Arc Detecting and Protection System. PMa/BLJ DANAK-197671 DELTA-E502289-1 Photo A2.15 Immunity to surge transients. SELCO Arc Detecting and Protection System. Photo A2.16 Immunity to voltage dips and interruptions. SELCO Arc Detecting and Protection System. PMa/BLJ